4. Select
Level Cal
.
5. Select
Do Lvl Lo Cal
. The system warns you that the previous values for the low level cali-
bration will be replaced. Click
OK
.
6. The system warns you that this will remove the loop from automatic control. Click
OK
.
7. The system reminds you to verify that the source is on and the vessel is at a low level.
Click
OK
.
8. The next screen shows you that the system is calibrating the low level.
9. The system displays the counts for the new low level. Click
OK
to accept,
ABORT
to can
cel.
10. Record the new value.
#[%''%+!>!'+!"B"#
Perform the High Level Calibration
]B!>!''%%%?'%!>'%B"!B!"'#[%?B
low these steps to perform the calibration:
NOTE:
It is ideal to perform the high level calibration when the vessel is full. If that is not feasible, the
other options can be considered:
< If the typical vessel is greater than 36” in diameter, you can close the shutter (in the off
position) before doing the calibration which typically represents a full vessel.
< Fill the vessel to at least 75% or greater before doing the calibration.
1. Select
Do Lvl Hi Cal
. The system warns you that the previous values for the high level
calibration will be replaced. Click
OK
.
2. The system warns you that this will remove the loop from automatic control. Click
OK
.
3. The system reminds you to verify that the source is on and the vessel is at a high level.
Click
OK
. The following screen appears, showing you that the system is calibrating the
high level.
40
Summary of Contents for X96SI/R
Page 2: ...2 Revisions 11 11 18 8 14 20 ...
Page 4: ...Chapter 1 Introduction 4 ...
Page 17: ...17 ...
Page 18: ...Chapter 2 Quick Start 18 ...
Page 24: ...24 ...
Page 25: ...Chapter 3 Installing the Level with Density Compensation Gauge 25 ...
Page 34: ...34 ...
Page 35: ...Chapter 4 Density Compensation Gauge 35 ...
Page 71: ... 71 ...
Page 72: ... Cont d 72 ...
Page 74: ...74 ...
Page 75: ...75 ...
Page 76: ...76 ...
Page 78: ...78 ...
Page 79: ...79 ...
Page 81: ...8 0 Display Menu The Display menu includes the following options 81 ...
Page 82: ...82 ...
Page 84: ...84 ...
Page 85: ...85 ...
Page 86: ...86 ...
Page 87: ...87 ...
Page 88: ...88 ...
Page 89: ...Chapter 5 Troubleshooting the Level with Density Compensation Gauge 89 ...
Page 101: ...Calibrate Density Dens Cal Const The Dens Cal Const menu includes the following items 101 ...
Page 111: ...111 ...
Page 112: ...112 ...
Page 113: ...113 ...
Page 114: ...114 ...
Page 115: ... 115 ...
Page 117: ...117 ...
Page 118: ...118 ...
Page 119: ...119 ...
Page 120: ...120 ...
Page 121: ...6 0 File System Menu The File System menu includes the following items 121 ...
Page 123: ...123 ...
Page 124: ...124 ...
Page 125: ...5 J Y 125 ...
Page 127: ...127 ...
Page 128: ...128 ...
Page 129: ...8 0 Display Menu The Display menu includes the following options 129 ...
Page 132: ...132 ...
Page 133: ...133 ...
Page 134: ...134 ...
Page 135: ...135 ...
Page 136: ...136 ...