Illustration 26: Dual CAN Bus with Redundant IM
X11CB INSTALLATION AND OPERATION
2.6.2.Redundant Configurations
An option to the X11CB is the addition of a second Interface Module on the same Lamp
Cabinet known as a redundant Interface Module. The two interface modules operate
independently over the same or different LANs. Each Interface Module talks to each of
the Alarm Modules across a separate CAN bus. The redundant Interface Module
communicates to a separate Alarm Module as a daughter card in the Host Alarm Module
Unit.
2.6.3.Input Response Time
The default response time of each point is
1 millisecond
, but it can be modified using the
X11CB operating software.
32
X11CB-3031-IOM