2–17
Troubleshooting and Error Codes
Publication 1336 IMPACT-6.8 – November, 2002
No HIM Display
Is HIM backlight lit?
Is the drive fan running?
Is the fuse blown on the
Gate Driver Board?
Voltage present at
DC+, DC–
No HIM Display
Check fuses on incoming
power.
Reconnect the HIM.
Is HIM connected properly?
Replace the HIM.
DC bus voltage present?
Replace Gate Driver Board.
Replace HIM, HIM
cable, or Control Board.
No
Yes
Yes
No
Yes
No
Yes
No
Do +5, +/–15, and 12
supply voltages on the
Control Board check
out?
Yes
Replace Control Board
or Gate Driver Board.
Replace the diode bridge
and any other damaged
components.
Replace the fuse, the Gate
Driver Board, or the
complete drive, as needed.
No
Yes
Yes
No
No
Restore incoming power to
the drive.
OK
Summary of Contents for Allen-Bradley IMPACT 1336 Series
Page 1: ...Troubleshooting Manual 1336 IMPACT Adjustable Frequency AC Drive 519 597 kW 700 800 HP ...
Page 174: ...7 14 Schematics Publication 1336 IMPACT 6 8 November 2002 This Page Intentionally Left Blank ...
Page 175: ...Notes Publication 1336 IMPACT 6 8 November 2002 ...
Page 176: ...N 2 Publication 1336 IMPACT 6 8 November 2002 ...
Page 177: ...N 3 Publication 1336 IMPACT 6 8 November 2002 ...
Page 178: ...N 4 Publication 1336 IMPACT 6 8 November 2002 ...
Page 179: ...N 5 Publication 1336 IMPACT 6 8 November 2002 ...
Page 180: ...N 6 Publication 1336 IMPACT 6 8 November 2002 ...
Page 181: ...N 7 Publication 1336 IMPACT 6 8 November 2002 ...
Page 182: ...N 8 Publication 1336 IMPACT 6 8 November 2002 ...
Page 183: ...N 9 Publication 1336 IMPACT 6 8 November 2002 ...
Page 184: ...N 10 Publication 1336 IMPACT 6 8 November 2002 ...
Page 185: ...N 11 Publication 1336 IMPACT 6 8 November 2002 ...
Page 186: ...N 12 Publication 1336 IMPACT 6 8 November 2002 ...
Page 187: ...N 13 Publication 1336 IMPACT 6 8 November 2002 ...
Page 188: ...N 14 Publication 1336 IMPACT 6 8 November 2002 ...
Page 194: ...Index I 6 Publication 1336 IMPACT 6 8 November 2002 This Page Intentionally Left Blank ...
Page 195: ......