Single Safety Gate Protection Using SmartGuard 600 Packaged Safety Controller
5
Wiring
Configure the
SmartGuard 600 Controller
Use RSNetWorx for DeviceNet software, version 8.0 or later, to
configure the SmartGuard 600 controller. Follow these steps to
configure the inputs and outputs used in this application example.
1.
In RSNetWorx for DeviceNet software, browse the network.
2.
Right-click the SmartGuard controller and choose Properties.
3.
Select the Local Input/Test Output tab.
V1
G1
T0
T1
I1
I0
I3
I5
I2
I4
I6
I7
T2
T3
E1
S1
O1
O0
V2
G2
O3
O5
O2
O4
O6
O7
E2
KM1
KM2
KM1
KM2
I9
I8
I11
I13
I10
I12
I14
I15
KM1-NC
KM2-NC
S3
M
E1 and E2: 24V dc Power Supplies
S1: Limit Switch 1
S2: Limit Switch 2
S3: Reset Switch
KM1 and KM2: Contactors
Connect a 24V dc power supply to terminals V0 and G0, the power supply terminals for internal
circuits.