Rockwell Automation Publication 750-IN115B-EN-P - March 2020
7
PowerFlex 755T Frames 5 and 6 EMC C2 Filter Kits
10. Connect the small diameter power wires to the auxiliary R/L1, S/L2, and T/L3 terminals on the drive.
11. Connect the large diameter power wires to the main R/L1, S/L2, and T/L3 terminals on the drive.
12. Route the AC input power cables through the customer-supplied conduit fitting in the bottom plate of the conduit box and connect the
cables to the input power terminals (R/L1, S/L2, T/L3) on the EMC C2 filter.
13. Route control and output power cables through the customer-supplied conduit fittings in the bottom plate of the conduit box and connect
them to the appropriate terminals on the drive.
14. As required, insert the appropriately sized cable clamp into the conduit box receptacle and secure the motor power cable and shield.
See the PowerFlex 750-Series Products with TotalFORCE Control Installation Instructions, publication
, for power wiring
information.
Wire Size Range
(1)
(2)
(1) Maximum/minimum wire sizes that the terminal block accepts - these values are not recommendations.
(2) Terminal block is designed to accept one wire.
Terminal Bolt Size
Maximum
Minimum
35.0 mm
2
(2 AWG)
2.5 mm
2
(14 AWG)
M6
(1/4 in.)
11
M6
Flat
4.5 N
•
m (40.0 lb
•
in)
10
M2.5
Flat
0.7 N
•
m (6.0 lb
•
in)
10. Small Diameter Wires
11. Large Diameter Wires
14. Cable Clamp for Motor Cable and Shield.
S/
L2
R/
L1
T/
L3
12
M6
10 mm
5.0 N
•
m (44.3 lb
•
in)
12
M6
10 mm
5.0 N
•
m (44.3 lb
•
in)