Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
A.3.1.2.2.2
[9-06]
Temperature range
Maximum temp (heating)
R/W
37~depending on outdoor unit, step: 1°C
55°C
A.3.1.2.2.3
[9-07]
Temperature range
Minimum temp (cooling)
R/W
5~18°C, step: 1°C
5°C
A.3.1.2.2.4
[9-08]
Temperature range
Maximum temp (cooling)
R/W
18~22°C, step: 1°C
22°C
└──────────────────
Delta T source
A.3.1.3.1
[9-09]
R/W
3~10°C, step: 1°C
5°C
A.3.1.3.2
[9-0A]
R/W
3~10°C, step: 1°C
5°C
└─
Room thermostat
A.3.2.1.1
[3-07]
Room temp. range
Minimum temp (heating)
R/W
12~18°C, step: A.3.2.4
12°C
A.3.2.1.2
[3-06]
Room temp. range
Maximum temp (heating)
R/W
18~30°C, step: A.3.2.4
30°C
A.3.2.1.3
[3-09]
Room temp. range
Minimum temp (cooling)
R/W
15~25°C, step: A.3.2.4
15°C
A.3.2.1.4
[3-08]
Room temp. range
Maximum temp (cooling)
R/W
25~35°C, step: A.3.2.4
35°C
A.3.2.2
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
A.3.2.3
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
A.3.2.4
R/W
0: 0,5 °C
1: 1 °C
└─
Operation range
14~25°C, step: 1°C
25°C (*5)
14~35°C, step: 1°C
35°C (*6)
A.3.3.2
[F-01]
R/W
10~35°C, step: 1°C
20°C
└─
Domestic hot water (DHW)
└─
Type
A.4.1
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
└─
Disinfection
A.4.4.1
[2-01]
R/W
0: No
1: Yes
A.4.4.2
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
A.4.4.3
[2-02]
R/W
0~23 hour, step: 1 hour
23
A.4.4.4
[2-03]
R/W
[E-07]
≠
1 :
55~80°C, step: 5°C
70°C
[E-07]=1 : 60°C
60°C
A.4.4.5
[2-04]
R/W
[E-07]
≠
1 : 5~60 min, step: 5 min
10 min
[E-07]=1 : 40~60 min, step: 5 min
4
0 min
└─
Maximum setpoint
A.4.5
[6-0E]
R/W
[E-07]
≠
1 : 40~80°C, step: 1°C
60°C
[E-07]=1 : 40~60°C, step: 1°C
60°C
└─
SP mode
A.4.6
R/W
0: Fixed
1: Weather dep.
└─
Weather dependent curve
A.4.7
[0-0B]
Weather-dependent curve
Leaving water value for high ambient temp. for
DHW WD curve.
R/W
35~[6-0E]°C, step: 1°C
50°C
A.4.7
[0-0C]
Weather-dependent curve
Leaving water value for low ambient temp. for
DHW WD curve.
R/W
45~[6-0E]°C, step: 1°C
60
°C
A.4.7
[0-0D]
Weather-dependent curve
High ambient temp. for DHW WD curve.
R/W
10~25°C, step: 1°C
15°C
A.4.7
[0-0E]
Weather-dependent curve
Low ambient temp. for DHW WD curve.
R/W
-40~5°C, step: 1°C
-10°C
└─
Heat sources
└─
Backup heater
A.5.1.1
[4-00]
R/W
0: Disabled
1: Enabled
2: Only DHW
A.5.1.2
R/W
0: Manual
1: Automatic
A.5.1.3
[4-07]
R/W
0: No
1: Yes
A.5.1.4
[5-01]
R/W
-15~35°C, step: 1°C
0°C
└─
System operation
└─
Auto restart
A.6.1
[3-00]
R/W
0: No
1: Yes
└─
Preferential kWh rate
A.6.2.1
[D-00]
R/W
0: None
1: BSH only
2: BUH only
3: All heaters
A.6.2.2
[D-05]
R/W
0: Forced off
1: As normal
└─
Pwr consumpt. Control
A.6.3.1
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
Forced pump OFF
Mode
Operation mode
Enable BUH step 2
Equilibrium temp.
Allowed heaters
Disinfection
Operation day
Start time
Temperature target
Duration
Room temp. offset
Ext. room sensor offset
Room temp. step
Space heating OFF temp
Space cooling On temp
Heating
Cooling
A.3.3.1
[4-02]
R/W
Emergency