Roger LRT-1 Operating Manual Download Page 7

LRT-1 Operating Manual.doc

 

2018-09-06 

 

 

7/13 

 

Configuration with RogerVDM software 

The address and other settings can be programmed with RogerVDM program (Windows). The connection to 
computer requires RUD-1 USB-RS485 interface. 

Procedure for programming with computer: 

 

Make connections as in fig. 5 

 

Place jumper on MEM contacts 

 

Connect RUD-1 to computer USB port 

 

Start RogerVDM software 

 

Select 

MCI-1 interface and RS485 communication channel. 

 

In the field 

Serial port select serial COM port with RUD-1 interface 

 

The program will establish connection with the device and it will display its current settings 

 

Configure MCI-1 as required 

 

Select 

Send to Device to upload new settings 

 

Optionally select 

Send to File… to backup your settings in file 

 

In the top menu select 

Device and Disconnect 

 

Connect device to your system 

 

Fig. 5 Connection of MCI-1 to RUD-1 interface (configuration) 

Summary of Contents for LRT-1

Page 1: ...Roger Access Control System LRT 1 reader Operating Manual Product version v1 0 Document version Rev A ...

Page 2: ...tput or from dedicated power supply Due to relatively high supply current 300mA wire diameter must be selected in such way that voltage drop between supply output and the reader is less than 1V The proper wire diameter is especially critical when reader is located in long distance from the supply source In such a case the use of dedicated power supply located close to the reader should be consider...

Page 3: ...then the range is reduced approximately by 15 If the reader is installed in a distance lower than 15 cm from metal wall then card reading might be not possible at all If the LRT 1 is mounted on metal pole with maximal cross section of 10x10 cm then reading range is reduced by 15 Note Reading range may be slightly reduced approx by 5 if supply voltage is in range of 11 12V Such reduction results fr...

Page 4: ...rt When contacts are shorted for a moment then interface restarts After restart LED_SY orange indicator is pulsing for 2s MEM Service mode When contacts are shorted then low level configuration can be started The contact is used both for manual address programming and configuration with RogerVDM FDM Firmware download When contacts are shorted then firmware download mode is started and new firmware...

Page 5: ...se of manual address programming for operation in RACS 5 the first digit of address is skipped Manual address programming Switch power supply off Place jumper on MEM contacts Select RACS 4 operating mode on MD1 and MD2 contacts table 2 Connect CLK A terminal with DTA B terminal Switch power supply on LED_ST red indicator will pulsate Disconnect CLK A and DTA B terminals Count the number of LED_SY ...

Page 6: ...erface is connected to RS485 bus A and B terminals of MC16 access controller Tab 3 Selection of MCI 1 operating mode The reader when operated in RACS 4 and RACS 5 system returns 32bit proximity card number instead of typical 40bit number Therefore some additional configuration steps are necessary to adapt both RACS systems to operation with LRT 1 In RACS 4 system it is necessary to select the opti...

Page 7: ... to computer USB port Start RogerVDM software Select MCI 1 interface and RS485 communication channel In the field Serial port select serial COM port with RUD 1 interface The program will establish connection with the device and it will display its current settings Configure MCI 1 as required Select Send to Device to upload new settings Optionally select Send to File to backup your settings in file...

Page 8: ...delay after which device will signal lost communication with controller When set to 0 then signalling is disabled Parameter concerns RACS 5 system only RS485 encryption Parameter enables encryption at RS485 bus RS485 encryption key Parameter defines key for encryption of communication at RS485 bus Range 4 16 ASCII characters AF Type Parameter defines authentication factor type returned by reader P...

Page 9: ...nections as in fig 6 Place jumper on FDM contacts Connect RUD 1 to computer USB port Start RogerVDM program In the top menu select Tools and then Update Firmware Proceed according to displayed messages After firmware upload remove jumper from FDM contacts Restart the interface by switching power supply off on or with jumper on RES contacts Fig 6 Connection of MCI 1 to RUD 1 interface firmware upda...

Page 10: ...face to access controller The address must be in range of 100 115 RACS 5 or 0 3 RACS 4 The address can be programmed manually while all low level settings can be configured with RogerVDM software LRT 1 reader must be connected to MCI 1 interface with UTP cable Unused wires of the UTP cable can be used for power supply Fig 7 Connection of LRT 1 reader to MC16 access controller ...

Page 11: ...figured manually for both RACS 4 and RACS 5 operating modes without connection of MCI 1 to computer 4 Full configuration of MCI 1 interface can be done only with RogerVDM program ad it requires connection of RUD 1 interface 5 MCI 1 interface must be installed indoors preferably in the same metal enclosure as access controller 6 MCI 1 interface can be mounted on flat surface with two screws or on D...

Page 12: ... 40mA Cable length between MCI 1 and LRT 1 max 1200m Cable length between MCI 1 and MC16 controller max 1200m Cable length between MCI 1 and PRxx1 or PRxx2 controller max 150m LRT 1 environmental conditions Class IV outdoor general conditions temperature 25 C to 60 C relative humidity 10 to 95 no condensation MCI 1 environmental conditions Class II indoor general conditions temperature 10 C ...

Page 13: ...sed of with other wastes as this may have a negative impact on the environment and health The user is obliged to deliver equipment to the designated collection points of electric and electronic waste For detailed information on recycling contact your local authorities waste disposal company or point of purchase Separate collection and recycling of this type of waste contributes to the protection o...