How to Interlock Two VF Series Controls together   

 

 

 

 

 

 

 

               

4/8/20  Page 8

 

1. Remove the run jumper from TB2 terminals 8 & 9 of the subordinate control. 
2. Add a wire from term. TB2-1 of the master control to terminal 7 of the subordinate control.  
3. Add a wire from TB2-2 of the master control to terminal 8 of the subordinate control. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 

 
 
 
 
 
 
 
 
 
 

How to Interlock an FC-40 Plus Series to a VF Series Control 

1. Add a wire from term. TB2-1 of the VF master control to TB2-11 of the 
subordinate control. 
2. Add a wire from TB2-2 of the VF master control to TB2-12 of the 
subordinate control. 
3. Move the run jumper on the subordinate control from TB2-6 & TB2-7 to 
TB2-5 & TB2-6. 

How to Interlock an FC-200 Series to a VF Series Control 

1. Remove the RUN jumper from TB2- 8 & 9 of the subordinate control. 
2. Add a wire from term. TB2-1 of the VF master control to TB2-7 of the 
subordinate control. 
3. Add a wire from TB2-2 of the VF master control to TB2-8 of the 
subordinate control. 
.

Summary of Contents for 121-200-0759

Page 1: ...ormation for each unit The Autotune Series of Variable Frequency Feeder Cubes generates an output frequency for feeding that is independent from the power line frequency An optional vibration sensor P...

Page 2: ...VOLTAGE INPUT SWITCHING 8 VF Control TB2 5 30 VDC INPUT VOLTAGE OFF ON CONTROL B LOW CURRENT SWITCH Subordinate VF Control TB2 INPUT FEEDER BOWL HOPPER INTERLOCK 2 1 Master VF Control TB2 OUTPUT VF Co...

Page 3: ...ngs 2 Enter Restores User Settings 2 Restore Settings 3 Enter Restores User Settings 3 Save Settings 1 Enter Saves User Settings 1 Save Settings 2 Enter Saves User Settings 2 Save Settings 3 Enter Sav...

Page 4: ...C installations to bypass the phase 2 fuse L2 To bypass remove the wire connecting TB1 L2 to the L2 fuse holder Remove the terminal end of the wire connecting the L2 fuse to the power switch and conne...

Page 5: ...r setting is displayed in the following manner A 50 0 8 Limiting the Maximum Output of Control The Max Amplitude setting can be adjusted to keep a vibratory feeder from hammering or vibrating excessiv...

Page 6: ...djust the frequency down by 2 or 3Hz so that the feeder becomes slightly over tuned B Auto Scan scans to locate the bowl s resonate frequency Once auto tracking has found the resonate frequency it can...

Page 7: ...nown setting Once a feed system has been set up properly the setting should be manually saved into the Save Settings1 memory If an operator disturbs the settings the Restore Settings1 feature can rest...

Page 8: ...ies Control 1 Add a wire from term TB2 1 of the VF master control to TB2 11 of the subordinate control 2 Add a wire from TB2 2 of the VF master control to TB2 12 of the subordinate control 3 Move the...

Page 9: ...peration Note It takes 72 hours for the adhesive to fully cure at 70 F Alternatively 8 or M4 screws can be used to mount the sensor to the feeder The mounting holes are 1 375 3 49cm apart D ROUTE THE...

Page 10: ...f a nearby noise source Solutions for Electrical Noise 1 Use shielded wires for all I O Input Output signals The I O signals may include 4 20mA input Run input Sensor input 0 5VDC input Interlock inpu...

Reviews: