background image

 

Part No 4801-5314 Rev 06-2015 

Float & Pump Replacement 

 PolarCool 

RollSeal, Inc.  •  1733 County Road 68  •  Bremen, Alabama 35033  •  256-287-7000 

Thumb 
Screw 

Decrease 
Water Level 

Increase 
Water Level 

Float Arm 

PolarCool Float & 

Pump Replacement 

Floats Mounted Through the Side of the Cabinet 

 NOTE: Water source must be disconnected to remove and replace float. 

1.

 

Before removing float, ensure electrical power has been 
disconnected and water supply is removed.   

2.

 

Remove the Pads. See manual 4801-5035 PolarCool User’s 
Manual for more information.  

3.

 

Note the Float location inside and outside the unit. Inside, it 
is located in the far left lower corner of the pan (See 
Illustration 1). Outside, it is located on the lower right of the 
front (See Illustration 2).   

4.

 

Two people may be helpful for replacement. Loosen the float 
hose adapter and lock nut located on the outside of the unit.   

5.

 

Remove the float from the inside. 

6.

 

Replace with the new float. 

7.

 

Attach the float on the outside of the unit with the lock nut and hose 
adapter. Wrap the float threads with thread seal tape. 

8.

 

Check tightness of water hose connections. 

9.

 

Restore the water source and fill the reservoir. Ensure that the water 
fills to the correct level. 

NOTE:  Water level in reservoir is normally 2-1/4" 

 1".  Do not allow the reservoir water to 

contact the pads when the reservoir water 
level is at the highest point.

 

Float Adjustment 

1.

 

Loosen adjustment screw as shown in Illustration 3. 

2.

 

To decrease water level in reservoir, move float arm downward 
as shown.  Retighten adjustment screw. 

3.

 

To increase water level in reservoir, move float arm upward as 
shown.   
Retighten adjustment screw. 

4.

 

Replace pads.   

5.

 

Reconnect power and run the Pump for at least 15 minutes  
to soak the Pad(s). 

6.

 

Turn the fan ON. 

NOTE:  Do not allow the pump to run  

without water in the reservoir.   
Without water, the pump may be damaged. 

 Warning! 

Disconnect All Power Sources Before Installing This Equipment! Failure To  

Disconnect Power Source Can Result In Property Damage, Serious Injury Or Death! 

!

 

Illustration 1 

Illustration 2 

Lock Nut 

Adapter 

Float 

Illustration 3 

Reviews: