background image

MCX4D Operating Manual.doc 

  

2018-07-20 

 

12/15 

 

  Connect the device to RUD-1 interface according to fig. 9 

  Place jumper on FDM pins 

  Press RES button 

  Start RogerVDM software 

  In the top menu select 

Tools->Update firmware

 

  Select device type and communication port with RUD-1 device as well as indicate firmware file 

(*.hex) 

  Click 

Update

 and proceed according to displayed messages 

  After firmware upload, remove jumper from FDM pins and press RES button 

Note: When firmware is updated then it is necessary to configure the device with RogerVDM software or 
start memory reset procedure and manually define the address of device. 

 

Fig. 9 Connection of expander to RUD-1 (firmware update) 

Installation 

Enclosure with DIN rail is recommended for installation of MCX4D expander. All electric connections must 
be done without voltage on wires/terminals and with power supply disconnected. Optionally, DIN rail 
mounting clips can be removed and the expander can be installed on flat surface. It is recommended to 
install the expander in the same enclosure as PSU. The cross section of power supply wires must be 
adequate as to avoid voltage drop greater than 200mV for rated load. It is recommended to use cables with 
minimal 1mm

2

 cross section and maximal 30 cm length. Such cables are offered with PSxD series power 

supply units. Prior to expander connection to the controller specify RS485 address and configure other 
electric parameters if necessary. The expander is configured within low level configuration by means of 
RogerVDM. Default address of factory new device is ID=100. 
 

Summary of Contents for MCX4D

Page 1: ...Roger Access Control System MCX4D I O expander Operating Manual Product version 1 0 Firmware version 1 1 14 189 Document version Rev D ...

Page 2: ...ch facilitate electrical connections during installation and maintenance MCX4D can be also used with PRT and Wiegand readers and then such readers must be connected to the controller directly or through dedicated expanders e g MCX402DR MCX102DR MCX16 NT Inputs and outputs of the expander can be configured to any functions and used for purposes not related to door control MCX4D is offered individua...

Page 3: ...ries PSUs Roger are offered with two 30cm 1mm cables dedicated to supply the expander Multiple MCX4D expanders can be supplied from the same PSU and in such case each connection must be made with individual pair of cables When expander s supply voltage is too low the battery cannot be fully charged and when the voltage is too high the battery can be damaged MCX4D which is supplied from PSU equippe...

Page 4: ...tored In order to ensure battery charging up to 80 level within 24h according to EN 60839 standard following current settings must be applied 0 3A for 7Ah battery 0 6A for 17Ah battery 0 9A for 24Ah battery RS485 communication bus distribution MCX4D is an addressable device connected to RS485 communication bus of the controller The bus is distributed to each controlled door Prior to connection the...

Page 5: ... EOL 2EOL 3EOL or DW Double Wiring types It is also possible to configure input response time which defines minimal pulse which can trigger the input The configuration of input electrical parameters is done within low level configuration by means of RogerVDM software Each input can be assigned with function In standard scenario of door control DC input is dedicated to connection of door contact wh...

Page 6: ...d RS485 communication bus to four doors For each door the MCX4D offers 1 0A power supply output VDR and VDR terminals 0 2A power supply output TML and TML terminals communication bus RS485 A and B terminals two programmable inputs DC and DR and two programmable outputs LCK and BELL The 1 0A output is dedicated to supply door lock and door related devices e g alarm signalling device The 0 2A output...

Page 7: ...roller Connection of multiple expanders to controller In the figure below an example of system including multidoor MC16 access controller and three MCX4D expanders is presented In general perspective the maximal number of expanders connected to the controller equals the number of unoccupied addresses on RS485 bus Each MCX4D can be equipped with own battery and be supplied from its own PSU It is al...

Page 8: ...ually within memory reset procedure Configuration parameters Code Name Function Communication settings 101 RS485 address Parameter defines device address on RS485 bus Range 100 115 106 Communication lost signalisation delay s Parameter defines delay before indicating communication lost with controller Range 0 64s When set to 0 the parameter is disabled Input types 210 DC1 Parameter defines input t...

Page 9: ...DR4 as above Output polarity 150 LCK1 Parameter defines output polarity Output with normal polarity represents high impedance in normal state and is shorted to ground when triggered Output with reversed polarity is shorted to ground in normal state and represents high impedance when triggered Range 0 Normal polarity default 1 Reversed polarity 151 BELL1 as above 152 LCK2 as above 153 BELL2 as abov...

Page 10: ...K4 comment as above 658 Object BELL4 comment as above Device configuration The expander is configured within low level configuration by means of RogerVDM software The address of expander can also be programmed manually within memory reset procedure Fig 8 Connection of expander to RUD 1 configuration Memory reset Turn power supply off Place jumper on MEM pins Connect LCK1 and DC1 terminals Turn pow...

Page 11: ...ice shall enter Service mode and LED RUN shall pulsate Start RogerVDM software From the top menu select Device New select your device model and version then click Connect button When the connection is established then the software shall download and display current settings of the device Configure settings as needed Click Send to Device to upload settings Click Send to File to backup settings From...

Page 12: ...ation Enclosure with DIN rail is recommended for installation of MCX4D expander All electric connections must be done without voltage on wires terminals and with power supply disconnected Optionally DIN rail mounting clips can be removed and the expander can be installed on flat surface It is recommended to install the expander in the same enclosure as PSU The cross section of power supply wires m...

Page 13: ...LED signals lack of external power supply In case of Memory reset the LED is used for manual addressing Single pulse every 4 sec Normal mode Quick pulsing Service mode Slow pulsing 0 5s 0 5s No communication with controller Very slow pulsing 1s 1s Configuration memory error Data transmission to controller Data receiving from controller MCX4D terminals Terminal Function BAT Battery positive pole BA...

Page 14: ...n collector output BELLx Transistor open collector output DCx Parametric input DRx Parametric input Specification Parameter Value Power supply voltage 13 8VDC 100mV with backup battery connected 10 15VDC no backup battery Power supply current Expander 50mA Expander with maximal load at power outputs and maximal 0 9 battery charging current 6 0A VOUT general purpose output power 13 8VDC 0 2A overlo...

Page 15: ... The user is obliged to deliver equipment to the designated collection points of electric and electronic waste For detailed information on recycling contact your local authorities waste disposal company or point of purchase Separate collection and recycling of this type of waste contributes to the protection of the natural resources and is safe to health and the environment Weight of the equipment...

Reviews: