Rockwell Automation Publication PFLEX-IN029B-EN-P - August 2014
23
PowerFlex 700H and 700S Drives - Frame 9 Procedures
Chapter 1
Remove Power from the Drive
1.
Turn off and lock out input power.
2.
Wait five minutes.
3.
Check the DC bus voltage at the Power Terminal Block by measuring
between the +DC and -DC terminals, between the +DC terminal and the
chassis, and between the -DC terminal and the chassis. The voltage must
be zero for all three measurements.
ATTENTION:
To avoid an electric shock hazard, verify that the voltage on the bus
capacitors has discharged completely before servicing. Check the DC bus voltage
at the Power Terminal Block by measuring between the +DC and -DC terminals,
between the +DC terminal and the chassis, and between the -DC terminal and
the chassis. The voltage must be zero for all three measurements.
Remove power before making or breaking cable connections. When you remove or
insert a cable connector with power applied, an electrical arc may occur. An
electrical arc can cause personal injury or property damage by:
•
sending an erroneous signal to your system’s field devices, causing unintended
machine motion
•
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module and its
mating connector. Worn contacts may create electrical resistance.
L1
L2
L3
O
I
Summary of Contents for Allen-BradleyPowerFlex 700AFE
Page 1: ...PowerFlex 700H 700S and 700AFE Drive Fan Systems Frames 9 14 Drives Installation Instructions ...
Page 4: ...4 Rockwell Automation PublicationPFLEX IN029B EN P August 2014 Summary of Changes Notes ...
Page 10: ...10 Rockwell Automation Publication PFLEX IN029B EN P August 2014 Table of Contents ...
Page 18: ...18 Rockwell Automation PublicationPFLEX IN029B EN P August 2014 Preface Notes ...
Page 295: ......