CPR32-SE v3.0 User Manual Rev.A.doc

 

2017-04-14 

 

 

8/15 

 

General guidelines for 18VAC power supply 

 

GND terminals of CPR and access controllers must be connected with any wire. 

 

CPR and access controllers can operate with directly connected backup batteries. 

 

CPR and access controllers cannot be started using only power supply from backup battery. 

General guidelines for 12VDC power supply 

 

Negative (GND) potentials of power supply units must be connected with any wire. 

 

It is not necessary to connect GND terminals of CPR and PR controllers. 

 

Connect  CPR/controller  and  power  supply  unit  with  separate  wire.  The  wire  section  must  be 
such as to prevent more than 0.5V voltage drop between  CPR/controller  and  unit at maximal 
load. 

 

It is recommended to install CPR/controller possibly close to power supply unit, preferably in the 
same room. 

 

Backup  batteries cannot  be connected  directly to CPR/controllers  thus  backup  supply must be 
ensured on power supply unit side. 

 

CPR/controllers can be supplied from single power supply unit if the output power is sufficient. 

3.4 Communication with CPR 

RS485  bus  and  UT  communication  interface  (e.g.  UT-2USB)  are  used  for  communication  with 
CPR32-SE v3.0 network controller. Single RS485 bus creates network (subsystem) including single 
CPR32-SE v3.0 unit and up to 32 access controllers. For the communication with distant subsystems 

it is required to use UT-4DR or UT-4 v2.0 communication interface as both enable communication 
through computer network (LAN or WAN). 

The RS485 bus consists  of two signal  lines A and  B. In the RACS  4 system any topology can be 
used  (star,  tree  or  any  combination  of  them,  except  for  loop)  in  order  to  connect  controllers  in 
network (subsystem). The matching resistors (terminators) connected at the ends of transmitting 

lines are not required. In most cases communication works with any cable type (standard telephone 
cable, shielded or unshielded twisted pair etc.) but the  recommended cable is unshielded twisted 

pair  (U/UTP  cat.5).  Shielded  cables  should  be  limited  to  installations  subject  to  strong 
electromagnetic  interferences.  The  RS485  communication  standard  used  in  the  RACS  4  system 

guarantees proper communication in a distance of up to 1200 meters as well as high resistance to 
interferences.  

3.5 Input and output lines 

Functions are assigned  to  inputs  and  outputs by means of PR Master software.  Lists of available 

functions are specified in tables 4 and 5. 

3.5.1 Inputs 

All  inputs  (IN1..IN8)  of  CPR  have  identical  electric  structure  and  can  be  configured  as  NO  or  NC 
lines  using  PR  Master  software.  The  NO  input  is  triggered  by  shorting  it  to  supply  minus  (GND) 
while the NC input must be normally shorted to supply minus (GND) and it becomes triggered when 

connection  with  GND  is  interrupted.  Every  input  is  internally  connected  (pulled  up)  to  the  power 
supply plus (+12V) through a 15kΩ resistor. 

3.5.2 Relay outputs 

CPR offers two relay outputs (REL1, REL2), each with single switching contact. Maximum load for 

REL1 equals to 30V/1.5A while maximum load for REL2 equals to 230VAC/5A and also 30VDC/5A. 
In the normal state (relay is off) the NC-COM contacts are shorted. In the triggering state (relay is 

on) the NO-COM contacts are shorted. In case of power outage both relays remain in the off state. 

3.5.3 General purpose outputs 

CPR offers four transistor outputs (IO1, IO2, CLK, DTA). All outputs are open collector type i.e. in 
normal (off) state are pulled to supply plus via 15kΩ resistor and when in trigger (on) state they 
short to supply minus. Maximum load for each output equals to 15VDC/1A. In case of overcurrent, 

outputs are automatically switched off and CPR automatically restarts. 

Summary of Contents for CPR32-SE v3.0

Page 1: ...ersion 3 0 5133 or newer Hardware version 3 0 Document version Rev A 2016 ROGER sp z o o sp k All rights reserved This document is subject to the Terms of Use in their current version published at the www roger pl website of the Roger sp z o o sp k company hereinafter referred to as ROGER ...

Page 2: ...rs 6 3 3 Power supply 6 3 4 Communication with CPR 8 3 5 Input and output lines 8 3 5 1 Inputs 8 3 5 2 Relay outputs 8 3 5 3 General purpose outputs 8 3 6 Installation guidelines 9 4 Configuration 9 4 1 Configuration by means of PR Master software 9 4 2 Memory Reset 13 4 3 Firmware update 13 4 4 Problem with erratic jumps of mouse cursor in Windows OS 14 5 Ordering information 14 6 Product history...

Page 3: ...erns PRxx1 series controllers The network controller is equipped with RS485 port which is used for direct communication with access controllers and for communication with computer PR Master software using communication interface e g UT 2USB Events from access control system are stored in internal memory buffer max 240 000 events Note The CPR32 NET v3 0 requires PR Master software in version 4 5 20...

Page 4: ...IN8 input line P2 Power supply for CPR IO1 IO1 output line COM REL1 relay common terminal IO2 IO2 output line NC REL1 relay output NC IN1 IN1 input line NO REL1 relay output NO IN2 IN2 input line CLK CLK output line GND Ground DTA DTA output line IN3 IN3 input line GND Ground IN4 IN4 input line A RS485 communication bus TML Built in feeder output 12VDC 0 2A B RS485 communication bus AUX Built in f...

Page 5: ...CPR32 SE v3 0 User Manual Rev A doc 2017 04 14 5 15 Fig 2 Typical connection diagram for CPR32 SE v3 0 network controller ...

Page 6: ...troller is designed for power supply from 230VAC 18VAC transformer with minimal power output 25VA but it can also be supplied with 12VDC The connection of power supply is shown in fig 4 and fig 5 If CPR is supplied with 18VAC then 12V backup battery can be connected in order to provide power supply in case of mains supply shortage The CPR charges backup battery with 300mA stabilized current up to ...

Page 7: ...CPR32 SE v3 0 User Manual Rev A doc 2017 04 14 7 15 Fig 4 CPR32 SE v3 0 and PR402DR PR411DR controllers supplied with 18VAC Fig 5 CPR32 SE v3 0 and PRxx1 PRxx2 series controllers supplied with 12VDC ...

Page 8: ...stors terminators connected at the ends of transmitting lines are not required In most cases communication works with any cable type standard telephone cable shielded or unshielded twisted pair etc but the recommended cable is unshielded twisted pair U UTP cat 5 Shielded cables should be limited to installations subject to strong electromagnetic interferences The RS485 communication standard used ...

Page 9: ...unication bus including connected access controllers CPR32 SE network controller and communication interface e g UT 2USB the installer can proceed with installation and configuration of PR Master software At first it is necessary to configure subsystem selecting the option Networks in the main window of PR Master software and then the button Add In the newly opened window shown in fig 6 select the...

Page 10: ... the CPR off and on Menu Settings Inputs Outputs In the window opened by means of this option it is possible to assign functions to CPR32 SE inputs and outputs Additionally in case of inputs the administrator can define their NO NC type and in case of outputs their normal inverted type All input functions can be divided into ON OFF monitored and ON monitored In case of ON OFF monitored input funct...

Page 11: ...ivated at all controllers doors within subsystem network 12 Clear all alarms in subsystem ON monitored When the input is activated then all alarms in CPR32 NET and controllers within particular subsystem network are cleared The function 12 operates as a sum of 01 and 13 functions 13 Clear alarms in all controllers ON monitored When the input is activated then all alarms in controllers within parti...

Page 12: ...of PR series controllers within the subsystem network 73 Alarm in CPR The output is activated for 3 minutes if Tamper Alarm or Power supply alarm is raised The function 67 operates as a sum of 81 and 82 functions 74 Low battery The output remains activated as long as charge level of backup battery connected to CPR32 NET unit is low 75 18VAC supply lost The output is activated after 15 minutes of 1...

Page 13: ... output is activated for 3 minutes when the event memory buffer is filled in 75 90 Low battery 3 min The output remains activated for 3 minutes if charge level of backup battery connected to CPR32 NET unit is low 91 18VAC supply lost 3 min The output is activated for 3 minutes after 15 minutes of 18VAC power supply shortage to CPR32 NET unit 92 Battery failure 3 min The output is activated for 3 m...

Page 14: ...tem is equipped with CPR32 SE network controller connected to PC through such serial interfaces as UT 2USB RUD 1 or UT 4 with virtual serial port then CPR is erroneously detected by Windows as Microsoft Serial Ball Point device In such case mouse cursor goes crazy erratically jumps around screen and PR Master software reports serial port error Note The problem which is described above is not cause...

Page 15: ...ay have a negative impact on the environment and health The user is obliged to deliver equipment to the designated collection points of electric and electronic waste For detailed information on recycling contact your local authorities waste disposal company or point of purchase Separate collection and recycling of this type of waste contributes to the protection of the natural resources and is saf...

Reviews: