Installation Instructions

MicroLogix™ 1200 Programmable Controllers

(Cat. No. 1762-L24AWA, 1762-L24BWA, 1762-L24BXB, 1762-L40AWA, 
1762-L40BWA, 1762-L40BXB, 1762-L24AWAR, 1762-L24BWAR, 
1762-L24BXBR, 1762-L40AWAR, 1762-L40BWAR, 1762-L40BXBR)

http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1
762-in006_-mu-p.pdf

Cette publication est disponible en français sous forme électronique (fichier PDF). Pour la 
télécharger, rendez-vous sur la page Internet indiquée ci-dessus.

Questa pubblicazione è disponibile in Italiano in formato PDF. Per scaricarla collegarsi al sito 
Web indicato sopra.

Diese Publikation ist als PDF auf Deutsch verfügbar. Gehen Sie auf die oben genannte 
Web-Adresse, um nach der Publikation zu suchen und sie herunterzuladen.

Esta publicación está disponible en español como PDF. Diríjase a la dirección web indicada 
arriba para buscar y descarga esta publicación.

Esta publicação está disponível em portugués como PDF. Vá ao endereço web que aparece 
acima para encontrar e fazer download da publicação.

FR

IT

DE

ES

PT

Summary of Contents for micrologix 1200

Page 1: ...harger rendez vous sur la page Internet indiquée ci dessus Questa pubblicazione è disponibile in Italiano in formato PDF Per scaricarla collegarsi al sito Web indicato sopra Diese Publikation ist als PDF auf Deutsch verfügbar Gehen Sie auf die oben genannte Web Adresse um nach der Publikation zu suchen und sie herunterzuladen Esta publicación está disponible en español como PDF Diríjase a la direc...

Page 2: ......

Page 3: ...A 1762 L40BXB 1762 L24AWAR 1762 L24BWAR 1762 L24BXBR 1762 L40AWAR 1762 L40BWAR 1762 L40BXBR Inside Important User Information 4 For More Information 5 Overview 6 Controller Description 7 Hazardous Location Considerations 8 Mounting the Controller 10 Connecting 1762 I O Expansion Modules 14 Wiring the Controller 15 Specifications 21 ...

Page 4: ...ciated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of R...

Page 5: ...e your MicroLogix 1200 programmable controller and expansion I O system MicroLogix 1200 Programmable Controllers User Manual 1762 UM001 A reference manual that contains data and function files instruction set and troubleshooting information for MicroLogix 1200 and MicroLogix 1500 MicroLogix 1200 and MicroLogix 1500 Instruction Set Reference Manual 1762 RM001 Information on installing and using 176...

Page 6: ... condensation shall be expected 2 Over Voltage Category II is the load level section of the electrical distribution system At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product s insulation 3 Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission IEC designations ATTENTION Do not remove the protective ...

Page 7: ...nal Doors and Label 2 Bus Connector Interface to Expansion I O 8 Trim Pots 3 Input LEDs 9 Default Communications Push Button 4 Output LEDs 10 Memory Module Port Cover 1 or Memory Module and or Real Time Clock 2 1 Shipped with controller 2 Optional equipment 5 Communication Port Channel 0 11 DIN Rail Latches 6 Status LEDs 12 Programmer HMI Port Equipped with 1762 LxxxxxR controllers only 12 1 2 3 4...

Page 8: ...24BXBR 24V dc 10 24V dc 4 fast 24V dc 5 relay 4 24V dc FET 1 high speed 24V dc FET 1762 L40AWA L40AWAR 120 240V ac 24 120V ac 16 relay 1762 L40BWA L40BWAR 120 240V ac 20 24V dc 4 fast 24V dc 16 relay 1762 L40BXB L40BXBR 24V dc 20 24V dc 4 fast 24V dc 8 relay 7 24V dc FET 1 high speed 24V dc FET WARNING EXPLOSION HAZARD x Substitution of components may impair suitability for Class I Division 2 x Do...

Page 9: ... AM00 Series C or later 1761 CBL AP00 Series C or later 2707 NC8 Series B or later 2707 NC10 Series B or later 2707 NC11 Series B or later DANGER D EXPLOSION x La substitution de composants peut rendre cet équipement impropre à une utilisation en environnement de Classe I Division 2 x Ne pas remplacer de composants ou déconnecter l équipement sans s être assuré que l alimentation est coupée x Ne p...

Page 10: ...uidelines publication 1770 4 1 Classification des environnements Câbles de communication Environnement dangereux de Classe I Division 2 1761 CBL PM02 série C ou ultérieure 1761 CBL HM02 série C ou ultérieure 1761 CBL AM00 série C ou ultérieure 1761 CBL AP00 série C ou ultérieure 707 NC8 série B ou ultérieure 2707 NC10 série B ou ultérieure 2707 NC11 série B ou ultérieure ATTENTION Vertical mountin...

Page 11: ...24AWAR L24BWA L24BWAR L24BXB L24BXBR L40AWA L40AWAR L40BWA L40BWAR L40BXB L40BXBR A 90 mm 3 5 in 90 mm 3 5 in B 110 mm 4 33 in 160 mm 6 30 in C 87 mm 3 43 in 87 mm 3 43 in C B A C B A 1762 L24AWA 1762 L24BWA 1762 L24BXB 1762 L24AWAR 1762 L24BWAR 1762 L24BXBR 1762 L40AWA 1762 L40BWA 1762 L40BXB 1762 L40AWAR 1762 L40BWAR 1762 L40BXBR ...

Page 12: ...troller Allow 50 mm 2 in of space on all but the right side for adequate ventilation as shown below DIN Rail Mounting The maximum extension of the latch is 14 mm 0 55 in in the open position A flat blade screwdriver is required for removal of the controller The controller can be mounted to EN50022 35x7 5 or EN50022 35x15 DIN rails DIN rail mounting dimensions are shown below Top Side Bottom A B C ...

Page 13: ...l 4 While pressing the controller down against the top of the rail snap the bottom of the controller into position 5 Leave the protective debris strip attached until you are finished wiring the controller and any other devices To remove your controller from the DIN rail 1 Place a flat blade screwdriver in the DIN rail latch at the bottom of the controller 2 Holding the controller pry downward on t...

Page 14: ...g on page 12 3 Drill holes through the template 4 Remove the mounting template 5 Mount the controller 6 Leave the protective debris strip in place until you are finished wiring the controller and any other devices Connecting 1762 I O Expansion Modules Connect 1762 I O after mounting the controller Remove the expansion port cover to install expansion I O modules Plug the ribbon cable connector into...

Page 15: ...able Controllers User Manual publication 1762 UM001 TIP The shading in the following terminal block illustrations indicates which terminals are tied to which commons VAC L1 VAC NEUT VAC DC 0 VAC DC 1 VAC DC 2 OUT 3 VAC DC 4 OUT 4 OUT 7 OUT 9 OUT 0 OUT 1 OUT 2 VAC DC 3 OUT 5 OUT 6 OUT 8 IN 0 IN 2 IN 5 IN 7 IN 9 COM 1 IN 11 IN 13 NC COM 0 IN 1 IN 3 IN 4 IN 6 IN 8 IN 10 IN 12 NC 1762 L24AWA 1762 L24A...

Page 16: ...0 VAC DC 1 VAC DC 2 OUT 3 OUT 4 OUT 6 OUT 9 OUT 14 OUT 12 1762 L40AWA 1762 L40AWAR OUT 11 VAC DC 4 VAC NEUT VAC DC 0 VAC DC 1 VAC DC 2 OUT 3 OUT 4 6 OUT OUT 9 OUT 14 OUT 12 OUT 15 VAC L1 OUT 0 OUT 1 OUT 2 VAC DC 3 OUT 7 OUT 5 OUT 8 OUT 13 OUT 10 VAC DC 5 24 VDC COM 0 IN 1 IN 3 IN 4 IN 6 IN 9 IN 11 IN 13 IN 15 IN 17 IN 19 IN 21 COM 2 IN 23 24 COM IN 0 IN 2 IN 5 IN 7 IN 8 COM 1 IN 10 IN 12 IN 14 IN ...

Page 17: ...king sure the pressure plate secures the wire Wire Type Wire Size 2 wire maximum per terminal screw Solid Cu 90 C 194 F 14 to 22 AWG Stranded Cu 90 C 194 F 16 to 22 AWG Wiring torque 0 791 Nm 7 in lb rated ATTENTION Be careful when stripping wires Wire fragments that fall into the controller could cause damage Once wiring is complete be sure the controller is free of all metal fragments before rem...

Page 18: ...following spade lugs The terminals will accept a 6 35mm 0 25 in wide spade standard for 6 screw for up to 14 AWG or a 4 mm metric 4 fork terminal When using spade lugs use a small flat blade screwdriver to pry the finger safe cover from the terminal blocks Then loosen the terminal screw TIP If you wire the terminal block with the finger safe cover removed you may not be able to put it back on the ...

Page 19: ...t Switching inductive loads without surge suppression can significantly reduce the life of relay contacts or damage transistor outputs By using suppression you also reduce the effects of voltage transients caused by interrupting the current to that inductive device and prevent electrical noise from radiating into system wiring Refer to the MicroLogix 1200 Programmable Controller User Manual public...

Page 20: ...g guidelines refer to the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 ATTENTION All devices connected to the RS 232 channel must be referenced to controller ground or be floating not referenced to a potential other than ground Failure to follow this procedure may result in property damage or personal injury x For 1762 L24BWA 1762 L40BWA 1762 L24BWAR and 1762 L40BWAR ...

Page 21: ...ontrollers User Manual Power Supply Inrush 120V ac 25A for 8 ms 240V ac 40A for 4 ms 24V dc 15A for 20 ms 120V ac 25A for 8 ms 240V ac 40A for 4 ms 24V dc 15A for 30 ms Power Supply Usage 68 VA 70 VA 27W 80 VA 82 VA 40W Power Supply Output 5V dc 400 mA 400 mA 1 400 mA 600 mA 600 mA 2 600 mA 24V dc 350 mA 350 mA 1 350 mA 500 mA 500 mA 2 500 mA Sensor Power Output none 24V dc at 250 mA 400 μF max 1 ...

Page 22: ...tude modulation 900 MHz keyed carrier x IEC1000 4 4 2 kV 5 kHz communications cable 1 kV 5 kHz x IEC1000 4 5 communications cable 1 kV galvanic gun I O 2 kV CM common mode 1 kV DM differential mode AC Power Supply 4 kV CM common mode 2 kV DM differential mode DC Power Supply 500V CM common mode 500V DM differential mode x IEC1000 4 6 10V communications cable 3V Terminal Screw Torque 0 791 Nm 7 in ...

Page 23: ...F 10 to 24V dc 10 at 55 C 131 F 25 at 30 C 86 F Off State Voltage Range 0 to 20V ac 0 to 5V dc Operating Frequency 47 Hz to 63 Hz 0 Hz to 20 kHz 0 Hz to 1 kHz scan time dependent On State Current x minimum x nominal x maximum x 5 0 mA at 79V ac x 12 mA at 120V ac x 16 0 mA at 132V ac x 2 5 mA at 14V dc x 7 3 mA at 24V dc x 12 0 mA at 30V dc x 2 0 mA at 10V dc x 8 9 mA at 24V dc x 12 0 mA at 30V dc...

Page 24: ...40V max 20A or total of per point loads whichever is less Relay Outputs Turn On Time Turn Off Time 10 msec minimum 1 1 scan time dependent Load Current 10 mA minimum Maximum Volts Amperes Amperes Continuous Volt Amperes Make Break Make Break 240V ac 7 5A 0 75A 2 5A 2 2 1 5A above 40 C 1800 VA 180 VA 120V ac 15A 1 5A 2 5A 2 1800 VA 180 VA 125V dc 0 22A 1 1 For dc voltage applications the make break...

Page 25: ...utput Current temperature dependent Surge Current per Point x peak current x maximum surge duration x maximum rate of repetition at 30 C 86 F x maximum rate of repetition at 55 C 131 F x 4 0A x 10 msec x once every second x once every 2 seconds x Not Applicable x Not Applicable x Not Applicable x Not Applicable 0 25 10 C 50 F 30 C 86 F 50 C 122 F 1 0A 55 C 131 F 1 5A 30 C 86 F 70 C 158 F 0 5 0 75 ...

Page 26: ...cond or 2596V dc for 1 second 265V ac Working Voltage IEC Class 2 reinforced insulation Input Group to Backplane Isolation Verified by one of the following dielectric tests 1517V ac for 1 second or 2145V dc for 1 second 132V ac Working Voltage IEC Class 2 reinforced insulation Input Group to Input Group Isolation Verified by one of the following dielectric tests 1517V ac for 1 second or 2145V dc f...

Page 27: ...econd or 2596V dc for 1 second 265V ac Working Voltage basic insulation 150V Working Voltage IEC Class 2 reinforced insulation Description 1762 L24BXB 1762 L40BXB 1762 L24BXBR 1762 L40BXBR Input Group to Backplane Isolation and Input Group to Input Group Isolation Verified by one of the following dielectric tests 1200V ac for 1 second or 1697V dc for 1 second 75V dc Working Voltage IEC Class 2 rei...

Page 28: ...28 MicroLogix 1200 Programmable Controllers Publication 1762 IN006C EN P September 2009 Notes ...

Page 29: ... in 160 0 mm 6 299 in 145 8 mm 5 739 in 95 86 mm 3 774 in 25 81 mm 1 016 in 0 164 Expansion I O d extension d E S E A Erweiterungsmodule l espansione dei moduli I O de expansión de E S de expa nsão de E S DIN rail center line Ligne médiane du rail DIN Mittellinie der DIN Schiene Línea central del riel DIN Linea centrale della guida DIN linha de centro do trilho DIN E S d extension ...

Page 30: ...0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 10 11 12 13 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 10 11 12 13 INPUTS INPUTS OUTPUTS OUTPUTS L24BWA L24BWAR L24AWA L24AWAR ...

Page 31: ...OUT 4 OUT 7 OUT 9 OUT 0 OUT 1 OUT 2 VAC OUT 5 OUT 6 OUT 8 24 VDC 24 COM IN 0 IN 2 IN 5 IN 7 IN 9 COM 1 IN 11 IN 13 COM 0 IN 1 IN 3 IN 4 IN 6 IN 8 IN 10 IN 12 VAC L1 VAC NEUT VAC DC 0 OUT 0 VAC DC 1 OUT 1 VAC DC 2 OUT 2 VAC DC 3 OUT 3 VAC DC 4 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 OUT 9 1762 L24AWA 1762 L24AWA 1762 L24BWA 1762 L24BWA L24AWA L24AWAR L24BWA L24BWAR ...

Page 32: ...13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 INPUTS INPUTS OUTPUTS OUTPUTS L40BWA L40BWAR L40AWA L40AWAR ...

Page 33: ...NEUT VAC DC 0 VAC DC 1 VAC DC 2 OUT 3 OUT 4 OUT 6 OUT 9 OUT 14 OUT 12 1762 L40AWA 24 VDC COM 0 IN 1 IN 3 IN 4 IN 6 IN 9 IN 11 IN 13 IN 15 IN 17 IN 19 IN 21 COM 2 IN 23 24 COM IN 0 IN 2 IN 5 IN 7 IN 8 COM 1 IN 10 IN 12 IN 14 IN 16 IN 18 IN 20 IN 22 1762 L40BWA OUT 11 VAC DC 4 VAC NEUT VAC DC 0 VAC DC 1 VAC DC 2 OUT 3 OUT 4 6 OUT OUT 9 OUT 14 OUT 12 OUT 15 VAC L1 OUT 0 OUT 1 OUT 2 VAC DC 3 OUT 7 OUT...

Page 34: ... 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 INPUTS OUTPUTS L40BXB L40BXBR 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 10 11 12 13 INPUTS OUTPUTS L24BXB L24BXBR ...

Page 35: ... 1 VDC 2 OUT 3 OUT 5 7 OUT VAC DC 3 OUT 14 OUT 12 OUT 15 24 VDC OUT 0 OUT 1 OUT 2 OUT 4 OUT 8 OUT 6 COM 2 OUT 13 OUT 10 VAC DC 4 1762 L40BXB NC IN 0 IN 2 IN 5 IN 7 IN 9 COM 1 IN 11 IN 13 NC COM 0 IN 1 IN 3 IN 4 IN 6 IN 8 IN 10 IN 12 NC 24 VDC VDC NEUT 4 VAC DC 0 VAC DC 1 VDC 2 OUT 3 COM 2 OUT 5 OUT 7 OUT 9 OUT 0 OUT 1 OUT 2 OUT 4 OUT 6 VAC DC 3 OUT 8 1762 L24BXB 1762 L24BXB L24BXB L24BXBR L40BXB L...

Page 36: ......

Page 37: ...r module up and running New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures Allen Bradley Rockwell Automation MicroLogix and TechConnect are trademarks of Rockwell Automation Inc Trademarks not b...