Page 22
RS500/600 Series Doors
Part No 4801-5158 Rev 1-2017
13
Jog Mode
The Jog Mode will permit an operator to manually control the
position of the door with the
Up
(
)
and
Down
(
)
arrow
buttons. To enter the Jog Mode, press both the
Up
(
)
and
Down
(
)
arrows at the same time for at least 5 seconds. The
controller will indicate the Jog Mode in the display as shown
below.
In the Jog Mode the door can be opened and closed and is not
affected by the Home Limit Switch or the Safety Beam. The
operator must carefully watch the door movement when nearing the full open and full closed positions. To exit the
Jog Mode, press and hold the
Up
(
)
and
Down
(
)
arrow buttons for at least 5 seconds. The Controller will
return to the normal operating mode with the Actual Position shown in the display.
When returning to the normal operating mode, the controller will not know the exact position that the operator has
left the door when exiting the Jog Mode. Therefore, the Controller will display a series of three horizontal bars.
Upon the next command the door will slowly proceed to the full open position to reset its memory. The door will
always follow this procedure after exiting the Jog Mode.
14
SC-325 & SC-650 Drive Diagnostics LEDs
KB Drive Diagnostic LEDs
Door Idle
PWR
LED
ST LED
Operating Condition
Possible Causes
OFF OFF
Drive
is
Off
No AC Power Applied
Fuse Blown
Defective Drive
Green
Steady Yellow
Normal Condition
Green Quick
Flash
Red/Yellow
AC Input Under voltage
Input AC=115 VAC/Drive Jumper set on
230 VAC
Green Slow
Flash
Red/Yellow
AC Input Overvoltage
Input AC=230 VAC/Drive Jumper set on
115 VAC
Green
Steady Red
Current Overload
Drive tripped due to current overload
Green
Red/Yellow/Green
Under voltage or
Overvoltage
Drive tripped due to out of range voltage
condition
Door Moving
PWR
LED
ST LED
Operating Condition
Possible Causes
Green
Slow Flash Green
Normal Condition
Green Quick
Flash
Red Overcurrent
Drive operating at 120%-200% of full
rated load
Green
Slow Flash Red
Short Circuit
Two phases may be shorted
Phase may be shorted to ground
Gear motor may be defective
Status
LED
Slow Flash = LED flashes 1 second off, 1 second on
Quick Flash = LED flashes 0.25 second off,
0.25 second on
Steady = LED is constantly on
Actual Position
Open Speed
Close Speed
TotalCycles
Service Cycles
Door Obstruction
(Cycles 100)
Mode
JOG
JOG Mode
Summary of Contents for RS-500 Series
Page 20: ...Page 20 RS500 600 Series Doors Part No 4801 5158 Rev 1 2017 AC DC Harness ...
Page 31: ...Part No 4801 5158 Rev 1 2017 RS500 600 Series Doors Page 31 Brake Rectifier Jumper ...
Page 41: ...Part No 4801 5158 Rev 1 2017 RS500 600 Series Doors Page 41 23 4 Matrix2 Loop Sensor ...
Page 43: ...Part No 4801 5158 Rev 1 2017 RS500 600 Series Doors Page 43 ...
Page 44: ...Page 44 RS500 600 Series Doors Part No 4801 5158 Rev 1 2017 ...