background image

Quick Installation Guide

00825-0400-4101, Rev AA
March 2011

Rosemount 2051

3

S

TEP

 1: M

OUNT

 

THE

 T

RANSMITTER

Liquid Applications

1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so that the drain/vent 

valves are oriented upward.

Gas Applications

1. Place taps in the top or 

side of the line.

2. Mount beside or above the taps.

Steam Applications

1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.

Flo

w

Flo

w

Flo

w

00825-0400-4101.fm  Page 3  Friday, March 25, 2011  1:34 PM

Summary of Contents for 2051

Page 1: ...1 Pressure Transmitter with PROFIBUS PA Rosemount 2051CF Series Flowmeter Transmitter with PROFIBUS PA Start End Step 1 Mount the Transmitter Step 2 Consider Housing Rotation Step 3 Set Jumpers and Switches Step 4 Connect the Wiring and Power Up Step 5 Basic Configuration Step 6 Trim the Transmitter Product Certifications ...

Page 2: ...ations Refer to the 2051 PROFIBUS PA reference manual document number 00809 0300 4101 for more instruction This manual is also available electronically on www emersonprocess com rosemount WARNING Explosions could result in death or serious injury Installation of this transmitter in an explosive environment must be in accordance with the appropriate local national and international standards codes ...

Page 3: ...e of the line 2 Mount beside or below the taps 3 Mount the transmitter so that the drain vent valves are oriented upward Gas Applications 1 Place taps in the top or side of the line 2 Mount beside or above the taps Steam Applications 1 Place taps to the side of the line 2 Mount beside or below the taps 3 Fill impulse lines with water Flow Flow Flow ...

Page 4: ...tallation Guide 00825 0400 4101 Rev AA March 2011 Rosemount 2051 4 STEP 1 CONTINUED Rosemount 2051C Panel Mount 1 1 Panel bolts are customer supplied Pipe Mount Coplanar Flange Traditional Flange Rosemount 2051T ...

Page 5: ...nt representative for more information Use the following bolt installation procedure 1 Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation However no additional lubricant should be applied when installing either type of bolt 2 Finger tighten the bolts 3 Torque the bolts to the initial torque value using a crossing pattern See...

Page 6: ...tallation to compensate for seating of the PTFE o ring Bolt Material Head Markings Initial Torque Final Torque Carbon Steel CS 300 in lbs 650 in lbs Stainless Steel SST 150 in lbs 300 in lbs Failure to install proper flange adapter O rings may cause process leaks which can result in death or serious injury The two flange adapters are distinguished by unique O ring grooves Only use the O ring that ...

Page 7: ...nt dust and lubrication by mounting the transmitter so that the process can drain away Figure 3 Inline Gage Low Side Pressure Port STEP 2 CONSIDER HOUSING ROTATION To improve field access to wiring or to better view the optional LCD display 1 Loosen the housing rotation set screw 2 First rotate the housing clockwise to the desired location If the desired location cannot be achieved due to thread l...

Page 8: ... labeled Security Simulate The simulate jumper is used in conjunction with the Analog Input AI block This jumper is used to simulate the pressure measurement and is used as a lock out feature for the AI block To enable the simulate feature the jumper must be moved to the ON position after power is applied This feature prevents the transmitter from being accidently left in simulate mode Figure 4 Tr...

Page 9: ...lated from touching the transmitter housing be connected to the next shield if cable is routed through a junction box be connected to a good earth ground at the power supply end 4 Plug and seal unused conduit connections 5 If applicable install wiring with a drip loop Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing 6 Replace the housing cover F...

Page 10: ... Continuously connect to the termination point c Be connected to a good earth ground at the power supply end Figure 7 Wiring 3 Replace the housing cover It is recommended that the cover be tightened until there is no gap between the cover and the housing 4 Plug and seal unused conduit connections Power Supply The dc power supply should provide power with less than two percent ripple The transmitte...

Page 11: ...0 and 125 in order to establish communication with the host Usually addresses 0 2 are reserved for masters or couplers therefore transmitter addresses between 3 and 125 are recommended Address can be set via either LOI see Table 1 and Figure 8 Class 2 master see Class 2 Master Manual for setting address Configure Engineering Units Unless otherwise requested the Rosemount 2051 Pressure Transmitter ...

Page 12: ...hanges between Save and Cancel Enter Selects menu category Enters character and advances Saves Steps Actions Set blocks to Out of Service Put Transducer Block into Out of Service mode Put Analog Input Block into Out of Service mode Select Measurement Type Set Primary Value type to Pressure Select Units Set Engineering Units Primary and secondary units must match Enter Scaling Set Scale In in Trans...

Page 13: ...s 2 master see Zero Trim via Class 2 Master for parameter settings Zero Trim via Class 2 Master 1 Place the transducer block into Out of Service OOS mode 2 Apply zero pressure to device and allow to stabilize 3 Go to Device Menu Device Calibration and set the Lower Calibration Point to 0 0 4 Place the transducer block to AUTO mode PRODUCT CERTIFICATIONS Approved Manufacturing Locations Emerson Pro...

Page 14: ...ass I Division 2 Groups A B C and D for indoor and outdoor hazardous locations Enclosure type 4X factory sealed Single Seal C6 Explosion Proof and intrinsically safe approval Intrinsically safe for Class I Division 1 Groups A B C and D when connected in accordance with Rosemount drawings 02051 1008 Temperature Code T3C For input parameters see control drawing 02051 1008 Single Seal Explosion Proof...

Page 15: ...l Conditions for Safe Use X 1 Appropriate ex d blanking plugs cable glands and wiring needs to be suitable for a temperature of 90 C 2 This device contains a thin wall diaphragm Installation maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected The manufacturer s instructions for maintenance shall be followed in detail to assure safety du...

Page 16: ...ratus E7 IECEx Explosion Proof Flame Proof Certification No IECEx KEM 08 0024X Ex d IIC T6 Tamb 50 to 65 C Ex ia IIC T5 Tamb 50 to 80 C IP66 1180 Vmax 42 4 V dc Special Conditions for Safe Use X 1 Appropriate ex d blanking plugs cable glands and wiring needs to be suitable for a temperature of 90 C 2 This device contains a thin wall diaphragm Installation maintenance and use shall take into accoun...

Page 17: ...etro Certifications E2 Flameproof Certificate number CEPEL EX 1767 09X BR Ex d IIC T6 T5 IP66 I2 Intrinsic Safety Certificate number CEPEL EX 1768 09X BR Ex ia IIC T4 IP66 IB FISCO Intrinsic Safety Certificate No CEPEL EX 1768 09X BR Ex ia IIC T4 Combinations of Certifications Stainless steel certification tag is provided when optional approval is specified Once a device labeled with multiple appr...

Page 18: ...ive and 8200 Market Boulevard Eden Prairie MN 55344 3695 Chanhassen MN 55317 9687 USA USA to which this declaration relates is in conformity with the provisions of the European Community Directives including the latest amendments as shown in the attached schedule Assumption of conformity is based on the application of the harmonized standards and when applicable or required a European Community no...

Page 19: ...ocess Flange Manifold Sound Engineering Practice ATEX Directive 94 9 EC Model 2051 Pressure Transmitter Certificate BAS08ATEX0129X Intrinsically Safe Group II Category 1 G Ex ia IIC T4 Ta 60 C to 70 C Ex ia IIC T4 Ta 60 C to 60 C FISCO Harmonized Standards Used EN60079 0 2006 EN60079 11 2007 Certificate Baseefa08ATEX0130X Type n Group II Category 3 G Ex nA nL IIC T4 Ta 40 C to 70 C Harmonized Stan...

Page 20: ...ritasveien 1 N 1322 Hovik Norway ATEX Notified Bodies for EC Type Examination Certificate KEMA KEMA Notified Body Number 0344 Utrechtseweg 310 6812 AR Arnhem P O Box 5185 6802 ED Arnhem The Netherlands Postbank 6794687 Baseefa Notified Body Number 1180 Rockhead Business Park Staden Lane Buxton Derbyshire SK17 9RZ United Kingdom ATEX Notified Body for Quality Assurance Baseefa Notified Body Number ...

Reviews: