Reference Manual
00809-0100-4663, Rev BA
January 2010
Rosemount 8732
www.rosemount.com
Appendix F
Resource Block
Parameters and Descriptions . . . . . . . . . . . . . . . . . . . . . . page F-1
Resource Block Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . page F-5
Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page F-5
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page F-6
This section contains information on the resource block for the
Rosemount 8732 Magnetic Flowmeter Transmitter. Descriptions of all
resource block parameters, errors, and diagnostics are included. Also, the
modes, alarm detection, status handling, virtual communication relationships
(VCRs), and troubleshooting are discussed.
Definition
The resource block defines the physical resources of the device, such as
measurement and memory. The resource block also handles functionality,
such as shed times, that is common across multiple blocks. The block has no
linkable inputs or outputs, and it performs memory-level diagnostics.
PARAMETERS AND
DESCRIPTIONS
Table F-1 lists all of the configurable parameters of the resource block,
including the descriptions and index numbers for each parameter. Newer
software revisions have added functionality and some index numbers have
changed. To determine the software revision of a transmitter, check the
parameter SOFTWARE_REVISION_MAJOR. The most recent transmitters
have a label on the electronic board stack.
Table F-1. Resource Block
Parameters
Index Number
Parameter
Rev 5
Description
ACK_OPTION
38
ACK_OPTION is a selection of whether alarms associated with the function block
will be automatically acknowledged.
ADVISE_ACTIVE
82
Active advisory alarms.
ADVISE_ALM
83
Alarm indicating advisory alarms. These conditions do not have a direct impact on
the process or device integrity.
ADVISE_ENABLE
80
Enables or disables the advisory conditions within a device.
ADVISE_MASK
81
Mask of advisory Alarm. Corresponds bit for bit to the Advisory Active. A bit on
means that the failure is masked out from alarming.
ADVISE_PRI
79
Designates the alarming priority of the advisory alarm.
ALARM_SUM
37
This parameter shows the current alert status, unacknowledged states, unreported
states, and disabled states of the alarms associated with the function block. In the
Rosemount 8732 Magnetic Flowmeter Transmitter, the two resource block alarms
are
write alarm
and
block
alarm
.
ALERT_KEY
04
ALERT_KEY shows the identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
Summary of Contents for 8732 Series
Page 2: ......
Page 4: ......
Page 10: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 TOC 6 ...
Page 26: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 2 14 ...
Page 38: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 3 12 ...
Page 92: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 A 8 ...
Page 186: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 H 8 ...
Page 189: ......