Page 1: ...AC 225x B Series Expandable 2 Reader Networked Access Control Panel Hardware Installation and User Manual Models AC 225 Bx AC 225 DIN AC 225IP Bx AC 225IP DIN ...
Page 2: ...al property rights covering the subject matter in this manual TEXTS IMAGES AND ILLUSTRATIONS INCLUDING THEIR ARRANGEMENT IN THIS DOCUMENT ARE SUBJECT TO THE PROTECTION OF COPYRIGHT LAWS AND OTHER LEGAL RIGHTS WORLDWIDE THEIR USE REPRODUCTION AND TRANSMITTAL TO THIRD PARTIES WITHOUT EXPRESS WRITTEN PERMISSION MAY RESULT IN LEGAL PROCEEDINGS The furnishing of this manual to any party does not give t...
Page 3: ... 3 4 Power Supply 17 3 5 AC 225x B Wiring Communications 18 3 6 Reader 19 3 7 MD IO84B 19 3 8 MD D02B 19 4 Input and Output Connections 20 4 1 Input Types 20 4 1 1 Normally Open Input Connection 20 4 1 2 Normally Closed Input Connection 21 4 1 3 Normally Open Supervised Single Resistor Input Connection 21 4 1 4 Normally Open Supervised Double Resistor Input Connection 21 4 1 5 Normally Closed Supe...
Page 4: ...Baud Rate 28 5 3 Access Control Panel Type 28 5 4 Access Control Panel Addressing 30 6 Communications 32 6 1 Serial Network Connection 32 6 1 1 RS 232 Connection to the Computer 32 6 1 2 RS 485 Connection to the Computer 33 6 1 3 Daisy Chaining 34 6 2 TCP IP Network Connection 35 6 2 1 LAN and WAN Requirements 35 A Declaration of Conformity 37 B Radio Equipment Directive RED 38 C RoHS Directive 39...
Page 5: ...en Input Connection 20 Figure 11 Normally Closed Input Connection 21 Figure 12 Normally Open Supervised Input Connection Single Resistor 21 Figure 13 Normally Open Supervised Input Connection Double Resistor 22 Figure 14 Normally Closed Supervised Input Connection Single Resistor 22 Figure 15 Normally Closed Supervised Input Connection Double Resistor 23 Figure 16 DIP Switches 27 Figure 17 RS 232 ...
Page 6: ... Description of AC 225x B Panels 8 Table 2 AxTraxNG Capabilities 9 Table 3 DIP Switches and Their Functions 27 Table 4 Switch Baud Rates 28 Table 5 Possible Hardware Settings 28 Table 6 Available Panel Addresses 30 Table 7 RS 232 Connection 33 Table 8 UL 294 Access Control Performance Ratings 40 ...
Page 7: ... of the system with the maximum number of functions including future options Therefore not all functions described in this manual may be available in the specific system and or product configuration you purchased Incorrect operation or installation or failure of the user to effectively maintain the system relieves the manufacturer and seller from all or any responsibility for consequent noncomplia...
Page 8: ...225IP BU Installed in ME 1015 with Type B plug power cable AC 225IP DIN PCBA only with wall DIN rail mounting base The IP models also includes onboard support for communications across a TCP IP network UL Certified When used in combination with Rosslare s AxTraxNG software system the AC 225x B gives you full control over access to your premises The system can control both single and double door en...
Page 9: ...l Figure 1 AC 225x B Panel Layout 1 1 AxTraxNG The AxTraxNG software system is designed to set up manage and supervise all aspects of an access control panel network Table 2 presents the AxTraxNG software capabilities Table 2 AxTraxNG Capabilities Users capacity 30 000 Unauthorized Users 30 000 Access groups 30 000 Number of panels in system 1 023 Number of doors in system 4 092 These options are ...
Page 10: ...atabase backup input and export of previous configurations and automatic backing up on a periodic basis 1 1 2 Configurable Links The system s configurable links model makes it possible to trigger any chosen output automatically or report a configurable alarm based on a selected input This allows easy integration with related access systems such as intruder alarms CCTV systems and elevator controls...
Page 11: ...reader ports 4 reader ports when using MD D02B Communication Wiegand D0 D1 or Clock Data C D Output voltage to reader 12 VDC battery only 8 8 11 8 VDC Max current to reader 245 mA LED control output and Tamper Input Visual Indicators 11 LEDs for outputs and communication status Audio Sounder output for use with compatible speakers provide chime bell and siren signals Battery Standby Time 3 hours w...
Page 12: ...1 5 A Output Power 15 VDC 4 A 60 Watts to the power management board Electrical Characteristics Power Management Board PM 10 Input Power 15 VDC 4 A to the power management board Output Power Two PTC fused outputs Each provides 13 8 VDC 1 5 A battery only 8 8 11 8 VDC One output for controller and readers One output for locks Battery Charger 13 8 VDC 300 mA for 12 VDC 7 Ah Lead Acid Battery Speaker...
Page 13: ...s with MD D02B The panels connect together in a network and are controlled by a central server computer running the AxTraxNG software system Figure 2 shows an example setup for a network of AC 225x B access control panels Figure 2 AC 225x B Sample Configuration The use of bushings is required for any conductors leaving the enclosure through the provided openings ...
Page 14: ...re 3 presents a detailed view of the non supervised inputs and their connection options Figure 3 Inputs Wiring Non supervised Inputs 3 2 Inputs Wiring Supervised Inputs When wiring the AC 225x for supervised inputs resistors should be placed on the input switch and not on the terminal block For further details see Chapter 4 ...
Page 15: ...llation and User Manual 15 3 3 Outputs Wiring Figure 4 and Figure 5 illustrate wiring for two main types of 12 VDC electrical release mechanisms Other electrical devices can be switched using the voltage free relay contacts Figure 4 Door Lock Failed Close ...
Page 16: ...AC 225x B Panel Setup 16 AC 225x B Series Hardware Installation and User Manual Figure 5 Door Lock Failed Open ...
Page 17: ... sure the connection polarity is correct to and to Connect the power to the input power terminals of the control panel It is recommended to add a 12 VDC lead acid backup battery requires the ME 1015 Power Management Enclosure to have uninterrupted operation in case main power supply fails A 12 V 7 AH battery provides 3 hours of backup operation Figure 6 Wiring Between PM 10 and AC 225x B ...
Page 18: ...AC 225x B Series Hardware Installation and User Manual 3 5 AC 225x B Wiring Communications Figure 7 presents a detailed view of the access control panel with all it wiring communications Figure 7 AC 225x B Wiring Communications ...
Page 19: ... O expansion board which adds four relay outputs and eight supervised inputs to the access control panel Attach the MD IO84B to the AC 225x B s expansion slot as marked in red in Figure 9 Figure 9 Connector Location for MD IO84B or MD D02B Expansions For more information see the MD IO84B Installation and User Guide 3 8 MD D02B The MD D02B is an optional reader expansion board which adds two reader...
Page 20: ...igure each input separately via the AxTraxNG system Non supervised inputs have two states Normal State Abnormal State Supervised inputs have three states Normal State Abnormal State Trouble State The Trouble state is caused by either tampering with the input circuit or by faulty hardware installation Once configured as supervised input add a resistor of 2 2 kΩ of 8 2 kΩ or both on the input circui...
Page 21: ...ontacts Normally Open Supervised Input has 3 states Switch Open Normal State Loop resistance 8 2 kΩ Switch Closed Abnormal State Loop resistance 0 short circuit Open circuit across input terminals Trouble State Loop resistance Infinite open circuit Figure 12 Normally Open Supervised Input Connection Single Resistor 4 1 4 Normally Open Supervised Double Resistor Input Connection Connect a 2 2 kΩ re...
Page 22: ...Resistor 4 1 5 Normally Closed Supervised Single Resistor Input Connection Connect a 2 2 kΩ resistor in series to the input switch contacts Normally Closed Supervised Input has 3 states Switch Closed Normal State Loop resistance 2 2 kΩ Switch Open Abnormal State Loop resistance Infinite open circuit Short circuit across input terminals Trouble State Loop resistance 0 short circuit Figure 14 Normal...
Page 23: ...esistor 4 2 Inputs Description 4 2 1 Request to Exit REX Button Input Use the REX input to open a door directly Typically the REX input is connected to a Normally Open push button that is located inside the premises The push button is generally located in an easy to access position and opens a door without reading a proximity card or PIN code Single door controller Door 1 IN1 Double door controlle...
Page 24: ...The following should be defined Single door controller Door 1 IN2 Door 1 INA Double door controller No general purpose inputs available General purpose inputs are suitable for most uses For example they might be used to detect tampering to activate alarm sensors or for monitoring power supply failure General purpose input functions when using MD IO84B or MD D02B MD IO84B IN5 to IN12 MD D02B IN5 to...
Page 25: ... door controller Door 1 Reader 1 IN OUT Door 1 Reader 2 OUT IN Double door controller Door 1 Reader 1 IN OUT Door 2 Reader 2 IN OUT When using the MD D02B the following should be defined Double door controller each door has two readers Reader 1 Door 1 IN OUT Reader 2 Door 1 OUT IN Reader 3 Door 2 IN OUT Reader 4 Door 2 OUT IN Four door controller each door has one reader Reader 1 Door 1 IN OUT Rea...
Page 26: ...Input and Output Connections 26 AC 225x B Series Hardware Installation and User Manual The controller activates the LED control for 2 seconds when an access granted event occurs ...
Page 27: ...ion 1 The panel s communication baud rate 2 3 The panel type defines the number of readers for each door one or two readers per door This also affects the number of doors controlled by the panel 4 The access control panel s RS 485 network address 5 6 7 8 Power down the access control panel before changing the DIP switch settings After changes have been made restart the panel The new settings are a...
Page 28: ... with two readers per each door This DIP switch setting influences the number of doors in the panel The default access control panel setting is for two readers per each door OFF Defines using two readers for each door Panel controls one door or two doors when MD D02B is installed ON Defines using one reader for each door Panel controls two doors or four doors when MD D02B installed Select the appr...
Page 29: ...quest to exit IN 2 Door2 monitor input IN 2A Readers Reader1 Door1 IN OUT Reader2 Door2 IN OUT Double Door with 4 Readers MD D02B Outputs Door1 Lock output OUT 1 General purpose output OUT 1A General purpose output OUT 2 General purpose output OUT 2A Door2 Lock output OUT 5 General purpose output OUT 6 General purpose output OUT 7 General purpose output OUT 8 Inputs Door1 Request to exit IN 1 Door...
Page 30: ...itor input IN 6 Door4 Request to exit IN 7 Door4 monitor input IN 8 Readers Reader1 Door1 IN OUT Reader2 Door2 IN OUT Reader3 Door3 IN OUT Reader4 Door4 IN OUT 5 4 Access Control Panel Addressing The last five DIP switches are used to set the binary code of the access control panel internal network address The default access control panel address is 1 For successful communications the DIP switch m...
Page 31: ... OFF ON OFF 12 OFF ON OFF ON ON 13 OFF ON ON OFF OFF 14 OFF ON ON OFF ON 15 OFF ON ON ON OFF 16 OFF ON ON ON ON 17 ON OFF OFF OFF OFF 18 ON OFF OFF OFF ON 19 ON OFF OFF ON OFF 20 ON OFF OFF ON ON 21 ON OFF ON OFF OFF 22 ON OFF ON OFF ON 23 ON OFF ON ON OFF 24 ON OFF ON ON ON 25 ON ON OFF OFF OFF 26 ON ON OFF OFF ON 27 ON ON OFF ON OFF 28 ON ON OFF ON ON 29 ON ON ON OFF OFF 30 ON ON ON OFF ON 31 ON...
Page 32: ...rial Network RS 232 or RS 485 Modem Network TCP IP Network 6 1 Serial Network Connection The computer serial port controlling the access control panel is set from within the AxTraxNG software The default bitrate is 9600 bps for direct connection to the computer When using an RS 232 connector only one access control panel can be linked to each communication port on the computer Use an RS 485 connec...
Page 33: ...r to the RS 485 position Using the RS 485 up to 32 access control panels can be linked together and connected to a single communication port on the computer Figure 18 Figure 18 RS 485 Panel Connection to PC Use the RS 485 interface for situations where there are multiple controllers connected The serial port used to control the access control panel is assigned within the AxTraxNG software The AC 2...
Page 34: ...from the PC to the last panel in the chain to 4 000 ft 1 219 2 m The first panel is connected directly to the server using an MD 14U converter while the second panel connects to the first panel Additional panels are connected in the same way one after another The server identifies each panel on the RS 485 network by its address At each end of the data line both where the panel connects to the comp...
Page 35: ...etworked panels can be connected via an RS 485 bus which means that one IP port can support up to 32 AC 225x B panels Figure 20 Figure 20 Connecting Multiple Access Control Panels to AC 225IP To connect to a TCP IP network using AC 225 non IP models add Rosslare s MD N32 TCP IP to RS 232 gateway converter For more information on operating an MD N32 refer to the MD N32 User Manual 6 2 1 LAN and WAN...
Page 36: ... panel by TCP IP connection for the first time the AxTraxNG software must configure the device Settings then remain stored in non volatile memory on the device see the AxTraxNG Software Manual When using an MD N32 for a single panel either an RS 232 cable or Rosslare s MD 14U RS 485 to RS 232 converter can be used To connect an MD N32 to more than one panel up to 32 panels Rosslare s MD 14U RS 485...
Page 37: ...ed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does ...
Page 38: ...ion and User Manual B Radio Equipment Directive RED Under our sole responsibility that the following labeled AC 225 Bx AC 225 DIN AC 225IP Bx and AC 225IP DIN are tested to conform to the EU Radio Equipment Directive RED 2014 53 EU in electrical and electronic equipment ...
Page 39: ... Manual 39 C RoHS Directive Under our sole responsibility that the following labeled AC 225 Bx AC 225 DIN AC 225IP Bx and AC 225IP DIN are tested to conform to the Restriction of Hazardous Substances RoHS directive 2011 65 EU in electrical and electronic equipment ...
Page 40: ...tion The following labeled AC 225 Bx AC 225 DIN AC 225IP Bx and AC 225IP DIN are UL listed to UL 294 7th Edition Standard for Access Control System Units Table 8 UL 294 Access Control Performance Ratings Destructive Attack Level I Endurance Level IV Line Security Level I Standby Power Level II ...
Page 41: ...al 41 E Limited Warranty The full ROSSLARE Limited Warranty Statement is available in the Quick Links section on the ROSSLARE website at www rosslaresecurity com Rosslare considers any use of this product as agreement to the Warranty Terms even if you do not review them ...
Page 42: ......
Page 43: ...resecurity com Europe Rosslare Israel Ltd 22 Ha Melacha St P O B 11407 Rosh HaAyin Israel Tel 972 3 938 6838 Fax 972 3 938 6830 support eu rosslaresecurity com Latin America Rosslare Latin America Buenos Aires Argentina Tel 54 11 4001 3104 support la rosslaresecurity com China Rosslare Electronics Shenzhen Ltd Shenzhen China Tel 86 755 8610 6842 Fax 86 755 8610 6101 support cn rosslaresecurity com...