1. Description
Trusted 20 Channel Isolated AI/DI FTA Loop Powered
4
Issue 5
Rockwell Automation Publication ICSTT-RM294E-EN-P
The connector linking the 20 channels on the input module to the FTA is terminated at
CON1 which is a 96‐way socket. A row of screw terminal connectors (TB1) are used to
connect the field wiring.
Unused inputs should be terminated by wiring a 24 V supply via a resistor (2K or 2K2) to the
A terminal and wiring the B terminal to the associated zero volts.