336
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 8
Metering and Diagnostics
Table 422 - L2 Apparent Power (Parameter 73)
L3 Apparent Power
L3 Apparent Power (Parameter 74) reports the apparent power for line 3 in kVA
or MVA depending on the configuration value for Power Scale (Parameter 377).
When Voltage Mode (Parameter 352) is set to any
Delta
base setting, L3
Apparent Power is set to 0. When Single or Three Phase (Parameter 176) is set to
Single Phase
, L3 Apparent Power is set to 0.
Table 423 - L3 Apparent Power (Parameter 74)
Total Apparent Power
Total Apparent Power (Parameter 75) reports the total apparent power of the
monitored power conductors in kVA or MVA depending on the configuration
value for Power Scale (Parameter 377). When Single or Three Phase (Parameter
176) is set to
Three Phase
, Total Apparent Power is calculated as follows:
Total Apparent Power = (L1 Apparent Power + L2 Apparent Power + L3 Apparent
Power)
When Single or Three Phase (Parameter 176) is set to
Single Phase
, Total
Apparent Power is calculated as follows:
Total Apparent Power = (L1 Apparent Power + L2 Apparent Power)
Default Value
0.000
Minimum Value
0.000
Maximum Value
2000000.000
Parameter Type
DINT
Size (Bytes)
4
Scaling Factor
1000
Units
kVA or MVA
Default Value
0.000
Minimum Value
0.000
Maximum Value
2000000.000
Parameter Type
DINT
Size (Bytes)
4
Scaling Factor
1000
Units
kVA or MVA
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......