background image

7

English

Indoor Unit Installation (1)

5.

Wiring

• Lift the sensor securing plate, remove the front metal plate cover, and connect the branch wiring to the terminal block. 

1) Strip wire ends (15mm).
2) Connect the power supply wire to the terminal block of main wiring box securely.
3) Connect the earth wires to the corresponding terminals.
4) Pull wires to make sure that they are securely latched up, then retain wires with wire retainer.
5) Make sure that the wires do not come in contact with the metal conduit for the heat exchanger. 

 WARNING

• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, 

electrical shock, or fire.

Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., 
from the terminal block.) Doing so may cause electric shock or fire.

• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

 CAUTION

• Carefully run the wires connecting to the sub electrical wiring box so that the wires will not come in contact with the copper 

pipe. If the wires come in contact with the copper pipe, water drops may enter the sub electrical wiring box and the unit may 
malfunction.

• Be sure to connect the wires correctly. An incorrect connection may damage components and make it impossible to 

operate or use the unit.

• When connecting the wires to the terminal block, be sure to curl the wire ends as shown in the following illustration and 

connect each wire to the corresponding terminal from the same direction. Furthermore, make sure that the right 
dimensions of the wire ends stripping are kept.  

• If the stranded wires must be used, make sure to use the round crimp-

style terminal for connection to the power supply terminal block. Place 
the round crimp-style terminals on the wires up to the covered part and 
secure in place. 

1

2

3

1

2

3

H05RN

Shape wires so 
that the front 
metal plate cover 
will fit securely.

Firmly secure wire 
retainer so that 
wires sustain no 
external stress.

Terminal block

Electrical component box

Firmly fix the wires with the 
terminal screws.

Wire retainer

Use 0.75mm

2

 wires.

Make sure that the wires do not 
come in contact with the metal 
conduit for the heat exchanger.

Connect 
the Faston 
terminal 
here.

Bundle the wires 
with a twist tie and 
carefully run the 
wires so that the 
wires will not come 
in contact with the 
copper pipe.

Earth wire

Power supply wire

From the sub electrical wiring box

To the sub electrical 
wiring box

Safety 
breaker

Earth leakage 
circuit breaker

Power supply 
50Hz 220-240V 
60Hz 220V 

Earth

<Good>

<Wrong>

<Wrong>

[Dimensions of the 
wire ends stripping]

20mm

10mm

Stranded Wire

Round crimp-style
terminal

Summary of Contents for rfwxv15aveb

Page 1: ...INSTALLATION MANUAL HEAT PUMP CONVECTOR Models RFWXV15AVEB RFWXV20AVEB...

Page 2: ...fire When wiring the power supply and connecting the wiring between the units position the wires so that the control box lid can be securely fastened Improper positioning of the control box lid may re...

Page 3: ...the remote controller range 8 the unit is at least 1m away from any television or radio set unit may cause interference with the picture or sound 9 no laundry equipment is located 2 Wireless remote co...

Page 4: ...led Grid field supply Mounting plate A Molding 64 644 134 700 600 574 26 140 230 250 35 35 210 160 150 unit mm Wall installation only Bottom of the unit Titanium apatite photocatalytic air purifying f...

Page 5: ...to the original position 3 How to set the different addresses When two indoor units are installed in one room the two wireless remote controllers can be set for different addresses 1 Remove the front...

Page 6: ...bottom frame and casings using nippers 5 Return by following the steps in reverse order 3 2 1 2 Attaching the connection pipe For water piping details see the valve kit installation manual 3 Connectin...

Page 7: ...r wall For wall installations secure the mounting plate using 5 screws and the indoor unit using 4 screws The mounting plate should be installed on a wall which can support the weight of the indoor un...

Page 8: ...es correctly An incorrect connection may damage components and make it impossible to operate or use the unit When connecting the wires to the terminal block be sure to curl the wire ends as shown in t...

Page 9: ...5 and 6 in the sub electrical wiring box with the specified wires Similarly connect X2M terminals 6 and 7 with sub electrical wiring box terminals 3 and 4 refer to Figure 1 3 Fasten the two way valve...

Page 10: ...result if the knob of the air purge valve is loose Check that the knob is tightly closed 8 DIP switch settings based on installation site conditions Set DIP switch SW2 1 to heating cooling use or heat...

Page 11: ...1 Remove the front grille 2 Remove 7 screws 3 Remove the upper casing 2 tabs 4 Remove the side casings 2 tabs on each side 5 Attach the indoor unit to the wall and secure using screws in 6 locations M...

Page 12: ...not to obstruct the flow of cool warm air 2 Place a partition plate between outlet and inlet sections 3 Place a partition plate on the right side 4 Change the upward blow limit switch 5 Use a movable...

Page 13: ...ating mode 1 3 The amount of the unit s water circulation should be 3L min to 15L min CAUTION If a special heat exchanger has been incorporated into the unit the water circulation should be within the...

Page 14: ...13 English...

Page 15: ...English 14...

Page 16: ...1104 HT 3P283987 1 M10B389 Two dimensional barcodeisacode for manufacturing...

Reviews: