Reference Manual
00809-0100-4835 Rev BD
July 2016
Rosemount 3150 Series
3-8
Figure 3-5a – Example for Elevated
Zero Calibration (English Units)
Range 2 with Zero Elevation for a calibration of –120 to –20
inH
2
O (100 inH
2
O span)
1. Calibrate the transmitter to 0 to 100 inH
2
O as described in the
Zero
Based Calibration Procedure
.
2. Consult Table 3-1 to determine appropriate Course Zero Select
Jumper position. If necessary, reposition jumper using the
Coarse
Zero Select Jumper Position Selection Procedure
.
For this example:
% Zero Offset = (-120 inH
2
O /250 inH
2
O)*100 = -48%
Position the jumper to the MID ZE position.
3.
Apply -120 inH
2
O to the high side process connection (as marked on
the transmitter sensor module) and adjust the zero until the
transmitter output reads 4mA.
Do not use the span adjustment.
NOTE
Applying 120 inH
2
O to the low side process connection (as
marked on the transmitter module) will give the same result
4.
Apply -20 inH
2
O to the high side process connection (as marked on
the transmitter sensor module). Verify the output reads 20mA. If
necessary, adjust the span. Recheck the zero after any span
adjustment.
NOTE
Applying 20 inH
2
O to the low side process connection (as marked
on the transmitter module) will give the same result.
Figure 3-5b – Example for Elevated
Zero Calibration (SI Units)
Range 2 with Zero Elevation for a calibration of –29,9 to –5,0 kPa
(24,9 kPa span)
1. Calibrate the transmitter to 0 to 24,9 kPa as described in the
Zero
Based Calibration Procedure
.
2. Consult Table 3-1 to determine appropriate Course Zero Select
Jumper position. If necessary, reposition jumper using the
Coarse
Zero Select Jumper Position Selection Procedure
.
For this example:
% Zero Offset = (-29,9 kPa /62,
2
kPa)*100 = -48%
Position the jumper to the MID ZE position.
3.
Apply -29,9 kPa to the high side process connection (as marked on
the transmitter sensor module) and adjust the zero until the
transmitter output reads 4mA.
Do not use the span adjustment.
NOTE
Applying 29,9 kPa to the low side process connection (as marked
on the transmitter module) will give the same result.
4.
Apply -5,0 kPa to the high side process connection (as marked on
the transmitter sensor module). Verify the output reads 20 mA. If
necessary, adjust the span. Recheck the zero after any span
adjustment.
NOTE
Applying 5,0 kPa to the low side process connection (as marked
on the transmitter module) will give the same result.
Summary of Contents for 3152
Page 2: ......
Page 6: ...Rosemount 3150 Series Reference Manual 00809 0100 4835 Rev BD July 2016 iv ...
Page 10: ...Rosemount 3150 Series Reference Manual 00809 0100 4835 Rev BD July 2016 1 2 ...
Page 27: ...Reference Manual 00809 0100 4835 Rev BD July 2016 Rosemount 3150 Series 2 17 ...
Page 45: ...Reference Manual 00809 0100 4835 Rev BD July 2016 Rosemount 3150 Series 3 18 ...
Page 51: ...Reference Manual 00809 0100 4835 Rev BD July 2016 Rosemount 3150 Series 4 6 ...
Page 70: ...Rosemount 3150 Series Reference Manual 00809 0100 4835 Rev BD July 2016 5 19 ...