LOKA HAHB remote control
EN
74
Installation and user manual
Rotation & Back-up indication
When there are two units, press the button to select the rotating function, and press
“CONFIRM”to turn on or off the rotating function.
1. Press “CONFIRM” to set the rotating time,then press the button „ ” or „ ”, to set
time. Setting time Range :1~99h,the default time is 10 hours.
2. Step 2 set high temperature co-open temperature -- or 26~32 degrees -- that is,
this function is invalid. When the ambient temperature is 26~32 degrees, when
the ambient temperature is greater than or equal to the set temperature, the two
machines will run 24 degrees at the same time in the COOL mode.
3. Step 3 set the low-temperature co-open temperature -- or 5-15 degrees -- that is, this
function is invalid. When the ambient temperature is 5-15 degrees, when the ambient
temperature is lower than the set temperature, the two machines will run at the same
time for 24 degrees to make the heating mode.
4. Step 4: set which machine will run first. Select A or B.
5. After this function is turned on, as long as the air conditioner is running at the setting
hour, it will automatically turn on another air conditioner and turn off the current air
conditioner. Press the POWER button to switch to another one immediately. A or B
icons flicker to indicate the corresponding air conditioning failure.
Automatically switch to another machine when running time is reached or machine
failure occurs.