Faults and malfunctions
ROTEX GCU compact -
53
Tab. 10-4 Fault codes (can be detected by switching panel PCB)
10.4 Rectifying burner faults and STB faults
Interlocking faults detected by the automatic firing unit can only
be reset manually directly on the boiler.
Unlocking the automatic firing unit:
Requirements: The cause of the malfunction is rectified, the
burner is electrically connected.
1. Switching ROTEX GCU compact on.
2. Push the Exit button (fig. 6-1, item 15) for at least 5 secs.
Î
Menu
"Special Level"
is displayed.
3. Select the
"FA failure"
level with the rotary switch.
Î
Fault code and request "Reset" is displayed.
4. Select "Yes" with the rotary switch.
5. Confirm the changes with a brief push of the rotary switch.
Î
Fault is reset.
6. Cancelling and jump back by pushing the Exit button again.
Code
Component/Designation
Fault
Possible fault rectification
E72
Internal mixer sensor
Measured value outside measuring range,
temperature sensor defective.
Ɣ
Check cable, terminal and plug connec-
tions.
Ɣ
Replace the temperature sensor.
E75
Outside temperature sensor
E76
Storage tank temperature
sensor
E81
Eeprom
Internal fault
Ɣ
Total reset
Ɣ
Replace switching panel PCB in
controller.
E88
Switching panel PCB control-
ler
E91
Connected CAN modules
Bus detection of a CAN module doubly pre-
sent.
Ɣ
Set bus addresses correctly.
E100
Flue gas temperature
Internal fault
Ɣ
Replace the combustion controller.
E129
Pressure sensor
Measured value outside measuring range,
sensor / temperature sensor defective.
Ɣ
Check cable, terminal and plug connec-
tions.
Ɣ
Replace the sensor / temperature
sensor.
E198
FlowSensor
Volume flow too low.
Ɣ
Check heating circulation pump / filter /
heating network.
E200
Communication automatic
firing
Fault in communication between automatic fir-
ing and switching panel PCB on controller.
Ɣ
Check cable and plug connections.
Ɣ
Total reset
Ɣ
Replace control panel PCB on the Gas
Combi Unit compact.
Ɣ
Replace the combustion controller.
W8001
FlowSensor
Volume flow fell below the minimum limit.
Ɣ
Check the parameter settings (see
Control System Instructions).
Ɣ
Check the pipes and valves for
blockages.
Ɣ
Check the built-in circulation pump.
E8002
Flow under minimum threshold (300 l/h)
W8003
Flue gas temperature
The flue gas temperature has exceeded the
threshold temperature.
Ɣ
Clean the boiler
E8004
The flue gas temperature has exceeded the
permissible absolute maximum value.
E8005
Water pressure
Measured value under permissible minimum
value.
Ɣ
Top up heating water.
Ɣ
Leak test
W8006
Warning message: Maximum permissible
pressure drop exceeded.
W8007
Warning message: Measured value over per-
missible maximum value.
Ɣ
Check diaphragm expansion vessel.
Ɣ
Drain heating water.
WARNING!
Risk of burns due to very hot boiler body with STB
fault.
Ɣ
Do not touch any metallic parts on the boiler.
Ɣ
Let the boiler cool down.
Ɣ
Wear protective gloves.
The cause of the last fault is saved in the unit and can
be reconstructed on restarting the unit, even after
power failure.