How to Interlock Two VF Series Controls together   

 

 

 

 

 

 

 

               

4/8/20  Page 8

 

1. Remove the run jumper from TB2 terminals 8 & 9 of the subordinate control. 
2. Add a wire from term. TB2-1 of the master control to terminal 7 of the subordinate control.  
3. Add a wire from TB2-2 of the master control to terminal 8 of the subordinate control. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 

 
 
 
 
 
 
 
 
 
 

How to Interlock an FC-40 Plus Series to a VF Series Control 

1. Add a wire from term. TB2-1 of the VF master control to TB2-11 of the 
subordinate control. 
2. Add a wire from TB2-2 of the VF master control to TB2-12 of the 
subordinate control. 
3. Move the run jumper on the subordinate control from TB2-6 & TB2-7 to 
TB2-5 & TB2-6. 

How to Interlock an FC-200 Series to a VF Series Control 

1. Remove the RUN jumper from TB2- 8 & 9 of the subordinate control. 
2. Add a wire from term. TB2-1 of the VF master control to TB2-7 of the 
subordinate control. 
3. Add a wire from TB2-2 of the VF master control to TB2-8 of the 
subordinate control. 
.

Summary of Contents for 121-000-075

Page 1: ...ut Frequency 5 180Hz Rated Output Current 18 Amps at 120V or 12 Amps at 240V Model Information The Autotune Series of Variable Frequency Feeder Cubes generates an output frequency for feeding that is...

Page 2: ...RODIX INC Toll Free 800 562 1868 FAX 815 316 4701 Email custserve rodix com rodix com VF 18 E cover docx 8 21 20 Page 2 RODIX INC FEEDER CUBE VF Series WIRING DIAGRAM Figure 1...

Page 3: ...ngs 2 Enter Restores User Settings 2 Restore Settings 3 Enter Restores User Settings 3 Save Settings 1 Enter Saves User Settings 1 Save Settings 2 Enter Saves User Settings 2 Save Settings 3 Enter Sav...

Page 4: ...single phase 120 or 240 VAC installations to bypass the phase 2 fuse L2 To bypass remove the wire connecting TB1 L2 to the L2 fuse holder Remove the terminal end of the wire connecting the L2 fuse to...

Page 5: ...r setting is displayed in the following manner A 50 0 8 Limiting the Maximum Output of Control The Max Amplitude setting can be adjusted to keep a vibratory feeder from hammering or vibrating excessiv...

Page 6: ...arts load fluctuations adjust the frequency down by 2 or 3Hz so that the feeder becomes slightly over tuned B Auto Scan scans to locate the bowl s resonate frequency Once auto tracking has found the r...

Page 7: ...to a known setting Once a feed system has been set up properly the setting should be manually saved into the Save Settings1 memory If an operator disturbs the settings the Restore Settings1 feature ca...

Page 8: ...ies Control 1 Add a wire from term TB2 1 of the VF master control to TB2 11 of the subordinate control 2 Add a wire from TB2 2 of the VF master control to TB2 12 of the subordinate control 3 Move the...

Page 9: ...f a nearby noise source Solutions for Electrical Noise 1 Use shielded wires for all I O Input Output signals The I O signals may include 4 20mA input Run input Sensor input 0 5VDC input Interlock inpu...

Reviews: