background image

Instructions

and

Operating Manual

SERIES X54-201L/SR

LOOP-POWERED

INDICATOR

Summary of Contents for X54-201L

Page 1: ...Instructions and Operating Manual SERIES X54 201L SR LOOP POWERED INDICATOR ...

Page 2: ... X54C92 5 X54 201 Panel Mount Assembly 6 X54 201L SR Installation Drawing Using I S Barriers or Explosion Proof Conduit 7 Warranty Ronan warrants equipment of its own manufacture to be free from defects in material and workmanship under normal conditions of use and service and will repair or replace any component found to be defective on its return transportation charges prepaid within one year of...

Page 3: ...ground Terminals Compression type for wire size up to 14 AWG 3 0 OPERATION 3 1 General Model X54 201 is put into service by connecting it in series with 4 20 mA current loop The connections are made to the two position compression type screw terminal mounted on the lower board and accessible from the top of the module The loop indicator module needs to be removed from the enclosure in order to fee...

Page 4: ...djust the zero and span controls 3 4 Decimal Point Selection The decimal point position is selected by the position of the DP jumper plug located at the lower left edge of the display board The jumper plug can be placed in any one of the following four positions 0 1 2 or 3 and corresponds to 0 no decimal point 1 one digit to the right of the decimal point 2 two digits to the right of the decimal p...

Page 5: ... output range and 4 00 mA or set the current using the circuit of Figure 2 to 4 00 mA B Adjust the zero control for the correct span zero display C Repeat Step A using 20 00 mA D Adjust the span control for the correct span full scale display E Repeat Steps A through D until the controls no longer need adjustment 4 2 Square Root Display Model X54 201SR A Set the calibrator to its mA output range a...

Page 6: ... CAPTIVE SCREW RONAN 6 1 X54B165 1 WIRE ASSY RONAN 7 1 X54B165 2 WIRE ASSY RONAN 8 1 X54B86 1 FRONT PLATE RONAN 9 1 X54B88 BASE PLATE RONAN 10 1 XIHFGCX2LS42311 E P HOUSING ADALET 11 1 600 4 TERMINAL BLOCK KULKA 12 2 6 32 X 0 375 PH PAN HD MS 13 4 8 32 X 0 250 PH PAN HD MS 14 2 4 40 X 1 250 PH FLAT HD MS 15 4 8 INTER TOOTH LKWR 16 1 X54B229 DECAL SET X54 201 Exp Proof Assy DRAWING NUMBER X54C92 RE...

Page 7: ...G MIDDLE RONAN 4 1 X54B158 MTG RING BOTTOM RONAN 5 2 X54B159 CAPTIVE SCREW RONAN 6 1 X54C119 TERMINAL PLATE RONAN 7 1 X54B86 FRONT PLATE RONAN 8 1 X54B165 3 WIRE ASSY RONAN 9 1 GFTCX 5 TERMINAL BLOCK CURTIS 10 2 TINNERMAN NUT CURTIS 11 1 20 AWG 6 00 IN LG RED UL1429 WIRE 12 1 22 AWG 6 00 IN LG BLK UL1429 WIRE 13 1 6 32 X 0 250 PH PAN HD MS 14 2 4 40 X 1 250 PH FLAT HD MS 15 1 6 INTER TOOTH LKWR 6 ...

Page 8: ... inductance and the internal inductance Li of each FMRC Approved apparatus installed in the loop Ca The sum of the cable capacitance and the internal capacitance Ci of each FMRC Approved apparatus installed in the loop 3 Maximum safe area voltage should not exceed 250 Vrms 4 De energize supply power before disconnecting loop apparatus 5 Vmax and Imax values do not apply in explosion proof installa...

Page 9: ... com RONAN ENGINEERING LIMITED U K 1 Tilley Road Crowther Industrial Estate Washington Tyne and Wear United Kingdom NE38 OEA E Mail ronanenguk aol com Ph 191 416 1689 Fx 191 416 5856 RONAN ENGINEERING LIMITED 32 Bermondsey Road Toronto Ontario Canada M4B 1Z5 416 752 0310 FAX 416 752 8072 E Mail ronantor primus ca Printed in U S A X54 201L SR 600 ...