![Rosslare AC-225-B Series Hardware Installation Download Page 21](http://html.mh-extra.com/html/rosslare/ac-225-b-series/ac-225-b-series_hardware-installation_1489228021.webp)
Input and Output Connections
AC-225x-B Series Hardware Installation and User Manual
21
4.1.2
Normally Closed Input Connection
Normally Closed Input has two states:
▪
Switch Closed
–
Normal State:
Loop resistance = 0 (short circuit).
▪
Switch Open
–
Abnormal State:
Loop resistance = Infinite (open circuit).
Figure 11: Normally Closed Input Connection
4.1.3
Normally Open Supervised Single Resistor Input Connection
Connect an 8.2 k
Ω
resistor in parallel to the input switch contacts.
Normally Open Supervised Input has 3 states:
▪
Switch Open
–
Normal State:
Loop resistance = 8.2 k
Ω
▪
Switch Closed
–
Abnormal State:
Loop resistance = 0 (short circuit).
▪
Open circuit across input terminals
–
Trouble State:
Loop resistance = Infinite (open circuit).
Figure 12: Normally Open Supervised Input Connection (Single Resistor)
4.1.4
Normally Open Supervised Double Resistor Input Connection
Connect a 2.2 k
Ω
resistor in series to the input switch contacts.
Connect an 8.2
kΩ
resistor parallel to the input switch contacts.
Normally Open Supervised Input has 3 states:
▪
Switch Open
–
Normal State:
Loop resistance = 10.4 k
Ω
▪
Switch Closed
–
Abnormal State:
Loop resistance = 2.2 k
Ω