1.0 GENERAL DESCRIPTION

Ronan’s Models X54-201L and -201SR are 3½-digit loop
powered indicators which display linear (-201L) and
square root (-201SR) values of the associated loop
current. The loop containing one of these indicators is
barely effected as the indicators require less than 1 V to
operate. These versatile modules allow the selection of
a linear or square root display, zero value, span and
decimal point through the placement of plug-in jumpers.
Spans from 0.100 to 1999 and span zeros from  –360 to
+1300 are selected by the plug-in jumpers. The decimal
point selector plug may be placed in any one of four
positions which selects one, two or three digits to the
right of the decimal point or in position 0 for no decimal
point. 

2.0  SPECIFICATIONS

Note:

Specifications apply at 25ºC ± 2ºC unless

otherwise stated. Specifications subject to change
without notice.

Input:

4-20 mA.

Input Protection:

Diode protected against

reverse polarity.

Voltage Drop:

Less than 1 V.

Span Selection:

Spans from 0.100 to 1999 digits are

selected by DIP-switch settings accessible at the top
board of the module. Refer to Table 3-1 on page 3.

Span Adjustment:

Front-accessible, multi-turn

potentiometer allows ± 20% adjustment of all ranges.

Zero-offset Selection:

Offsets from –360 to +1300

digits are selected by DIP-switch settings accessible at
the top board of the module. Refer to Table 3-2 on
page 3.

Zero Adjust:

Front accessible, multi-turn potentiometer

allows ± 10%  adjustment of selected span range.

Decimal Point Selection:

Plug-in jumpers, accessible

at the top board of the module, allow selection of the
decimal point position. See section 3.5.

Accuracy:

Linear Display:

± 0.1% of span or ±1 digit. 

Square Root Display:

± 0.3% of span or ± 1 digit

(applies from 4.3 to 20 mA input).

Operating Ambient Temperature Range:  

–10º to

+55ºC.

Temperature Coefficient:

Zero

: ± 0.01% of Span/ºC, ± 0.01% of elevated zero

value/ºC. 

Span

: ± 0.015% of Span/ºC.

Display:

3½-digit LCD, black digits on a reflective

background.

Terminals:

Compression type for wire size up to #14

AWG.

3.0  OPERATION

3.1 General

Model X54-201 is put into service by connecting it
in series with 4-20 mA current loop. The
connections are made to the two-position
compression-type screw terminal mounted on the
lower board and accessible from the top of the
module.  The loop indicator module needs to be
removed from the enclosure in order to feed the
wires past the bottom board and into the screw
terminals.  To remove the module from the
explosion-proof enclosure: 

A. Unscrew and remove the enclosure cap.  
B. Snap off the top plate of the module and insert

your index finger into cutout and remove the
plate.

C. Loosen the two module captive mounting

screws until the module is free.

D. Remove the module from the enclosure and

fasten the input wiring to the screw terminals.

E. Connect the lead that returns back to the –

output of the power supply, either directly or
through a two wire transmitter, to the – terminal
of the X54-201. Connect the other wire to the +
terminal. See Figure 3-1.

F. Re-install the module and enclosure cap.

The Model X54-201 Loop Powered Indicator is
normally shipped calibrated to ranges as specified
by the purchaser. However, it is designed to allow
easy reconfiguration in the field. The span is
changed by changing the position of one or two of
the SW1 switches -1 through -5. The span zero
value is changed by changing the settings of SW2
switches -1 through -6 and SW1-6.

Figure 3-1:

Wiring Diagram

2

X54-201 Approvals (_PM2 and _EXP2)

Factory Mutual Approvals

-EXP2 Housing

= Explosion Proof

-Class I-III, Div. 1, Grps B-G and NEMA 4

= Intrinsic Safe

-Class I-III, Div, Div. 1, Grps A-G and NEMA 4

-PM2 Housing

= Div. 2 Applications -Class I, Div. 2, Grps A-D

= Intrinsic Safe

-Class I, Div.1, Grps A-D

CSA Approvals

-EXP2 Housing

= Explosion Proof

-Class I-II, Div. 1, Grps B-G

= Intrinsic Safe

-Class I-II, Div. 1, Grps A-G

= Div. 2 Applications -Class I-II, Div. 2, Grps A-G

-PM2 Housing

= Div. 2 Applications -Class I, Div. 2, Grps A-D

= Intrinsic Safe

-Class I-II, Div. 1, Grps A-G

CENELEC Approvals

X54-201-MI (EXP housing)

Intrinsic Safe

-EEx ia IIC T4 (Tamb = 85°C)

-EEx ia IIC T5

X54-201-MX (EXP Housing)

Flame Proof

-EEx d IIC T6

-

+

Summary of Contents for X54-201L

Page 1: ...Instructions and Operating Manual SERIES X54 201L SR LOOP POWERED INDICATOR ...

Page 2: ... X54C92 5 X54 201 Panel Mount Assembly 6 X54 201L SR Installation Drawing Using I S Barriers or Explosion Proof Conduit 7 Warranty Ronan warrants equipment of its own manufacture to be free from defects in material and workmanship under normal conditions of use and service and will repair or replace any component found to be defective on its return transportation charges prepaid within one year of...

Page 3: ...ground Terminals Compression type for wire size up to 14 AWG 3 0 OPERATION 3 1 General Model X54 201 is put into service by connecting it in series with 4 20 mA current loop The connections are made to the two position compression type screw terminal mounted on the lower board and accessible from the top of the module The loop indicator module needs to be removed from the enclosure in order to fee...

Page 4: ...djust the zero and span controls 3 4 Decimal Point Selection The decimal point position is selected by the position of the DP jumper plug located at the lower left edge of the display board The jumper plug can be placed in any one of the following four positions 0 1 2 or 3 and corresponds to 0 no decimal point 1 one digit to the right of the decimal point 2 two digits to the right of the decimal p...

Page 5: ... output range and 4 00 mA or set the current using the circuit of Figure 2 to 4 00 mA B Adjust the zero control for the correct span zero display C Repeat Step A using 20 00 mA D Adjust the span control for the correct span full scale display E Repeat Steps A through D until the controls no longer need adjustment 4 2 Square Root Display Model X54 201SR A Set the calibrator to its mA output range a...

Page 6: ... CAPTIVE SCREW RONAN 6 1 X54B165 1 WIRE ASSY RONAN 7 1 X54B165 2 WIRE ASSY RONAN 8 1 X54B86 1 FRONT PLATE RONAN 9 1 X54B88 BASE PLATE RONAN 10 1 XIHFGCX2LS42311 E P HOUSING ADALET 11 1 600 4 TERMINAL BLOCK KULKA 12 2 6 32 X 0 375 PH PAN HD MS 13 4 8 32 X 0 250 PH PAN HD MS 14 2 4 40 X 1 250 PH FLAT HD MS 15 4 8 INTER TOOTH LKWR 16 1 X54B229 DECAL SET X54 201 Exp Proof Assy DRAWING NUMBER X54C92 RE...

Page 7: ...G MIDDLE RONAN 4 1 X54B158 MTG RING BOTTOM RONAN 5 2 X54B159 CAPTIVE SCREW RONAN 6 1 X54C119 TERMINAL PLATE RONAN 7 1 X54B86 FRONT PLATE RONAN 8 1 X54B165 3 WIRE ASSY RONAN 9 1 GFTCX 5 TERMINAL BLOCK CURTIS 10 2 TINNERMAN NUT CURTIS 11 1 20 AWG 6 00 IN LG RED UL1429 WIRE 12 1 22 AWG 6 00 IN LG BLK UL1429 WIRE 13 1 6 32 X 0 250 PH PAN HD MS 14 2 4 40 X 1 250 PH FLAT HD MS 15 1 6 INTER TOOTH LKWR 6 ...

Page 8: ... inductance and the internal inductance Li of each FMRC Approved apparatus installed in the loop Ca The sum of the cable capacitance and the internal capacitance Ci of each FMRC Approved apparatus installed in the loop 3 Maximum safe area voltage should not exceed 250 Vrms 4 De energize supply power before disconnecting loop apparatus 5 Vmax and Imax values do not apply in explosion proof installa...

Page 9: ... com RONAN ENGINEERING LIMITED U K 1 Tilley Road Crowther Industrial Estate Washington Tyne and Wear United Kingdom NE38 OEA E Mail ronanenguk aol com Ph 191 416 1689 Fx 191 416 5856 RONAN ENGINEERING LIMITED 32 Bermondsey Road Toronto Ontario Canada M4B 1Z5 416 752 0310 FAX 416 752 8072 E Mail ronantor primus ca Printed in U S A X54 201L SR 600 ...

Reviews: