9
x
Faults and malfunctions
62
FA ROTEX A1 BO - 10/2007
Tab. 9-3
Possible malfunctions on the A1 BO (Part 3)
9.3
Control unit fault signals
The control unit detects malfunctions, e.g. sensor disruptions or short-circuits. The type of malfunction is displayed via a fault
code. The fault codes are explained in the documentation of the relevant ROTEX control.
9.4
Burner malfunctions
The LED in the reset button of the automatic firing units (fig 6-1, pos. 9) indicates the processes of the burner control. In the
normal mode
, the LED transmits a brief flashing signal, followed by a long pause.
LED display in the event of a
malfunction
:
– LED burns steadily, the burner is shut off and locked.
– The continuous lighting is interrupted every 10 seconds and a flash code is broadcast which gives information about the
cause of the last fault.
Fig. 9-1
Fault codes of the automatic firing units
I
short signal
l
long signal
—
Pause
Malfunction
Possible cause
Possible solution
Mixer device has thick
layer of oil or heavy
carbon deposits
Air supply line contaminated/clogged
• Clean air supply line
Flue gas pipe of the LAS is leaking
• Seal the flue gas pipe, change seal
Burner setting wrong
• Check/correct burner setting
Oil nozzle is wrong size
• Check/change nozzle type
Combustion air quantity wrong
• Measure fan pressure, correct burner setting
Suction line draws air (leakage)
• Seal suction line
Soot formation on the
air nozzle
Recirculation too low
• Open recirculation slightly
Solenoid valve at oil
pump does not open
Coil defective
• Change coil
Automatic firing unit faulty
• Change automatic firing unit
Automatic flame guard
does not actuate
Flame guard contaminated or defective
• Clean or change flame guard
Glass on light tube dirty
• Clean or change glass or light tube
STL switch off
Water throughput too low due to air inclusion
• Vent system
Water flow too low due to valves closing too quickly
along the entire heating network
• Use slow closing or timed valves, if needed, install overflow valve
Pump standstill
• Check network connection, change pump if necessary
Storage tank switched off in operation without
hot water storage tank
• Disconnect storage temperature sensor
• Switch off storage tank charging circuit
Flue gas temperature
sensor switch off
Flue gas temperature too high
• Clean the boiler
Flash Code
Cause of the fault
l
l l l l
No flame signal within safety period
l l
l l l
External light during pre-ventilation time/ pre-ignition time
l l l
l l
Contact release thermostat does not close within 400 s
l l
l l l
—
l l l l l
Manual fault shutdown