Programming and Parameters
Inputs & Outputs File
(File J)
F
ile
J
Gr
oup
No.
Parameter Name and Description
See
Values
Relate
d
INPUT
S &
OUTP
UTS
(File
J)
A
n
al
og
In
pu
ts
320
[Anlg In Config]
Selects the mode for the analog inputs.
321
[Anlg In Sqr Root]
Enables/disables the square root function for each input.
322
325
[Analog In 1 Hi]
[Analog In 2 Hi]
Sets the highest input value to the analog
input x scaling block.
Default:
Min/Max:
Units:
10.000 Volt
10.000 Volt
4.000/20.000 mA
,
0.000/20.000 mA
,
–/+10.000V,
0.000/10.000V
0.001 mA,
0.001 Volt
323
326
[Analog In 1 Lo]
[Analog In 2 Lo]
Sets the lowest input value to the analog
input x scaling block.
Default:
Min/Max:
Units:
0.000 Volt
0.000 Volt
4.000/20.000 mA,
0.000/10.000V (No. 323),
–/+10.000V (No. 326)
0.000/10.000V,
0.001 mA,
0.001 Volt
324
327
[Analog In 1 Loss]
[Analog In 2 Loss]
Selects drive action when an analog
signal loss is detected. Signal loss is
defined as an analog signal less than 1V
or 2mA. The signal loss event ends and
normal operation resumes when the input
signal level is greater than or equal to
1.5V or 3mA.
Default:
Options:
0
0
0
1
2
3
4
5
6
“Disabled”
“Disabled”
“Disabled”
“Fault”
“Hold Input”
“Set Input Lo”
“Set Input Hi”
“Goto Preset1”
“Hold OutFreq”
0
x
x
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1
=Current
0
=Voltage
x =Reserved
Bit #
Factory Default Bit Values
Analog In 1
Analog In 2
Nibble 1
Nibble 2
Nibble 3
Nibble 4
0
x
x
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1
=Enable
0
=Disable
x =Reserved
Bit #
Factory Default Bit Values
Analog In 1
Analog In 2
Nibble 1
Nibble 2
Nibble 3
Nibble 4
Standard
E C
Summary of Contents for PowerFlex 70
Page 4: ...soc 2 Notes ...
Page 134: ...A 18 Supplemental Drive Information Notes ...
Page 168: ...Index 14 ...
Page 169: ......