background image

5 Installation

Installer reference guide

7

RBRP069A61
ROTEX LAN adapter
4P510034-1 – 2017.10

5.3.3

To connect the indoor unit

INFORMATION

▪ In the indoor unit switch box, the cable is connected to

the  same  terminals  the  user  interface  is  connected  to.
For more information, see the installation manual of the
indoor unit.

▪ The  2  wires  from  the  cable  are  NOT  polarised.  When

connecting  them  to  the  terminals,  their  polarity  does
NOT matter.

1

When  entering  the  wiring  from  the  bottom:  inside  the  LAN
adapter  casing,  ensure  strain  relief  by  routing  the  cable  along
the indicated cable path.

2

Connect  indoor  unit  terminals  X5M/1+2  to  LAN  adapter
terminals X3A/1+2.

X4A

X1A

X2A

X3A

X5M

2

1

5.3.4

To connect the router

X4A

X1A

X2A

X3A

NOTICE

To  prevent  communication  problems  due  to  cable
breakdown,  do  NOT  exceed  the  minimum  bend  radius  of
the Ethernet cable.

5.3.5

To connect the electrical meter

INFORMATION

This  connection  is  ONLY  supported  by  LAN  adapter
RBRP069A61.

1

When  entering  the  wiring  from  the  bottom:  inside  the  LAN
adapter  casing,  ensure  strain  relief  by  routing  the  cable  along
the indicated cable path.

2

Connect the electrical meter to LAN adapter terminals X2A/1+2.

S1S

2

1

X4A

X1A

X2A

X3A

INFORMATION

Mind the polarity of the cable. The positive wire MUST be
connected to X2A/1; the negative wire to X2A/2.

INFORMATION

Make  sure  to  connect  the  electrical  meter  in  the  correct
direction,  so  that  it  measures  the  total  energy  injected
INTO the grid.

5.3.6

To connect the digital inputs

INFORMATION

This  connection  is  ONLY  supported  by  LAN  adapter
RBRP069A61.

INFORMATION

How the digital outputs are connected to X1A depends on
the  Smart  Grid  application.  The  connection  described  in
the  instructions  below  is  for  the  system  to  run  in  the
"Recommended 

ON" 

operation 

mode. 

For 

more

information, see 

"7 Smart Grid application" on page 11

.

WARNING

Make  sure  X1A/N+L  are  protected  by  a  fast  acting  circuit
breaker (rated current 100 mA~6 A).

WARNING

When connecting the wiring to LAN adapter terminal X1A,
make  sure  each  wire  is  securely  fastened  to  the
appropriate  terminal.  Use  a  screwdriver  to  open  the  wire
clamps.  Make  sure  the  bare  copper  wire  is  fully  inserted
into the terminal (bare copper wire CANNOT be visible).

1

3

2

1

Ensure strain relief by fastening the cable with a cable tie to the
cable tie mounting.

2

Provide  a  detection  voltage  to  X1A/N+L.  Make  sure  X1A/N+L
are protected by a fast acting circuit breaker.

3

For  the  system  to  run  in  the  "Recommended  ON"  operation
mode  (Smart  Grid  application),  connect  the  digital  input  to  the
X1A/1+2 LAN adapter digital input.

Summary of Contents for RBRP069A61

Page 1: ...Installer reference guide ROTEX LAN adapter English Installer reference guide ROTEX LAN adapter RBRP069A61...

Page 2: ...peration mode 11 7 2 Recommended ON mode 11 7 2 1 Energy buffering 11 7 2 2 Power limitation 11 7 3 Forced OFF mode 12 7 4 Forced ON mode 12 8 Troubleshooting 12 8 1 Overview Troubleshooting 12 8 2 So...

Page 3: ...esent for RBRP069A62 but ALWAYS inactive INFORMATION When the LAN adapter performs a Smart Grid compatibility check the Smart Grid LED flashes This is NOT erroneous behaviour After a successful check...

Page 4: ...4 2 Overview of electrical connections Connectors X4A 4 N L 3 2 1 2 1 230 V AC X1A X2A X3A b a c d b e a RBRP069A61 only b To digital inputs of solar inverter energy management system c To electrical...

Page 5: ...ing the LAN adapter 5 2 1 About mounting the LAN adapter The LAN adapter is mounted to the wall by way of the mounting holes a in the rear casing Before mounting the rear casing to the wall you have t...

Page 6: ...static discharge Before mounting the PCB touch an earthed part a radiator the casing of the indoor unit to eliminate static electricity and protect the PCB from damage ONLY handle the PCB by its sides...

Page 7: ...X1A X2A X3A INFORMATION Mind the polarity of the cable The positive wire MUST be connected to X2A 1 the negative wire to X2A 2 INFORMATION Make sure to connect the electrical meter in the correct dir...

Page 8: ...dapter installation 5 4 1 LAN adapter serial number Before closing the LAN adapter note down its serial number This number can be found on the adapter s Ethernet connector bottommost number on X4A Not...

Page 9: ...ically performs a power reset Result The LAN adapter software is now updated to the latest version INFORMATION During the software update the LAN adapter and the app CANNOT be operated It is possible...

Page 10: ...the power supplied by the indoor unit AND the 230 V AC detection voltage supplied to X1A NOTICE Use appropriate tooling to set the DIP switches to another position Beware of electrostatic discharge Fo...

Page 11: ...on the state of the inputs you can make the system run in 4 Smart Grid operation modes Smart Grid operation mode SG0 SG1 Normal operation free mode 0 0 Recommended ON 1 0 Forced OFF 0 1 Forced ON 1 1...

Page 12: ...orced OFF mode for a long time comfort issues can occur 7 4 Forced ON mode In Forced ON operation mode there is NO power limitation The system selects the comfort setpoint for domestic hot water produ...

Page 13: ...eartbeat LED NOT blinking No normal operation Try resetting the LAN adapter or contact your dealer Network LED flashing Communication problem Check the network connection Indoor unit communication LED...

Page 14: ...contact Electric pulse meter 5 V DC pulse detection supplied by PCB Hydro SWB A3P LAN adapter PCB LD1 LD4 PCB LED Q1DI Circuit breaker SS1 A3P DIP switch S1S SG0 contact S2S SG1 contact S3S Electrical...

Page 15: ......

Page 16: ...Ausland Our partners abroad Unsere Partner im Ausland Nos partenaires l tranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granic Na i partne i v zahrani http...

Reviews: