background image

 

 

1/2 

 

Roger Access Control System 

MCT62E Installation Manual 

Firmware version: 1.1.30.266 and higher 

Document version: Rev. C 

 

This  document  contains  minimum  information  that  is  necessary  for  initial  setup 
and  installation  of  the  device.  The  detailed  description  of  configuration 
parameters  and  functionalities  is  specified  in  respective  Operating  manual 
available a

www.roger.pl

I

NTRODUCTION

 

The  reader  is  designed  for  operation  with  MC16  access  controller  (RACS  5 
system). Factory new reader is configured with default settings including ID=100 
address. 

D

EVICE CONFIGURATION

 

The  reader  can  be  configured  in  regard  of  various  parameters  (including 
address)  in  order  to  adapt  it  to  the  requirements  of  specific  installation.  Device 
can  be  configured  from  VISO  v2  management  software  or  RogerVDM  utility 
software. 

Note:  Remote  configuration  of  device  from  VISO  v2  software  is  possible  only  if 
jumper  is  placed  on  MEM  contacts  (fig.  3).  If  the  jumper  is  removed  then  such 
configuration is blocked. In case of factory new device, jumper is placed on MEM 
contacts. 

C

ONFIGURATION WITH 

VISO

 V

2

 PROGRAM

 

In  RACS  5  v2  system  the  reader  can  be  installed  at  site  without  previous 
configuration.  According  to  AN006  application  note,  its  address  and  other 
settings can be configured from VISO v2 management software and during such 
configuration the access to its service contacts (fig. 3) is not required. 

C

ONFIGURATION WITH 

R

OGER

VDM

 PROGRAM

 

 

Fig. 1 Connection of MCT reader to RUD-1 interface for configuration 

Programming procedure with RogerVDM software: 

1.  Connect  the  device  to  RUD-1  interface  (fig.  1)  and  connect  the  RUD-1  to 

computer’s USB port. 

2.  Remove jumper from MEM contacts (fig. 3) if it is placed there. 
3.  Restart the device (switch power supply off and on or short RST contacts for 

a  moment)  and  orange  LED  SYSTEM  will  pulsate.  Then  within  5  seconds 
place jumper on MEM contacts. 

4.  Start  RogerVDM  program,  select 

MCT

  device,  firmware  version, 

RS485

 

communication channel and serial port with RUD-1 interface. 

5.  Click 

Connect,

  the  program  will  establish  connection  and  will  automatically 

display 

Configuration

 tab. 

6.  Enter  unoccupied  RS485  address  in  range  of  100-115  and  other  settings 

according to requirements of specific installation. 

7.  Click 

Send to Device

 to update the configuration of device. 

8.  Optionally  make  a  backup  by  clicking 

Send  to  File… 

and  saving  settings  to 

file on disk. 

9.  Disconnect  from  RUD-1  interface  and  leave  jumper  on  MEM  contacts  to 

enable  further  configuration  of  device  from  VISO  v2  software  or  remove 
jumper from MEM contacts to block such remote configuration. 

Note: Do not read any cards when the device is configured with RogerVDM. 

M

ANUAL ADDRESSING

 

Manual addressing procedure enables configuration of new RS485 address with 
all other settings unchanged. 

Manual addressing procedure: 

1.  Remove all connections from A and B lines. 
2.  Remove jumper from MEM contacts (fig. 3) if it is placed there. 
3.  Restart the device (switch power supply off and on or short RST contacts for 

a  moment)  and  orange  LED  SYSTEM  will  pulsate.  Then  within  5  seconds 
place jumper on MEM contacts. 

4.  Enter  3  digits  of  RS485  address  in  range  of  100-115  with  any  EM  125kHz 

card. 

5.  Leave jumper on MEM contacts to enable further configuration of device from 

VISO v2 software or remove jumper from MEM contacts to block such remote 
configuration. 

6.  Restart the device. 

Readers without keypad can be addressed with multiple card readings where the 
N  number  of  readings  emulates  digit  of  the  address.  Three  series  of  readings 
with any EM 125kHz proximity card are necessary to set the address. After each 
series wait for two beeps and proceed with the next digit. Zero digit is emulated 
with 10 readings. 
Example: 
Programming of ID=101 address with card readings:  

1.  Read card 1 time and wait for two beeps. 
2.  Read card 10 times and wait for two beeps. 
3.  Read card 1 time and wait for two beeps. 
4.  Wait till reader is restarted with the new address. 

M

EMORY RESET

 

Memory  reset  procedure  resets  all  settings  to  factory  default  ones  including 
ID=100 address. 

Memory reset procedure: 

1.  Remove all connections from A and B lines. 
2.  Remove jumper from MEM contacts (fig. 3) if it is placed there. 
3.  Restart the device (switch power supply off and on or short RST contacts for 

a  moment)  and  orange  LED  SYSTEM  will  pulsate.  Then  within  5  seconds 
place jumper on MEM contacts. 

4.  Read any EM 125kHz card 11 times. 
5.  Wait till device confirms reset with long acoustic signal. 
6.  Leave jumper on MEM contacts to enable further configuration of device from 

VISO v2 software or remove jumper from MEM contacts to block such remote 
configuration. 

7.  Restart the device. 

F

IRMWARE UPDATE

 

The  firmware  of  device  can  be  changed  to  newer  or  older  version.  The  update 
requires  connection  to  computer  with  RUD-1  interface  (fig.  2)  and  starting 
RogerVDM software. The latest firmware file is available a

www.roger.pl

Firmware update procedure: 

1.  Connect  the  reader  to  RUD-1  interface  (fig.  2)  and  connect  the  RUD-1  to 

computer’s USB port. 

2.  Place jumper on FDM contacts (fig. 3). 
3.  Restart the reader (switch power supply off and on or short RES contacts for 

a moment). 

4.  Start RogerVDM program and in the top menu select 

Tools

 and then 

Update 

firmware

5.  In  the  opened  window  select  device  type,  serial  port  with  RUD-1  interface 

and path to firmware file (*.hex). 

6.  Click 

Update 

to start firmware upload with progress bar in the bottom. 

7.  When  the  update  is  finished,  disconnect  from  RUD-1  interface  and  remove 

jumper  from  FDM  contacts.  Additionally  it  is  recommended  to  start  memory 
reset procedure. 

 

Fig. 2 Connection of MCT reader to RUD-1 interface for firmware update 

Reviews: