Controller functions
Version 1
RES-407
Page 35
Part 1 of 3: Error messages as of April 2005 (faults)
NOTE:
The error messages shown here are output as faults (constant error voltage at actual value output,
alarm LED lit continuously, alarm relay energized).
Error
code
Act. val.
output
voltage
[V]
Cause
Action if machine
started for first time
Action if machine
already operated, HS
band not changed
101
0.66
No current signal
Fault area
Fault area
102
1.33
No voltage signal
Fault area
Fault area
103
2.00
No current / voltage signals
Fault area
Fault areas
107
2.66
Temperature step, down
Fault areas
("loose contact")
Fault areas
("loose contact")
108
Temperature step, up
307
Temperature too high / low
(
section 7.9)
-
-
308
309
310
201
3.33
No line frequency / line fre-
quency fluctuates
Check power supply
Check power supply
202
Line frequency too high /
fluctuates
203
Line frequency too low /
fluctuates
304
4.00
Heatup time too long
(
section 7.10)
Perform
RESET
Perform
RESET
901
4.66
No line voltage / sync signal
Replace device
Replace device
913
Triac defective
Replace device
Replace device
914
Internal fault, device defective
Replace device
Replace device
915
916
917
Jumper for alarm output incor-
rect
Check jumper
Check jumper
918