EN

11

Indicators

LED

ON / FLASHING

OFF

L1

  (TX)

Mains power.

Non power or incorrect connection.

L2

 (RX)

ON: better signal

In the first 20 minutes after giving power, the LED is 

off in the absence of a received infrared signal.

After 20 minutes from power on, the LED remains off.

Flashing rapidly: strong signal.

In the first 20 minutes after switching on, the LED 

flashes or is on steady if it receives an infrared signal.
Flashing slowly: weak signal.

L3

 (RX)

Normally on. N.C. contact closed.

Obstacle detected. N.C. contact open.

Preliminary checks

•  The mounting surfaces for the photocells must be clean, perfectly level and not subject to vibration.

•  The maximum range is set in the factory to 15 m. 

•  For installations with a distance of less than 2.5 m between the transmitter 

TX

 and the receiver 

RX

remove the lenses from the transmitter and receiver, taking care not to damage the photocell.

•  The minimum permissible distance between transmitter and receiver is 80 cm.

Installation

1.  Open the photocell units and remove the electronic circuit boards.

2.  With the system disconnected from mains electricity, make the electrical connections as shown in fig. 4, 

5 and 6.  

3. 

Warning: with a 24V DC power supply, pay attention to the polarities. With a 24V AC power supply, connect 

the negative pole (“-”) of the photocells to the common COM of the control unit.

4.  Configure one pair of photocells as the MASTER pair (see fig. 4) using the jumpers ID1 and ID2.

5.  Configure, using the jumpers ID1 and ID2, any other pairs of photocells as SLAVE1, SLAVE2, SLAVE3, see fig. 

5 and 6.

 

Warning:  there  cannot  be  SLAVE  configurations  equal  to  one  another,  and  only  one  pair  must  be 

configured as MASTER.      

 

NOTE: Change the jumper position in absence of voltage.

6.  Connect the photocells with the synchronisation wire (

SYNC

). 

If the photocells are not connected, they 

will NOT work.

7.  Up to 4 pairs of synchronised photocells may be installed (1 3 SLAVEs).

8.  Perform the alignment procedure before closing the photocells permanently, see chapter 8.

Alignment procedure

The alignment procedure must be performed on one pair of photocells at a time.

1.  Turn on the power supply.

2.  Position the 

RX

 receiver and the 

TX

 transmitter by aligning the two devices optically. 

3. 

 

For M90/F4ESO only. 

Adjust the orientation of the light beam as shown in fig. 7.

 

 

 

To adjust horizontal orientation 

(±105°), loosen the screws 

1

 and move the bracket 

3

 into the correct 

position. Tighten the screws 

1

.

 

To adjust vertical orientation 

(±5°), turn the screw 

2

 clockwise or anticlockwise to set the correct position.

4.  For the first 20 minutes after switching on, the LED 

L2

 flashes faster the more signals are received, until it 

remains on steady with a maximum signal. LED 

L2

 switches off after 20 minutes. To check the alignment 

again, turn the power off and on again.” 

5. 

LED 

L3

 must remain on to indicate that the N.C. contact is closed. If it is off, it means that the contact is open 

and that the photocell detects an obstacle.

6.  Fix the photocell permanently.

7.  Permanently close the photocell casing and securing it with the supplied screws.

Summary of Contents for M90/F4ES

Page 1: ... Instruction and warnings for the installer pag 10 DE Anleitungen und Hinweise für den Installateur S 13 FR Instructions et mises en garde pour l installateur page 16 ES Instrucciones y advertencias para el instalador pág 19 PT Instruções e advertências para o instalador pág 22 IS178 Rev 01 20 03 2018 ...

Page 2: ...2 1 2 23 5 35 109 8 40 45 129 7 M90 F4ES M90 F4ES M90 F4ESO M90 F4ESO 28 1 1 15 5 71 2 1 16 10 3 22 16 85 75 2 2 23 40 5 11 10 37 85 129 7 ...

Page 3: ...3 3 M90 F4ES M90 F4ESO TX RX RX TX 1 1 2 2 3 3 TX RX ...

Page 4: ...ASTER 24V COM SYNC 24V COM SYNC FT FT1 NERO BLACK ROSSO RED ID1 ID2 4 5 24V COM FT2 FT1 SLAVE1 L1 ID1 1 2 3 1 2 3 4 5 ID2 ID1 ID2 L3 L2 TX RX L1 ID1 1 2 3 1 2 3 4 5 ID2 ID1 ID2 L3 L2 TX RX MASTER 24V COM SYNC 24V COM 24V COM FT2 SYNC SYNC 24V COM SYNC FT1 ID1 ID2 ID1 ID2 ...

Page 5: ... 2 3 1 2 3 4 5 ID2 ID1 ID2 L3 L2 TX RX MASTER SLAVE1 L1 ID1 1 2 3 1 2 3 4 5 ID2 ID1 ID2 L3 L2 TX RX L1 ID1 1 2 3 1 2 3 4 5 ID2 ID1 ID2 L3 L2 TX RX ID1 ID2 ID1 ID2 24V COM SYNC 24V COM SYNC SYNC 24V COM FT1 24V COM SYNC 24V COM SYNC 24V COM SYNC COM 24V COM FT2 SYNC SYNC ID1 ID2 ID1 ID2 24V ...

Page 6: ...6 7 2 1 1 3 ...

Page 7: ...OLOGIA ADOTTATA Infrarosso attivo con trasmissione modulata controllata da microcontrollore TENSIONE DI ALIMENTAZIONE 24 Vac dc ASSORBIMENTO DI CORRENTE TX 18 mA RX 27 mA LUNGHEZZA D ONDA EMISSIONE INFRAROSSO 860 nm ANGOLO DI EMISSIONE DEL DIODO 10 DISTANZA MASSIMA DI FUNZIONAMENTO 15 m DISTANZA MINIMA DI FUNZIONAMENTO 0 8 m CONTATTO DI USCITA Doppio relay con contatti in serie doppia sicurezza us...

Page 8: ... jumper ID1 e ID2 le eventuali altre coppie di fotocellule come SLAVE1 SLAVE2 SLAVE3 fig 5 e 6 Attenzione non ci possono essere configurazioni SLAVE uguali tra loro e solo una coppia deve essere configurata come MASTER NOTA modificare la posizione dei jumper in assenza di tensione 5 Collegare con filo di sincronizzazione SYNC le fotocellule Se non collegato le fotocellule NON funzionano 6 E possib...

Page 9: ...ure idonee alla corretta rimozione del prodotto Questo prodotto è costituito da vari tipi di materiali alcuni possono essere riciclati altri devono essere smaltiti attraverso sistemi di riciclaggio o smaltimento previsti dai regolamenti locali per questa categoria di prodotto E vietato gettare questo prodotto nei rifiuti domestici Eseguire la raccolta separata per lo smaltimento secondo i metodi p...

Page 10: ...red with modulated transmission controlled by a microcontroller MAINS POWER VOLTAGE 24 Vac dc CURRENT ABSORPTION TX 18 mA RX 27 mA INFRARED BEAM WAVELENGTH 860 nm LED EMISSION ANGLE 10 MAXIMUM OPERATING RANGE 15 m MINIMUM OPERATING RANGE 0 8 m OUTPUT CONTACT Double relays with contacts in series double safety normally closed contact 30 V max 0 5 A max with resistive load SYNCHRONISM digital with w...

Page 11: ...2 5 Configure using the jumpers ID1 and ID2 any other pairs of photocells as SLAVE1 SLAVE2 SLAVE3 see fig 5 and 6 Warning there cannot be SLAVE configurations equal to one another and only one pair must be configured as MASTER NOTE Change the jumper position in absence of voltage 6 Connect the photocells with the synchronisation wire SYNC If the photocells are not connected they will NOT work 7 Up...

Page 12: ...the product correctly and safely This product consists of numerous different materials Some of these materials may be recycled while others must be disposed of correctly at the specific recycling or waste management facilities indicated by local legislation applicable for this category of product Do not dispose of this product as domestic refuse Observe local legislation for differentiated refuse ...

Page 13: ...EINGESETZTE TECHNOLOGIE Aktives Infrarot mit modulierter Übertragung von Microcontroller kontrolliert VERSORGUNGSSPANNUNG 24 Vac dc STROMAUFNAHME TX 18 mA RX 27 mA WELLENLÄNGE DER INFRAROTSTRAHLUNG 860 nm EMISSIONSWINKEL DER DIODE 10 MAXIMALE REICHWEITE 15 m MINDESTREICHWEITE 0 8 m AUSGANGSKONTAKT Doppelrelais mit in Serie geschalteten Kontakten doppelte Sicherheit Öffnerkontakt max 30 V max 0 5 A...

Page 14: ...rankenalsSLAVE1 SLAVE2 SLAVE3überdieDrahtbrückenID1undID2konfigurieren Abb 5 und 6 Achtung Es können keine SLAVE Konfigurationen untereinander gleich sein und nur ein Paar darf als MASTER konfiguriert sein NOTE Stellen Sie die Position der Jumper ohne Spannung ein 5 Die Lichtschranken mit Synchronisationsdraht SYNC anschließen Besteht keine Verbindung funktionieren die Fotozellen nicht 6 Es können...

Page 15: ...echnisch qualifiziertem Personal mit den geeigneten Verfahren ausgebaut werden Dieses Produkt besteht aus verschiedenen Stoffen von denen einige recycelt werden können Informieren Sie sich über die Recycling oder Entsorgungssysteme die für diese Produktkategorie von den örtlichgültigenVorschriftenvorgesehensind DiesesProduktdarfnichtzusammenmitdemHaushaltsmüll entsorgt werden Für die Entsorgung ge...

Page 16: ...hniques TECHNOLOGIE ADOPTÉE Infrarouge actif avec transmission modulée contrôlée par micro contrôleur TENSION D ALIMENTATION 24 Vac dc ABSORPTION DE COURANT TX 18 mA RX 27 mA LONGUEUR D ONDE EMISSION INFRAROUGE 860 nm ANGLE D EMISSION DE LA DIODE 10 PORTEE MAXIMALE DE FONCTIONNEMENT 15 m PORTEE MINIMALE DE FONCTIONNEMENT 0 8 m CONTACT DE SORTIE Double relais avec contacts en série double sécurité ...

Page 17: ...tres paires de photocellules comme SLAVE1 SLAVE2 SLAVE3 à l aide des cavaliers ID1 et ID2 voir fig 5 et 6 Attention il ne peut y avoir de configurations SLAVE identiques entre elles et une seule paire doit être configurée comme MASTER REMARQUE changer la position du jumper en l absence de tension 5 Brancheraveclefildesynchronisation SYNC lesphotocellules Fautedebranchement lesphotocellules NE fonc...

Page 18: ...alifiés selon les procédures adaptées Ce produit est constitué de différents types de matériaux certains peuvent être recyclés d autres doivent être triés à travers des systèmes de recyclage ou d élimination prévus par les législations locales pour cette catégorie de produit Il est interdit de jeter ce produit dans les déchets ménagers Effectuer le tri pour l élimination suivant les méthodes prévu...

Page 19: ... TECNOLOGÍA Infrarrojo activo con transmisión modulada controlada por un microcontrolador TENSIÓN DE ALIMENTACIÓN 24 Vac dc CONSUMO DE CORRIENTE TX 18 mA RX 27 mA LONGITUD DE ONDA EMISIÓN INFRARROJO 860 nm ÁNGULO DE EMISIÓN DEL DIODO 10 ALCANCE MÁXIMO DE FUNCIONAMIENTO 15 m ALCANCE MÍNIMO DE FUNCIONAMIENTO 0 8 m CONTACTO DE SALIDA Doble relé con contactos en serie doble seguridad salida normalment...

Page 20: ... sí y sólo una pareja ha de configurarse como MAESTRO NOTA cambiar la posición del puente sin tensión 5 Conecte con cable de sincronización SYNC las fotocélulas Si no está conectado las fotocélulas NO funcionan 6 Se pueden conectar hasta 4 parejas de fotocélulas sincronizadas 1 MAESTRO 3 ESCLAVOS 7 Realizar el procedimiento de alineación antes de cerrar definitivamente las fotocélulas véase el cap...

Page 21: ... correctamente el producto Este producto consta de varios tipos de materiales algunos pueden reciclarse y otros han de eliminarse a través de los sistemas de reciclaje o eliminación contemplados por los reglamentos locales para esta categoría de producto Queda prohibido echar este producto en los residuos domésticos Efectúe la recogida separada para eliminarlo según los métodos contemplados por lo...

Page 22: ...A ADOTADA Infravermelho ativo com transmissão modulada controlada por microcontrolador TENSÃO DE ALIMENTAÇÃO 24 Vac dc ABSORÇÃO DE CORRENTE TX 18 mA RX 27 mA COMPRIMENTO DE ONDA DE EMISSÃO DE INFRAVERMELHO 860 nm ÂNGULO DE EMISSÃO DO DIODO 10 ALCANCE MÁXIMO DE FUNCIONAMENTO 15 m ALCANCE MÍNIMO DE FUNCIONAMENTO 0 8 m CONTATO DE SAÍDA Relé duplo com contatos em série segurança dupla saída normalment...

Page 23: ...quer outros pares de fotocélulas como SLAVE1 SLAVE2 SLAVE3 com os jumper ID1 e ID2 figs 5 e 6 Atenção não pode haver configurações SLAVE iguais entre si e apenas um par deve ser configurado como MASTER NOTA alterar a posição do jumper na ausência de alimentação 5 Ligue com fio de sincronização SYNC as fotocélulas Se não ligado as fotocélulas NÃO funcionam 6 É possível ligar até 4 pares de fotocélu...

Page 24: ...r desinstalado sempre por pessoal técnico qualificado utilizando os procedimentos adequados para a correta remoção do produto Este produto é constituído de diversos tipos de materiais alguns podem ser reciclados e outros devem ser descartados por meio de sistemas de reciclagem ou descarte previstos pelos regulamentos locais para esta categoria de produto É proibido jogar este produto nos rejeitos ...

Reviews: