Supply Wire Requirements
Use 12 to 18 AWG wire rated for the proper temperature of the application. For connections
in ambient temperatures above 140 °F (60 °C), use a wire rated for 176 °F (80 °C). For
ambients greater than 176 °F (80 °C), use a wire rated for 230 °F (110 °C). For DC powered
transmitters with extended cable lengths, verify that there is a minimum of 12 V DC at the
terminals of the transmitter.
Disconnects
Connect the device through an external disconnect or circuit breaker. Clearly label the
disconnect or circuit breaker and locate it near the transmitter and per local electrical
control.
Overcurrent Protection
The Rosemount 8712 Flowmeter Transmitter requires overcurrent protection of the supply
lines. Maximum ratings of overcurrent devices are as follows:
Figure 14. Power Supply Current
Table 6. Overcurrent Ratings
Power System
Fuse Rating
Manufacturer
90-220 V AC
250 V; 2 Amp, Quick Acting
Bussman AGCI or Equivalent
42 V DC
50 V, 3 Amp, Quick Acting
Bussman AGCI or Equivalent
1.0
0.8
0.6
0.4
0.2
0
0
10
20
30
40
50
Power Supply (Volts)
Supply Curre
nt (Amp
s)
4750RevBAQIG.fm Page 18 Thursday, July 16, 2009 3:52 PM
Summary of Contents for 8750WA
Page 37: ...Quick Installation Guide 00825 0100 4750 Rev BA June 2009 Rosemount 8750WA 37 ...
Page 38: ...Quick Installation Guide 00825 0100 4750 Rev BA June 2009 Rosemount 8750WA 38 ...
Page 39: ...Quick Installation Guide 00825 0100 4750 Rev BA June 2009 Rosemount 8750WA 39 ...
Page 40: ...Quick Installation Guide 00825 0100 4750 Rev BA June 2009 Rosemount 8750WA 40 ...