Table 1. Screw terminals 

Screw terminal 

Description 

+12V 

12VDC power supply 

GND 

Ground 

RS485 bus, line A 

RS485 bus, line B 

COM 

REL relay common terminal 

NC 

REL relay output (NC) 

NO 

REL relay output (NO) 

IN1 

IN1 input line 

IN2 

IN2 input line 

IN3 

IN3 input line 

OUT1 

OUT1 output line 

OUT2 

OUT2 output line 

1,2,3,4,5,6,7,8 

Ethernet port 

 

Table 2. Specification 

Supply voltage 

Nominal 12VDC, min./max. range 10-15VDC 

Current 

consumption 

(average) 

~110 mA 

Inputs 

Three  parametric  inputs  internally  connected  to 
the  power  supply 

plus  (+12V)  through  a  5.6kΩ 

resistor,  approx.  3.5V  triggering  level  when 
configured as NO or NC. 

Relay output 

Relay  output  with  single  NO/NC  contacts,  rated 
30V/1.5A 

Transistor outputs 

Two  (IO1,IO2)  open  collector  outputs,  15VDC/1A 
rated 

Tamper protection 

Enclosure opening reported to access controller 

Identification methods 

ISO/IEC14443A 

MIFARE 

Ultralight, 

Classic, 

Desfire EV1 and Plus proximity cards 
Mobile device (Android, iOS) compatible with NFC 
Mobile  device  (Android,  iOS)  compatible  with 
Bluetooth Low Energy v4.1 

Reading range 

Up to 7 cm for MIFARE and NFC 
Up  to  10  m  for  BLE 

–  depends  on  ambient 

conditions and particular mobile device. Terminal’s 
radio  power  can  be  increased  within  low  level 
configuration. 

Distances 

Up  to  1200  m  between  controller  and  terminal 
(RS485) 

IP Code 

IP41 

Environmental class 
(acc. to EN 50133-1) 

Class  I,  indoor  general  conditions,  temperature: 
+5°C  to  +40°C,  relative  humidity:  10  to  95%  (no 
condensation) 

Dimensions H x W x D  

85 x 155,5 x 21,5 mm 

Weight 

190g 

Certificates 

CE 

 

 

Fig. 5 Connection of terminals and expanders to MC16 access controller 

 

Fig. 6 Connection of door lock, door contact and exit button to MCTxx-IO 
terminal 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

This  symbol  placed  on  a  product  or  packaging  indicates  that  the 
product  should  not  be  disposed  of  with  other  wastes  as  this  may 
have a negative impact on the environment and health. The user is 
obliged  to  deliver  equipment  to  the  designated  collection  points  of 
electric and electronic waste. For detailed information on recycling, 
contact  your  local  authorities,  waste  disposal  company  or  point  of 
purchase.  Separate  collection  and  recycling  of  this  type  of  waste 
contributes to the protection of the natural resources and is safe to 
health and the environment. Weight of the equipment is specified in 
the document. 

 

Contact: 

Roger Sp. z o. o. sp. k. 

82-400 Sztum 

Gościszewo 59 

Tel.: +48 55 272 0132 
Fax: +48 55 272 0133 

Tech. support: +48 55 267 0126 

E-mail: 

[email protected]

 

Web

www.roger.pl

 

Reviews: