28
Rockwell Automation Publication 440G-UM001C-EN-P - June 2019
Chapter 5
Commissioning
Figure 10 - Wiring
First Time Learn
Apply power to the switch without the actuator present. After the switch
completes the power-sequence (approximately eight seconds), the LED flashes
green eight times, indicating the total number of times a new actuator can be
learned. This LED sequence repeats until an actuator is placed in the sensing
field, or “guard-closed” position, of the switch.
Table 12 - Commissioning Process for Unique Coded Switches
Learning Additional
Replacement Actuators
The switch will automatically start a new learn process when a unique coded
replacement actuator is placed in the sensing field, or “guard-closed” position,
of the switch.
Red (Safety A+)
Pink (Safety B)
Green (Lock)
White (Aux)
Blue (Gnd)
Grey (Safety A)
Yellow (Safety B+)
Brown (+24)
24V DC Com
+24V DC
889D-F8NB-x
or
889D-F8AB-x
Lock
NC
NC
NC
Diag
Status
440G-LZ
State
Approximate Duration
LED Indicators
Step 1: Actuator Present
15 seconds
Flashing green, slow
Step 2: Verifying Actuator
15 seconds
Flashing red/green, slow
Step 3: Programming Switch
15 seconds
Flashing red/green, fast
Step 4: Program Finalization
15 seconds
Flashing green (number of times a
new actuator can be learned)
Step 5: Ready State
—
Solid red (Power to Release)
Solid green (Power to Lock)
IMPORTANT
When the switch learns a new actuator, it no longer recognizes previously
learned actuators.