![RoofTech 100 Installation And Maintenance Manual Download Page 18](http://html1.mh-extra.com/html/rooftech/100/100_installation-and-maintenance-manual_1485324018.webp)
16
PRESSOSTATS SETTING
Factory high pressure adjustment 42bars (609.17PSI )
Clogged filter
Δ
P warning (upstream/downstream filters) > 250 Pa
Airflow detector
Δ
P warning (upstream/downstream blower)
< 50 Pa
RANGE AND SETTINGS OF THEMAL PROTECTION / NOMINAL INTENSITY OF THE
CONTACTORS (CLASSE AC3)
Model
100
120
140
160
PE
GE
PE
GE
PE
GE
PE
GE
Q1
Range
20-25A
20-25A
20-25A
24-32A
Adjustment
21A
22A
23A
32A
Q2
Range
20-25A
20-25A
20-25A
24-32A
Adjustment
21A
22A
23A
32A
Q3
Range
20-25A
20-25A
20-25A
24-32A
Adjustment
21A
22A
23A
32A
Q4
Range
20-25A
20-25A
20-25A
24-32A
Adjustment
21A
22A
23A
32A
Q5
Range
13-18A
13-18A
13-18A
13-18A
Adjustment
15A
15A
15A
15A
Q6
Range
2.5-4A
2.5-4A
2.5-4A
2.5-4A
Adjustment
3.5A
3.5A
3.5A
3.5A
Q7
Range
2.5-4A
2.5-4A
2.5-4A
2.5-4A
Adjustment
3.5A
3.5A
3.5A
3.5A
Q8
Range
13-18A
13-18A
13-18A
13-18A
Adjustment
15A
15A
15A
15A
Q9
Range
4-6.3A
4-6.3A
4-6.3A
4-6.3A
Adjustment
6A
6A
6A
6A
Contactor AC3
K1
25A
25A
25A
32A
K2
25A
25A
25A
32A
K3
25A
25A
25A
32A
K4
25A
25A
25A
32A
K5
18A
18A
18A
18A
K6
6A
6A
6A
6A
K7
6A
6A
6A
6A
K8
18A
18A
18A
18A
K9
9A
9A
9A
9A
COMPRESSORS CRANKCASE HEATER
Models
100
120
140
160
Power
W
90
65
90
65
Summary of Contents for 100
Page 2: ......
Page 29: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Page 45: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XVII CONTROL pCO1 ...
Page 46: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XVIII pCO1 ...
Page 47: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XIX pCO1 ...
Page 48: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XX pCO1 ...
Page 49: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXI POWER 1P N T P O P H N ...
Page 50: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXII ...
Page 51: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXIII ...
Page 53: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXV 1P N T P O P H N ...