Pressing contemporaneously the buttons
and
, the technician will enter the menu
and can change following parameters:
REG
Parameters regulation
Default
U.m.
dOn
Hysteresis when switching on
0,0
°C
dOFF
Hysteresis when switching off
0,0
°C
rOn
Delay when switching on
0
sec
rOFF
Delay when switching off
0
sec
dtCk
Difference between ambient temperature and evaporation temperature to
determine a probable damage to the compressor
1,0
°C
rICk
Period of time during which compressor’s failure conditions should remain until
the system sends to the display the signal C KO and starts using the
resistance;
900
Sec
tEVk
Underneath this evaporation temperature the system searches the failure in
the fan
-8,0
°C
tAVk
Minimum ambient temperature to abilitate fan’s failure search
0,0
°C
rIVk
Period of time during which fan’s failure conditions should remain before the
system sends to the display the signal V KO and starts using the resistance
900
sec
AnLE
Enables antilegionella cycles (1 enables, 0 disables)
0
rtAL
Period between 2 anti legionella cycles
7
days
tAL
Set point temperature to enable an antilegionella cycle
65,0
°C
SOLE
Parameters of solenoid
tISb
Underneath this temperature defrost will start
-10,0
°C
rISb
During this period the temperature should remain lower than tiSb
10
min
tFSb
Target temperature to end defrost cycle
8,0
°C
tMsb
Maximim defrost time
20
min
tEq
Pressures equalization time before compressor’s starting up
30
Sec
rCOn
Delay at solenoid closing after compressor’s starting up
10
sec
RESI
Parameters of resistance
rArS
If the temperature of the upper part of the tank does not reach the set point in
the period rArS, the resistance is supplied
1
hour
VENT
Parameters of fan
tEL
Evaporation’s low limit temperature to activate fan’s self-regulation
5,0
°C
tEH
Evaporation’s high limit temperature to activate fan’s self-regulation
10,0
°C
tAL
Temperature of low part of the tank to activate fan’s self-regulation
35,0
°C
Rit
Delay in changing fan’s speed
30
sec
Vmin
Minimum fan’s speed
1