External buzzer
The output is dedicated to connection of external speaker in
order to signal acoustically following alarms:
firmware memory error – infinite, modulated
signal (3 sec. of sound /3 sec. of pause)
configuration error – repeated double short
acoustic signals
event memory error – repeated three short
acoustic signals
RTC error – repeated four short acoustic signals
Tamper alarm or Power supply alarm – the signal
is modulated (1 sec. of sound/ 1 sec. of pause)
and lasts 3 minutes
[66]
Data transmitted
The output is activated whenever data is transmitted by CPR
on RS485 bus.
[67]
Alarm in CPR -
modulated
The output is activated for 3 minutes if Tamper Alarm or
Power supply alarm is raised. The function [67] operates as a
sum of [81] and [82] functions. The signal is modulated (1
sec. of signal/ 1 sec. of pause).
[71]
Alarm in subsystem
(network)
The output is activated for 3 minutes if Tamper Alarm, Power
supply alarm or any alarm in one of controllers is raised. The
function [71] operates as a sum of [81], [82] and [72]
functions.
[72]
Alarm in controllers
The output is activated for 3 minutes if any alarm is raised in
one of PR series controllers within the subsystem (network).
[73]
Alarm in CPR
The output is activated for 3 minutes if Tamper Alarm or
Power supply alarm is raised. The function [67] operates as a
sum of [81] and [82] functions.
[74]
Low battery
The output remains activated as long as charge level of
backup battery connected to CPR32-NET unit is low.
[75]
18VAC supply lost
The output is activated after 15 minutes of 18VAC power
supply shortage to CPR32-NET unit and remains activated
until the power supply is restored.
[76]
Battery failure
The output is activated in case of battery failure (no battery
or internal damage of battery). If the output is activated then
the battery must be checked by maintenance personnel. The
output remains activated until the problem is eliminated.
[77]
CPR on
The output signals that CPR32-NET is switched on by PR
Master software.
[78]
CPR off
The output signals that CPR32-NET is switched off by PR
Master software.
[79]
Internal failure
The output is activated when internal testing detects RTC
failure, firmware memory failure or data memory error.
Internal test is performed every 20 minutes. The output is
activated until the failure/error is removed.
[80]
Buffer alarm -
modulated
The output is activated when the event memory buffer is full
and remains activated until the buffer is cleared. The signal
is modulated (1 sec. of signal/ 1 sec. of pause).