Publication 20P-IN069A-EN-P

PowerFlex® DC Drive
Frame D Overvoltage Clipping Board Fuse Replacement

Installation Instructions

What This Kit Includes

Fuses 14x51 mm, 10 A, 90V (3)

Static strap

Tools That You Need

Flathead screwdriver

ATTENTION:  Only qualified personnel familiar with DC drives 
and associated machinery should plan or implement the installation, 
start-up and subsequent maintenance of the system. Failure to comply 
may result in personal injury and/or equipment damage.

ATTENTION:  To avoid an electric shock hazard, ensure that all 
power to the drive has been removed before performing the following.

ATTENTION:  This drive contains ESD (Electrostatic Discharge) 
sensitive parts and assemblies. Static control precautions are required 
when installing, testing, servicing or repairing this assembly. 
Component damage may result if ESD control procedures are not 
followed. If you are not familiar with static control procedures, 
reference A-B publication 8000-4.5.2, “Guarding Against 
Electrostatic Damage” or any other applicable ESD protection 
handbook.

Summary of Contents for Allen-Bradley PowerFlex Series

Page 1: ...y may result in personal injury and or equipment damage ATTENTION To avoid an electric shock hazard ensure that all power to the drive has been removed before performing the following ATTENTION This drive contains ESD Electrostatic Discharge sensitive parts and assemblies Static control precautions are required when installing testing servicing or repairing this assembly Component damage may resul...

Page 2: ...ons When you remove or insert a cable connector with power applied an electrical arc may occur An electrical arc can cause personal injury or property damage by sending an erroneous signal to your system s field devices causing unintended machine motion causing an explosion in a hazardous environment Electrical arcing causes excessive wear to contacts on both the module and its mating connector Wo...

Page 3: ...on 20P IN069A EN P 5 Remove the three fuses at locations F11 F21 and F31 6 Install the new fuses 7 Close the control panel See steps 3 and 4 on page 2 8 Replace the DPI cable if present XCD X1UVW1 XUVW F31 F21 F11 ...

Page 4: ...treet Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation SA NV Vorstlaan Boulevard du Souverain 36 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Power Control and Information Solutions ...