background image

8 Configuration

Installer reference guide

59

RRLQ004~008CA + RHBH/X04+08CB
ROTEX HPSU low temperature Bi‑bloc
4P384979-1C – 2017.04

In case of…

…then the following applies:

One leaving water temperature
zone

▪ When 

the 

leaving 

water

temperature  home  page  is
OFF  and  the  outdoor  ambient
temperature  drops  below  4°C,
then  the  unit  will  supply
leaving  water  to  the  heat
emitters  to  heat  up  the  room
again,  and  the  leaving  water
temperature  setpoint  will  be
lowered.

▪ When 

the 

leaving 

water

temperature home page is ON,
the  external  room  thermostat
is  "Thermo  OFF"  and  the
outdoor  ambient  temperature
drops below 4°C, then the unit
will supply leaving water to the
heat  emitters  to  heat  up  the
room  again  and  the  leaving
water temperature setpoint will
be lowered.

▪ When 

the 

leaving 

water

temperature home page is ON
and 

the 

external 

room

thermostat  is  "Thermo  ON",
then  room  frost  protection  is
guaranteed  by  the  normal
logic.

Two leaving water temperature
zones

▪ When 

the 

leaving 

water

temperature  home  page  is
OFF,  and  the  outdoor  ambient
temperature  drops  below  4°C,
then  the  unit  will  supply
leaving  water  to  the  heat
emitters  to  heat  up  the  room
again,  and  the  leaving  water
temperature  setpoint  will  be
lowered.

▪ When 

the 

leaving 

water

temperature home page is ON,
the 

operation 

mode 

is

"heating",  and  the  outdoor
ambient  temperature  drops
below  4°C,  then  the  unit  will
supply  leaving  water  to  the
heat  emitters  to  heat  up  the
room  again,  and  the  leaving
water temperature setpoint will
be lowered.

▪ The  selection  of  "cooling"  or

"heating"  is  done  via  the  user
interface.  When  the  leaving
water  temperature  home  page
is ON and the operation mode
is  "cooling",  then  there  is  no
protection.

[C‑07]=0: leaving water temperature control

Under  leaving  water  temperature  control,  room  frost  protection  is
NOT  guaranteed.  However,  if  [2‑06]  is  set  to  "1",  limited  frost
protection by the unit is possible:

▪ When  the  leaving  water  temperature  home  page  is  OFF  and  the

outdoor  ambient  temperature  drops  below  4°C,  then  the  unit  will
supply  leaving  water  to  the  heat  emitters  to  heat  up  the  room
again, and the leaving water temperature setpoint will be lowered.

▪ When  the  leaving  water  temperature  home  page  is  ON  and  the

operation mode is "heating", then the unit will supply leaving water
to the heat emitters to heat up the room according to normal logic.

▪ When  the  leaving  water  temperature  home  page  is  ON  and  the

operation mode is "cooling", then there is no protection.

Shut-off valve

The  following  is  only  applicable  in  case  of  2  leaving  water
temperature  zones.  In  case  of  1  leaving  water  temperature  zone,
connect the shut-off valve to the heating/cooling output.

The  shut-off  valve,  which  is  in  the  main  leaving  water  temperature
zone, output is configurable.

INFORMATION

During  defrost  operation,  the  shut-off  valve  is  ALWAYS
opened.

Thermo On/OFF: the valve closes, depending on [F-0B] when there
is no heating demand from the main zone. Enable this setting to:

▪ avoid  leaving  water  supply  to  the  heat  emitters  in  the  main  LWT

zone (through the mixing valve station) when there is request from
the additional LWT zone.

▪ activate the On/OFF pump of the mixing valve station ONLY when

there is demand. See 

"5 Application guidelines" on page 10

.

#

Code

Description

[A.3.1.1.6.1] [F-0B]

The shut-off valve:

▪ 0  (No)(default):  is  NOT  influenced  by

heating or cooling demand.

▪ 1  (Yes):  closes  when  there  is  NO

heating or cooling demand.

INFORMATION

The setting [F‑0B] is only valid when there is a thermostat
or  external  room  thermostat  request  setting  (NOT  in  case
of leaving water temperature setting).

Cooling:  ONLY  applicable  for  RHBX  and  RHVX.  The  shut-off  valve
closes,  depending  on  [F-0C]  when  the  unit  is  running  in  cooling
operation  mode.  Enable  this  setting  to  avoid  cold  leaving  water
through the heat emitter and the forming of condensation (e.g. under
floor heating loops or radiators).

#

Code

Description

[A.3.1.1.6.2] [F-0C]

The shut-off valve:

▪ 0 (No): is NOT influenced by changing

the space operation mode to cooling.

▪ 1  (Yes)(default):  closes  when  the

space operation mode is cooling.

Operation range

Depending on the average outdoor temperature, the operation of the
unit in space heating or space cooling is prohibited.

Space heating OFF temp: When the averaged outdoor temperature
raises  above  this  value,  space  heating  is  turned  OFF  to  avoid
overheating.

#

Code

Description

[A.3.3.1]

[4-02]

▪ RHBH/X04+08  and  RHVH/X04+08:

14°C~35°C (default: 25°C)

▪ RHBH/X11+16  and  RHVH/X11+16:

14°C~35°C (default: 35°C)

The same setting is also used in
automatic heating/cooling changeover.

Space  cooling  On  temp:  ONLY  applicable  for  RHBX  and  RHVX.
When  the  averaged  outdoor  temperature  drops  below  this  value,
space cooling is turned OFF.

Summary of Contents for RHBH04CB3V

Page 1: ...Installer reference guide ROTEX HPSU low temperature Bi bloc English Installer reference guide ROTEX HPSU low temperature Bi bloc RRLQ004 006 008CA RHBH X04 08CB...

Page 2: ...24 6 4 Preparing water piping 24 6 4 1 Water circuit requirements 24 6 4 2 Formula to calculate the expansion vessel pre pressure 25 6 4 3 To check the water volume and flow rate 25 6 4 4 Changing th...

Page 3: ...mum flow rate 74 9 4 2 Air purge function 74 9 4 3 To perform a test run 75 9 4 4 To perform an actuator test run 75 9 4 5 Underfloor heating screed dryout 75 10 Hand over to the user 76 11 Maintenanc...

Page 4: ...TION Do NOT touch the air inlet or aluminium fins of the unit NOTICE Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit NOTICE Works executed on the outdoor...

Page 5: ...e cylinder is marked with Liquid filling siphon attached Charge with the cylinder upright A siphon tube is NOT present Charge with the cylinder upside down Open refrigerant cylinders slowly Charge the...

Page 6: ...applicable if the power supply is three phase and the compressor has an ON OFF starting method If there exists the possibility of reversed phase after a momentary black out and the power goes on and o...

Page 7: ...r unit are delivered on site It contains information about Unpacking and handling the units Removing the accessories from the units Keep the following in mind At delivery the unit must be checked for...

Page 8: ...l safety precautions the indoor unit installation manual the operation manual and the addendum book for optional equipment are located in the upper part of the box Follow the procedure below to remove...

Page 9: ...A The drain pan heater is required to avoid freezing up of the drain pan It is recommended to install this option in colder regions with possible low ambient temperatures or heavy snowfall For install...

Page 10: ...d system behaviour For installation instructions see the installation manual of the remote outdoor sensor PC configurator EKPCCAB The PC cable makes a connection between the switch box of the indoor u...

Page 11: ...2 1 Single room Under floor heating or radiators Wired room thermostat Setup B A a A Main leaving water temperature zone B One single room a User interface used as room thermostat The under floor heat...

Page 12: ...om the remote controller of the heat pump convectors Configuration Setting Value Unit temperature control A 2 1 7 Code C 07 1 Ext RT control Unit operation is decided by the external thermostat Settin...

Page 13: ...nit The room temperature of the main room is controlled by the user interface used as thermostat A thermostatic valve is installed before the under floor heating in each of the other rooms INFORMATION...

Page 14: ...ernal room thermostat b Remote controller of the heat pump convectors For each room with heat pump convectors The heat pump convectors are directly connected to the indoor unit For each room with unde...

Page 15: ...signals of each heat pump convector are connected in parallel to the digital input on the indoor unit X2M 1 and X2M 4 The indoor unit will only supply the desired additional leaving water temperature...

Page 16: ...perature set via the user interface When weather dependent operation is active the water temperature is determined automatically depending on the outdoor temperature During heating operation of the au...

Page 17: ...can be An outdoor temperature thermostat An electricity tariff contact A manually operated contact Setup Connect the following field wiring L N H Com A K2A K1A X2M BTI K2A K1A Indoor Auto Boiler 1 2 3...

Page 18: ...ume How many showers are needed per day 1 shower 10 min 10 l min 100 l How many baths are needed per day 1 bath 150 l How much water is needed at the kitchen sink per day 1 sink 2 min 5 l min 10 l Are...

Page 19: ...ater if applicable in the domestic hot water tank Setup and configuration No additional equipment needed Only in case a booster heater is present in the system measure its capacity resistance measurem...

Page 20: ...neral rule Power meter 1 Measures the outdoor unit Power meter 2 Measures the rest i e indoor unit backup heater and optional booster heater Setup Connect power meter 1 to X5M 7 and X5M 8 Connect powe...

Page 21: ...management system a Power limitation activation 4 digital inputs b Backup heater c Booster heater Pi t DI4 DI3 DI1 a b Pi Power input t Time DI Digital inputs power limitation levels a Power limitati...

Page 22: ...in the automatic heating cooling changeover logic To protect the outdoor unit the internal sensor of the outdoor unit is always used 6 Preparation 6 1 Overview Preparation This chapter describes what...

Page 23: ...25 C in heating mode 6 2 2 Additional installation site requirements of the outdoor unit in cold climates Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER...

Page 24: ...thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation 6 4 Preparing water piping 6 4 1 Water circuit requirements INFORMATION Also rea...

Page 25: ...ent galvanic corrosion Valve Separating circuits When using a 3 way valve in the water circuit make sure that the domestic hot water circuit and the floor heating circuit is fully separated Valve Chan...

Page 26: ...the following Increase the pre pressure according to the required installation height difference The pre pressure should increase by 0 1 bar for each metre above 7 m Check if the water volume does NO...

Page 27: ...r fire Do NOT install a phase advancing capacitor because this unit is equipped with an inverter A phase advancing capacitor will reduce performance and may cause accidents WARNING All wiring must be...

Page 28: ...heater and booster heater b Backup heater c Indoor unit d Domestic hot water tank e Booster heater Item Description Wires Maximum running current Outdoor unit and indoor unit power supply 1 Power supp...

Page 29: ...e unit Example When connecting the refrigerant piping When connecting the electrical wiring When maintaining or servicing the unit DANGER RISK OF ELECTROCUTION Do NOT leave the unit unattended when th...

Page 30: ...per protruding part of the bolts is 15 mm 283 5 8 0 1 0 0 mm 1 0 0 300 In any case provide at least 300 mm of free space below the unit Additionally make sure the unit is positioned at least 100 mm ab...

Page 31: ...the unit Avoid drain water flowing over the footpath so that it does not become slippery in case of ambient freezing temperatures If you install the unit on a frame install a waterproof plate within 1...

Page 32: ...4 2 Precautions when mounting the indoor unit INFORMATION Also read the precautions and requirements in the following chapters General safety precautions Preparation 7 4 3 To install the indoor unit C...

Page 33: ...to guarantee its lifetime The drying material may dissolve and damage the system NOTICE Take the following precautions on refrigerant piping into account Avoid anything but the designated refrigerant...

Page 34: ...sure the flare nut is fitted 7 5 6 To braze the pipe end The indoor unit and outdoor unit have flare connections Connect both ends without brazing If brazing should be needed take the following into...

Page 35: ...tem Tightening torque N m Service port cap 11 5 13 9 7 5 8 To connect the refrigerant piping to the outdoor unit 1 Connect the liquid refrigerant connection from the indoor unit to the liquid stop val...

Page 36: ...rass flare nut and the copper flare 1 Charge the system with nitrogen gas up to a gauge pressure of at least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect small l...

Page 37: ...ength is the one way length of liquid piping 7 7 4 To determine the complete recharge amount INFORMATION If a complete recharge is necessary the total refrigerant charge is the factory refrigerant cha...

Page 38: ...t connection of the domestic hot water cylinder To avoid back siphonage it is recommended to install a non return valve on the water inlet of the domestic hot water tank in accordance with the applica...

Page 39: ...changeover to an external heat source 13 Connecting the power consumption digital inputs 14 Connecting the safety thermostat 7 9 2 About electrical compliance Only for indoor units See 7 9 8 To conne...

Page 40: ...inputs field supply Outdoor ambient temperature sensor option Electrical meters field supply Safety thermostat field supply b High voltage power supply Interconnection cable Normal kWh rate power supp...

Page 41: ...es according to the applicable legislation CAUTION To guarantee the unit is completely earthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary dep...

Page 42: ...of the backup heater miswiring is possible To detect possible miswiring it is highly recommended to measure the resistance value of the heater elements Depending on the different backup heater types...

Page 43: ...4A 4B 4C or 4D 5 Reinstall the faceplate onto the wallplate Be careful NOT to pinch the wiring when attaching the frontplate to the unit a The main user interface is required for operation but has to...

Page 44: ...put cable to the appropriate terminals as shown in the illustration below X1M X2M 29 X1M YC Y1 Y2 Y3 Y4 A4P X2M a a Installation of EKRP1HB is required 2 Fix the cable with cable ties to the cable tie...

Page 45: ...ion cable d Liquid pipe e Liquid pipe insulation f Finishing tape 2 Install the service cover 7 10 2 To close the outdoor unit 1 Close the switch box cover 2 Close the service cover NOTICE When closin...

Page 46: ...ler settings Overview settings To set the user permission level to Installer 1 Set the user permission level to Adv end user 2 Go to 6 4 Information User permission level 3 Press for more than 4 secon...

Page 47: ...he other user interface will be overwritten Receive data the user interface you are operating does NOT contain the correct data and the data on the other user interface will be used to overwrite 6 The...

Page 48: ...400 V 9W 5 3PN 1 1 2 9 kW 3N 400 V 9W Relay setting Relay setting Backup heater operation If backup heater step 1 is active If backup heater step 2 is active 1 1 2 Relay 1 ON Relays 1 2 ON 1 2 Relay...

Page 49: ...b c d b c a Space heating cooling control user interface b OFF c On d Pump operation continued Code Description A 2 1 9 F 0D continuation 1 Sample default The pump is ON when there is heating or cooli...

Page 50: ...e field supply f Shower field supply g Cold water INFORMATION The correct domestic hot water default settings becomes only applicable when domestic hot water operation is activated E 05 1 Thermostats...

Page 51: ...Normally closed The alarm output will NOT be powered when an alarm occurs See also table below Alarm output logic Code Description A 2 2 6 4 F 04 Bottom plate heater Only applicable for RHBH X11 16 a...

Page 52: ...described in this chapter The weather dependent installer settings define the parameters for the weather dependent operation of the unit When weather dependent operation is active the water temperatu...

Page 53: ...temperature equals or drops below the low ambient temperature 9 03 C 9 02 C default 22 C Note This value should be higher than 1 09 as for low outdoor temperatures less cold water suffices 1 09 Desire...

Page 54: ...d Leaving water temperature Delta T source Temperature difference for entering and leaving water The unit is designed to support under floor loops operation The recommended leaving water temperature s...

Page 55: ...setting can compensate for a slow or a quick heating cooling system during the heat up cool down cycle Note The setting of the emitter type will influence the maximum modulation of the desired leavin...

Page 56: ...ult 33 C 7 4 2 3 8 07 Comfort cooling 9 03 C 9 02 C default 18 C Code Description 7 4 2 4 8 08 Eco cooling 9 03 C 9 02 C default 20 C Preset leaving water temperature shift value for the main leaving...

Page 57: ...TA 4 C 4 enabled L 4 C R 8 C 4 C TA 4 C Leaving water temperature maximum modulation ONLY applicable in room thermostat control and when modulation is enabled The maximum modulation variance on the de...

Page 58: ...ature 2 05 External room thermostat control C 07 1 Allow for the external room thermostat to take care of room frost protection Turn ON the leaving water temperature home page Leaving water temperatur...

Page 59: ...unit will supply leaving water to the heat emitters to heat up the room according to normal logic When the leaving water temperature home page is ON and the operation mode is cooling then there is no...

Page 60: ...t changing from heating to cooling and vice versa Changeover settings related to the outdoor temperature ONLY when automatic is selected Code Description A 3 3 1 4 02 Space heating OFF temp If the out...

Page 61: ...re is weather dependent according to the weather dependent curve During weather dependent operation the end user cannot adjust the desired tank temperature on the user interface Code Description A 4 6...

Page 62: ...enabled and permission signal for auxiliary boiler is ON the booster heater will be restricted even when Ta 5 03 See C 02 3 default The booster heater is allowed when the heat pump is NOT active in do...

Page 63: ...the target domestic hot water temperature is NOT reached The actual maximum running time also depends on setting 8 04 When system layout Room thermostat control This preset value is only taken into ac...

Page 64: ...4 4 2 2 00 Operation day 0 Each day 1 Monday 2 Tuesday 3 Wednesday 4 Thursday 5 Friday 6 Saturday 7 Sunday A 4 4 1 2 01 Disinfection 0 No 1 Yes A 4 4 3 2 02 Start time 00 23 00 step 1 00 A 4 4 4 2 03...

Page 65: ...llowed during domestic hot water operation This setting is only overruled when backup heating is required during defrost operation or malfunctioning of the outdoor unit when A 6 C is enabled Code Desc...

Page 66: ...efines the temperature difference between bivalent ON temperature and bivalent OFF temperature Permission signal X1 X2 EKRP1HB TA C 03 C 04 a b TA Outdoor temperature a Closed b Open Code Description...

Page 67: ...be applied at low outdoor temperature when space heating priority is enabled The corrected higher set point will make sure that the total heat capacity of the water in the tank remains approximately u...

Page 68: ...ferential kWh rate power supply is of type 1 or indoor unit is connected to a normal kWh rate power supply via X2M 30 31 and the backup heater is NOT connected to the preferential kWh rate power suppl...

Page 69: ...6 1 5 09 Limit DI1 0 kW 20 kW step 0 5 kW default 20 kW Code Description A 6 3 6 2 5 0A Limit DI2 0 kW 20 kW step 0 5 kW default 20 kW A 6 3 6 3 5 0B Limit DI3 0 kW 20 kW step 0 5 kW default 20 kW A 6...

Page 70: ...door temperature is higher than 4 02 or lower than F 01 depending on heating cooling operation mode 1 Possible at all outdoor temperatures Pump operation during flow abnormality F 09 defines whether t...

Page 71: ...ersion Energy metering Consumed elec Produced energy Error information Error history Contact helpdesk number Version User interface Indoor unit Outdoor unit User settings Display Temperature lock Set...

Page 72: ...p operation mode Power saving possible User interface location Options DHW operation DHW tank type Contact type main Contact type add Digital I O PCB Demand PCB External kWh meter External kWh meter D...

Page 73: ...le in case of hybrid system The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have not...

Page 74: ...purge 2 Performing an automatic air purge INFORMATION Start by performing a manual air purge When almost all the air is removed perform an automatic air purge If necessary repeat performing the autom...

Page 75: ...ater step 1 test Backup heater step 2 test Pump test INFORMATION Make sure that all air is purged before executing the test run Also avoid disturbances in the water circuit during the test run 2 way v...

Page 76: ...dryout program 3 Select Start dryout and press 4 Select OK and press Result The underfloor heating screed dryout starts and following screen will be shown It stops automatically when done To stop it...

Page 77: ...hecklist for yearly maintenance of the indoor unit Check the following at least once a year Water pressure Water filter Water pressure relief valve Pressure relief valve of the domestic hot water tank...

Page 78: ...NING Prevent hazard due to the inadvertent resetting of the thermal cut out this appliance must NOT be supplied through an external switching device such as a timer or connected to a circuit that is r...

Page 79: ...ght between the indoor unit and the highest point of the water circuit If the indoor unit is located at the highest point of the installation the installation height is considered 0 m The maximum wate...

Page 80: ...han the last expected large hot water tapping This start up can be set by installer settings disinfection function When the Domestic hot water Type Scheduled only is selected it is recommended to prog...

Page 81: ...our dealer P4 00 OU Malfunction of radiating fin temperature sensor Please contact your dealer U0 00 OU Shortage of refrigerant Please contact your dealer U2 00 OU Defect of power supply voltage Pleas...

Page 82: ...ic hot water Type Reheat or Reheat sched is selected it is recommended to program the start up of the disinfection function at least 4 hours later than the last expected large hot water tapping This s...

Page 83: ...into the outdoor unit Possible consequence Self combustion and explosion of the compressor because of air going into the operating compressor Use a separate recovery system so that the unit s compres...

Page 84: ...uT 4 0CuT 4 0CuT 4 0CuT 7 9CuT 7 9CuT 7 9CuT 6 4CuT 6 4CuT M P P 6 4CuT 3TW60815 1 OUTDOOR UNIT OUTDOOR AIR TEMPERATURE THERMISTOR HEAT EXCHANGER HEAT EXCHANGER THERMISTOR CAPILLARY TUBE 1 CAPILLARY T...

Page 85: ...r Water side Shut off valve with drain fill valve Filter Plate heat exchanger Refrigerant inlet Refrigerant outlet Evaporator Condenser Refrigerant inlet Refrigerant outlet Backup heater Flow sensor A...

Page 86: ...ctor X1M X2M Terminal strip Y1E Electronic expansion valve coil Y1R Reversing solenoid valve coil Z1C Z4C Ferrite core Field wiring Terminal strip Connector Terminal Protective earth BLK Black BLU Blu...

Page 87: ...in supply pump M2P Domestic hot water pump M2S 2 way valve for cooling mode M3S 3 way valve for floor heating domestic hot water PC A4P Power circuit PHC1 A4P Optocoupler input circuit Q DI Earth leak...

Page 88: ...ish Translation Changeover to ext heat source Changeover to external heat source If no bottom plate heater If no bottom plate heater Max load Maximum load Min load Minimum load Only for bottom plate h...

Page 89: ...ain X2M 1 4 add X2M 1a 4 main X2M 1 2 3 4 add X2M 1a 2a 3 4 main X2M 1 2 4 add X2M 1a 2a 4 NC valve X2M 5 7 NO valve X2M 6 7 2 core 2 core 2 core 2 core 2 core 2 core signal 5 core 3 core 4 or 3 core...

Page 90: ...ion is expected installation of EKHBDPCA2 drainpan kit must be considered Entering water temperature limit to prevent condensation Entering water temperature C Entering water temperature C Dry bulb te...

Page 91: ...who is qualified to install the product User Person who is owner of the product and or operates the product Applicable legislation All international European national and local directives laws regulat...

Page 92: ...S18CB3V HBH16CB3V HVH16S18CB3V HBX04CB3V HVX04S18CB3V HBX08CB3V HVX08S18CB3V HBX11CB3V HVX11S18CB3V HBX16CB3V HVX16S18CB3V HBH08CB9W HVH08S26CB9W HBH11CB9W HVH11S26CB9W HBH16CB9W HVH16S26CB9W HBX08CB9...

Page 93: ...1 C 35 C 7 7 1 2 1 08 Set weather dependent cooling Leaving water value for low ambient temp for LWT main zone cooling WD curve R W 9 03 9 02 C step 1 C 22 C 7 7 1 2 1 09 Set weather dependent coolin...

Page 94: ...Secondary rtrn 2 Disinf shunt A 2 2 B C 08 R W 0 No 1 Outdoor sensor 2 Room sensor Capacities A 2 3 1 6 02 R W 0 10kW step 0 2kW 3kW 1 0kW 2 A 2 3 2 6 03 R W 0 10kW step 0 2kW 3kW A 2 3 3 6 04 R W 0 1...

Page 95: ...Saturday 7 Sunday A 4 4 3 2 02 R W 0 23 hour step 1 hour 23 A 4 4 4 2 03 R W E 07 1 55 80 C step 5 C 70 C E 07 1 60 C 60 C A 4 4 5 2 04 R W E 07 1 5 60 min step 5 min 10 min E 07 1 40 60 min step 5 mi...

Page 96: ...d A 8 1 05 R W 0 Disabled 1 Enabled A 8 1 06 R W 10 25 C step 1 C 20 C A 8 1 07 R W 25 43 C step 1 C 35 C A 8 1 08 R W 9 03 9 02 C step 1 C 22 C A 8 1 09 R W 9 03 9 02 C step 1 C 18 C A 8 1 0A R W 0 N...

Page 97: ...2 4 A 8 5 0E 1 A 8 6 00 R W 2 20 C step 1 C 2 C A 8 6 01 R W 0 10 C step 1 C 2 C The temperature difference determining the heat pump OFF temperature What is the requested limit for DI2 What is the r...

Page 98: ...6 C step 0 5 C 1 C A 8 9 0D R W 0 8 step 1 0 100 1 4 80 50 5 8 80 50 6 A 8 9 0E 6 A 8 A 00 0 A 8 A 01 0 5 3 6 What is the maximum desired LWT for add zone in cooling What is the desired delta T in hea...

Page 99: ...Type 1 1 Type 2 A 8 E 03 R O 0 No BUH 1 1 step 2 2 steps A 8 E 04 R O 0 No 1 Yes A 8 E 05 R W 0 No 1 1 Yes 2 A 8 E 06 R O 0 No 1 Yes A 8 E 07 R W 0 6 0 Type 1 1 1 Type 2 2 A 8 E 08 R W 0 Disabled 6 1...

Page 100: ...A 8 F 05 0 A 8 F 06 0 A 8 F 09 R W 0 Disabled 1 Enabled A 8 F 0A 0 A 8 F 0B R W 0 No 1 Yes A 8 F 0C R W 0 No 1 Yes A 8 F 0D R W 0 Continuous 1 Sample 2 Request Close shut off valve during thermo OFF C...

Page 101: ......

Page 102: ......

Page 103: ......

Page 104: ...usland Our partners abroad Unsere Partner im Ausland Nos partenaires l tranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granic Na i partne i v zahrani http...

Reviews: