1-20
Installation/Wiring
Essential Requirements for CE Compliance
Conditions 1-3 listed below
must be
satisfied for PowerFlex drives to
meet the requirements of
EN61800-3
.
1.
Grounding as described in
additional grounding recommendations.
2.
Output power, control (I/O) and signal wiring must be braided,
shielded cable with a coverage of 75% or better, metal conduit or
equivalent attenuation.
3.
Allowable cable length in
is not exceeded.
Table 1.I Allowable Cable Length
(1)
Refer to
for details on optional external filters.
(2)
Equivalent to EN55011 Class A.
(3)
Equivalent to EN55011 Class B.
Figure 1.6 Connections and Grounding
(1)
First Environment Unrestricted Distribution installations require a shielded enclosure.
Keep wire length as short as possible between the enclosure entry point and the EMI
filter.
(2)
Integral EMI filters are available on 240V, 1-Phase drives.
Filter Type
EN61800-3 First Environment
Restricted Distribution or
Second Environment
(2)
EN61800-3 First Environment
Unrestricted Distribution
(3)
Integral
10 meters (33 feet)
1 meter (3 feet)
External - S Type
(1)
10 meters (33 feet)
1 meter (3 feet)
External - L Type
(1)
100 meters (328 feet)
5 meters (16 feet)
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
EMI Fittings and Metal Conduit
IP 30/NEMA 1/UL Type 1
Option Kit
Shielded Enclosure
(1)
Building Structure Steel
Enclosure Ground Connection
(2)
EMI Filter
L1'
L2'
L3'
L1
L2
L3
Shielded Motor Cable
userman.book Page 20 Friday, June 21, 2002 2:48 PM
Summary of Contents for Allen-Bradley PowerFlex 4
Page 4: ...soc 2 userman book Page 2 Friday June 21 2002 2 48 PM ...
Page 6: ...ii userman book Page ii Friday June 21 2002 2 48 PM ...
Page 32: ...1 22 Installation Wiring Notes userman book Page 22 Friday June 21 2002 2 48 PM ...
Page 70: ...4 8 Troubleshooting Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Page 74: ...A 4 Supplemental Drive Information Notes userman book Page 4 Friday June 21 2002 2 48 PM ...
Page 82: ...B 8 Accessories and Dimensions Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Page 88: ...C 6 RS485 DSI Protocol Notes userman book Page 6 Friday June 21 2002 2 48 PM ...
Page 92: ...Index 4 Notes userman book Page 4 Friday June 21 2002 2 48 PM ...