10
NEC 310-15 restricts the minimum wire size for a 30-amp circuit to 10-gauge.
12-gauge may be used for installations of 20 amps or less, provided that the
length of the wire does not cause a significant voltage drop. Ideally the voltage
drop in any of your wiring runs should be 2% or less of the system voltage: for
example, this would be approximately 0.24 volts for a 12-volt system, or 0.48
volts for a 24-volt system. Refer to Tables 4.2.1 and 4.2.2 for help in
determining the proper gauge of wire when factoring in voltage drop and
distance.
#12
#10
#8
#6
#4
#2
5A
30
47
75
119
190
302
10A
15
24
37
60
95
151
15A
10
16
25
40
63
101
20A
7
12
19
30
47
75
25A
—
9
15
24
38
60
30A
—
8
12
20
32
50
Table 4.2.1. Maximum distance (in feet) for wire at a specific gauge and cur-
rent, which will result in no more than a 0.24v (2%) voltage drop when used
with a 12-VOLT nominal system. Divide these distances in half for a round-trip
(both positive and negative) wire run.
#12
#10
#8
#6
#4
#2
5A
59
94
150
238
379
604
10A
30
47
75
119
190
302
15A
20
31
50
79
126
201
20A
15
24
37
60
95
151
25A
—
19
30
48
76
121
30A
—
16
25
40
63
101
Table 4.2.2. Maximum distance (in feet) for wire at a specific gauge and cur-
rent, which will result in no more than a 0.48v (2%) voltage drop when used
with a 24-VOLT nominal system. Divide these distances in half for a round-trip
(both positive and negative) wire run.