background image

R O P E X

R O P E X

R O P E X

R O P E X

INDUSTRIE - ELEKTRONIK GmbH

Page 2

1. APPLICATION AND SHORT DESCRIPTION

As all other

, this unit is used to control

the temperature of heating elements (heatseal bands,

beaded bands, cutting wires, etc.) by monitoring the

resistivity of the heating elements. Precision

measurement together with high response produces

perfect temperature control during the film sealing

processes. With a correctly installed system, the

temperature is controlled with an accuracy of ±3%.

By changing settings, this controller can be used to

control heating elements with a range of resistances from

a few milliohms to several ohms. Therefore, this universal

controller may be used in a variety of general applications

for controlling the heatseal elements in:

vertical and horizontal f/f/s machines

pouch filling and sealing machines

film wrapping machines

pouch making machines

group packaging machines, etc.

The controller,

have all the known

functions of the RES-200 series, plus two digital timers,

sealing time and cooling time. This eliminates additional

external usage of timers to control heat impulse timing

and jaw action.

This additional feature makes the controller very suitable

for use in:

hand operated and table top machines

heatsealing sealing presses

L-sealers

RES controllers

RES-241 / 242,

As shown in Section 5, a complete sealing station can be

controlled with this controller without using additional

electrical components.

All parameters related to the sealing phase, like time and

temperature, can easily be selected by use of the digital

switches on the front panel of the unit.

The desired values are entered according to the

appropriate units, i.e.

and/or

.

Numerous functional sequences can be programmed

with the dip switches mounted on side of the controller.

This allows the user to select the best program for any

specific heatsealing process.

Processes that are primarily temperature dependent can

be programmed, e.g. closing of the jaw only after full

sealing temperature has been reached; or opening of the

jaws only after the cooling to a pre-determined

temperature has been reached.

(see Section 4: Timing Functions Programming).

The cycle sequence can be observed during operation by

means of the analog temperature meter and the LED´s

for heating and cooling.

Both the

and

controllers are identical

with the exception of the "alarm function" that is contained

only in the Model RES-242.

°C

sec

RES-241

RES-242

2.

FUNCTIONS OF THE RES-241 / 242

CONTROL FUNCTIONS

The controller operates in two different modes: monito-

ring or controlling.

If there is

, the controller will only

monitor the resistance of the heating element without

raising the temperature. Resistance monitoring is

accomplished by means of short low power pulses every

10 cycles of the line frequency. It is in this mode that the

"Z" calibration is performed. In the monitoring mode, the

"ON" LED blinks red. When a START signal is applied,

LED "ON" becomes steady state red.

no START signal

The controller then goes into the regulating mode and

increases the temperature of the heating element to the

desired set point as rapidly as possible.

The maximum secondary voltage is initially supplied to

the heating element and then subsequently reduced by

the phase control as the preset maximum temperature is

approached.

A high sampling rate together with virtually instant

feedback gives the controller an instantaneous response

capability.

2.1

Summary of Contents for Resistron RES-241

Page 1: ...nd Operation Built in Timers Preferred for General Applications FEATURES TABLE OF CONTENTS 1 APPLICATION AND SHORT DESCRIPTION 2 FUNCTIONS OF THE RES 241 242 2 1 Control Function 2 2 Zero Calibration 2 3 Start Function 2 4 Cycle Timing 2 5 Alarm Function 2 5 1 Alarm Signal 2 5 2 Reset 3 CONTROLS AND INDICATORS 4 PROGRAMMING OF THE TIMING FUNCTIONS 5 EXAMPLE 6 WIRING DIAGRAM 7 OPERATING INSTRUCTION...

Page 2: ...esired values are entered according to the appropriate units i e and or Numerous functional sequences can be programmed with the dip switches mounted on side of the controller This allows the user to select the best program for any specific heatsealing process Processes that are primarily temperature dependent can be programmed e g closing of the jaw only after full sealing temperature has been re...

Page 3: ...trimmer with the heatseal element at ambient temperature and the controller in the monitoring mode Z 20 C 68 F After calibration the hand should rest quietly at Z START FUNCTION A heating cycle is initiated with the start function The controller then switches from the monitoring mode to the regulating mode and concurrently starts the timing cycles The START signal can be given in three different w...

Page 4: ...ond Functions of the RES 241 242 Continuation CYCLING TIMING Heating and cooling cycle time follow each other Depending upon the program selected by use of the DIP switch the either starts with the START signal or when the heating element reaches the pre set temperature see Section 4 Timing Functions Programming The always starts at the end of the heating cycle The maximum time duration for heatin...

Page 5: ...y Selection LED GREEN for Cooling Time LED RED for Sealing Time DIP Switch to select U2 DIP Switches for Programming of Sealing Process 1 2 3 4 5 6 7 8 9 10 ON 10 Turn ZERO Trimmer for setting Calibration to Z LED is RED when START HAND BUTTON will start controller with a full timing cycle LED RED blinks in monitoring mode remains when controller starts heating cycle LED YELLOW Indicates status of...

Page 6: ...mperature has been reached 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON A F 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON B G 1 2 3 4 5 6 7 8 9 10 ON C 1 2 3 4 5 6 7 8 9 10 ON D 1 2 3 4 5 6 7 8 9 10 ON E 1 2 3 4 5 6 7 8 9 10 ON H 4 1 PROGRAMMING THE OUTPUT RELAY tK Cooling Time tH Heating Time K1 Relay 4 2 PROGRAMMING THE HEATING TIME 4 3 PROGRAMMING FOR CONSTANT HEAT At the initial start sig...

Page 7: ... the end of the relay K1 opens the valve is deactivated and the jaws open The sealing cycle is complete cooling cycle cooling cycle time This program is the same as example 1 until the end of the heating cycle At the end of the heating cycle the cooling cycle starts and ends only when the has drop below the temperature pre selected on the COOL digital selector switch digits x 10 in C Only then the...

Page 8: ...5 4 3 12 13 14 15 16 17 18 START SWITCH START 24VDC ALARM INTERNAL ALARM RELAY RES 242 ONLY Normally open max 50V 0 2A U IR R R CURRENT TRANSFORMER HEATSEAL BAND U U1 2 PRI SEC LINE RELAY TERMINALS 100 VDC 1 5A 240 VAC 1 5A 0 K1 2x 47nF 560R POWER TRANSFORMER 6 WIRING DIAGRAM twisted FILTER ...

Page 9: ... 7 8 9 10 ON Connect the controller as shown in the wiring diagram No special attention must be given to the polarity of the measuring wires for current and voltage as well as the transformer s primary or secondary Section 12 Make sure that there is START signal at See General Installation Instructions VERY IMPORTANT NO ALARM and LED ALARM is red all wiring system must be rechecked for correct and...

Page 10: ...clockwise if the hand is on the right side turn the trimmer counter clockwise If the ZERO calibration is not possible the meter hand remains on the right side pass the wire only with the heatseal element at ambient temperature through the current transformer a second time in extreme cases a third pass might be necessary This situation might occur when the heatseal element is very long and thin hig...

Page 11: ...tput START HEATING CYCLE TIME COOLING CYCLE TIME TEMP SET POINT COOLING Phase 1 1 2 2 3 3 4 4 4 5 5 6 6 t t t JAW ACTION S S OPEN OPEN CLOSING CLOSED O P E N I N G CURRENT LED OUTPUT I2 IMAX MONITORING PULSE MONITORING PULSE A B C D Phase Jaws are opening Cooling phase set up Start of cooling time Time must be allowed for the seal to befor jaws are opened Power output is Temperature remains at set...

Page 12: ... on base for DIN rail 35 x 7 5mm oder 35 x 15mm nach DIN EN 50022 10 OUTLINE DIMENSIONS 147 75 60Hz 50Hz 130 43 32 30 136 147 PANEL JUMPER FOR LINE FREQUENCY 20mm TYPE RES XXX 0 45mm TYPE RES XXX 1 CLEAR COVER GASKET MOUNTING BRACKET TERMINAL BLOCKS OUTLINE DIMENSIONS CLEAR COVER 138 x 68 1 0 0 0 0 7 DIP SWITCH to select U2 PANEL CUTOUT CURRENT TRANSFORMER ...

Page 13: ...e Every tenth cycle 200 msec at 50Hz or 166 msec at 60Hz In controlling mode Every voltage cycle 20 msec at 50Hz or 16 6 msec at 60Hz Calibrated for heating elements with T 10 x 10 K 5 C bis 45 C Terminal Blocks with plug in connectors IP 20 Controller 1 2 kg 2 64 Ibs Current Transformer 0 15 kg 0 33 Ibs K 4 1 Page 13 11 TECHNICAL SPECIFICATIONS Type of Construction Operating Range of Line Voltage...

Page 14: ... 230 V 50 60 Hz Line Voltage Standard 230 VAC Option 115 VAC oder 400VAC Temperature Range X 3 0 300 C X 5 0 500 C X 0 X 1 Maximum Load Current see Technical Specifications X 1 Alarm X 2 Alarm without with SERIES RESISTRON Supply Controller with clear front panel gasket and mounting brackets Current transformer ...

Page 15: ...perature coefficient No additional resistances in the secondary circuit Observe the number of passes twisted No push on connectors Current measuring wires I R Correct dimensions of transformer secondary voltage power duty cycle Controller Set DIP Switch into correct position Set jumper for line frequency into proper position Voltage measuring wire U connected directly to the ends of heatseal eleme...

Reviews: