Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017
53
PowerFlex 6000 Drive (P_PF6000)
Engineering Tab Page 3
The following table shows the functions on the Engineering tab page 3.
Table 17 - Engineering Tab Page 3 Description
Function
Action
Security
Configuration Parameters
Stop Drive:
On I/O Fault
Check to stop the drive if an I/O Fault
is detected.
Clear the box to show only the I/O Fault
Status/Alarm and not stop the drive if
an I/O Fault is detected.
Engineering
Configuration
(Code E)
Cfg_ShedOnIOFault
Stop Drive:
On Fail to Start
This occurs when the bit is:
•
‘On’ indicates a motor fail to start is
detected, the motor is stopped. A
reset is required before another
start can be attempted.
•
‘Off ’indicates a motor fail to start is
detected, the instruction sets only
the Sts_FailToStart status (and the
Alm_FailToStart alarm, if so
configured). The outputs are not
changed, so the instruction
continues to start the motor.
Cfg_ShedOnFailToStart
Stop Drive:
On Interlock Trip
The motor always stops on an interlock
trip. This item cannot be unchecked. It
is displayed as a reminder that the
Interlock Trip function always trips
the motor.
None