4 Installation

Installation manual

7

07C2V3
ROTEX HPSU monobloc compact outdoor unit
4P501825-1 – 2017.08

4.2.4

To prevent the outdoor unit from falling
over

In  case  the  unit  is  installed  in  places  where  strong  wind  can  tilt  the
unit, take following measure:

1

Prepare  2  cables  as  indicated  in  the  following  illustration  (field
supply).

2

Place the 2 cables over the outdoor unit.

3

Insert  a  rubber  sheet  between  the  cables  and  the  outdoor  unit
to prevent the cable from scratching the paint (field supply).

4

Attach the cable’s ends. Tighten those ends.

4.3

Connecting the water piping

4.3.1

To connect the water piping

NOTICE

Do  NOT  use  excessive  force  when  connecting  the  piping.
Deformation of the piping can cause malfunctioning of the
unit.  Make  sure  that  the  tightening  torque  does  NOT
exceed 30 N•m.

To facilitate service and maintenance, 2 shut-off valves are provided.
Mount the valves on the space heating water inlet and space heating
water outlet. Mind their position: the integrated drain valves will only
drain the side of the circuit on which they are located. To be able to
only  drain  the  unit,  make  sure  the  drain  valves  are  positioned
between the shut‑off valves and the unit.

a

b

a

Water inlet

b

Water outlet

1

Screw the outdoor unit nuts on the shut-off valves.

2

Connect the field piping on the shut-off valves.

3

For  how  to  connect  the  HPSU  monobloc  tank,  see  the
installation manual of the tank.

NOTICE

To  protect  the  water  circuit  against  freezing,  add  glycol.
For  instructions,  see  the  installation  manual  of  the  HPSU
monobloc tank.

NOTICE

Install a manometer in the system.

NOTICE

Install air purge valves at all local high points.

4.3.2

To insulate the water piping

The  piping  in  the  complete  water  circuit  MUST  be  insulated  to
prevent  condensation  during  cooling  operation  and  reduction  of  the
heating and cooling capacity.

To  prevent  the  freezing  of  the  outdoor  water  piping  during  winter
time, the thickness of the sealing material MUST be at least 13 mm
(with λ=0.039 W/mK).

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

During  winter,  protect  the  water  piping  and  shut‑off  valves  against
freezing  by  adding  heat  tape  (field  supply).  If  the  outdoor
temperature  can  drop  below  –20°C  and  no  heat  tape  is  used,  it  is
recommended to install the shut‑off valves indoors.

4.4

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

4.4.1

To connect the electrical wiring on the
outdoor unit

1

Remove the switch box cover. See 

"4.1.1 To open the outdoor

unit" on page 4

.

2

Insert the wiring from the back of the unit:

a

b
c

≥25 mm

a

Low voltage cable

b

High voltage cable

c

Power supply cable

Summary of Contents for HPSU

Page 1: ...Installation manual ROTEX HPSU monobloc compact outdoor unit English Installation manual ROTEX HPSU monobloc compact outdoor unit ...

Page 2: ... souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják spełniają wymogi następujących norm i innych ...

Page 3: ... 4 4 3 To connect the remote outdoor sensor 8 4 4 4 To connect the shut off valve 8 5 Commissioning 9 5 1 Checklist before commissioning 9 6 Hand over to the user 9 7 Technical data 10 7 1 Piping diagram Outdoor unit 10 7 2 Wiring diagram Outdoor unit 11 1 About the documentation 1 1 About this document Target audience Authorised installers Documentation set This document is part of a documentatio...

Page 4: ...he user interface does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it is important that the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached a flow error 7H will be generated no heating or operation See the installer reference guide for more information M...

Page 5: ...the floor prepare 4 sets of M8 or M10 anchor bolts nuts and washers field supply as follows INFORMATION The maximum height of the upper protruding part of the bolts is 15 mm 283 1 0 0 mm 1 0 0 330 300 7 4 0 In any case provide at least 300 mm of free space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow mm 1 5 0 1 5 0 a 330 300 ...

Page 6: ...dboard b Instruction sheet NOTICE To prevent damage to the supporting feet do NOT tilt the unit sideways in any way 4 2 3 To provide drainage Make sure that condensate can be evacuated properly When the unit is in cooling mode condensate may also form in the hydro part When providing drainage therefore make sure to cover the entire unit NOTICE If the unit is installed in a cold climate take adequa...

Page 7: ...the shut off valves 3 For how to connect the HPSU monobloc tank see the installation manual of the tank NOTICE To protect the water circuit against freezing add glycol For instructions see the installation manual of the HPSU monobloc tank NOTICE Install a manometer in the system NOTICE Install air purge valves at all local high points 4 3 2 To insulate the water piping The piping in the complete w...

Page 8: ...upply 4 Make sure that the cable does NOT come in contact with sharp edges 5 Install the switch box cover INFORMATION When installing field supply or option cables foresee sufficient cable length This will make it possible to remove reposition the switch box and gain access to other components during service CAUTION Do NOT push or place redundant cable length in the unit 4 4 2 To connect the main ...

Page 9: ...n devices are installed according to this document and have not been bypassed The power supply voltage matches the voltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the outdoor unit The correct pipe size is installed and the pipes are properly insulated...

Page 10: ...or Accumulator Compressor High pressure switch Muffler Muffler 4 way valve Pressure sensor Refrigerant flow Cooling Heating Liquid stop valveV Plate heat exchanger Gas stop valve with service port Air purge Flow sensor Pump Flow switch Outlet Shut off valve with drain fill valve Expansion vessel Safety valve Blow off Filter Inlet Outlet water heat exchanger thermistor Refrigerant liquid side therm...

Page 11: ... S1PH High pressure switch S2 S503 Connector SA1 Surge arrestor SHEET METAL Terminal strip on fixed plate SW1 SW3 Push buttons SW2 SW5 DIP switches U Connector V Connector V2 V3 V401 Varistor W Connector X11A X12A Connector X1M X2M Terminal strip Y1E Electronic expansion valve coil Y1R Reversing solenoid valve coil Z1C Z4C Ferrite core Field wiring Terminal strip Connector Terminal Protective eart...

Page 12: ...SU monobloc compact outdoor unit 4P501825 1 2017 08 Electrical connection diagram Hydro switch box Power Supply Q3DI X3M X5M X5M XAG1 X4M 1N 50 Hz 230 V AC Power supply L N L N M2S NO Valve 1 2 2 1 2 1 1 2 5 6 external outdoor ambient sensor option 4D112157A R6T t ...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...sland Our partners abroad Unsere Partner im Ausland Nos partenaires à l étranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granicą Naši partneři v zahraničí http de rotex heating com ueber rotex international 4P501825 1 2017 08 ROTEX Subject to change and correction ...

Reviews: