Publication 1756-UM001A-EN-P - September 2000
Communicate with a PanelView
™
Terminal Over a ControlNet
™
Network
9-5
Step 2: Add the PanelView
Terminal
A.
Right-click
name_of_local_cnb
and select
New Module
.
B.
Select
PanelView
and click
OK
.
C.
Type a name for the PanelView terminal.
D.
Type or select the ControlNet node number of the terminal.
E.
Does the terminal read more than 8 words of scheduled data
(16-bit integers) or write more than 8 words of scheduled data?
F.
How closely must the PanelView terminal match the information
on this tab?
42399
42400
If:
Then select
up to 8
Data - 8 INT
more than 8
Data - 32 INT
EXAMPLE
Select a Comm Format
If the PanelView terminal writes:
•
45 time-critical bits (45
÷
16 = 3 integers)
•
4 time-critical integers
Then the terminal writes 7 time-critical
integers, so select
Data - 8 INT
.
If this information must match:
Then select
all, including minor revision number
Exact Match
all
except
the minor revision number
Compatible Module
none
Disable Keying
Summary of Contents for Allen-Bradley ControlLogix 1756-L Series
Page 1: ...ControlLogix System 1756 Lx User Manual ...
Page 10: ...Publication 1756 UM001A EN P September 2000 Table of Contents vi ...
Page 64: ...Publication 1756 UM001A EN P September 2000 4 16 Communicate with 1756 I O Notes ...
Page 152: ...Publication 1756 UM001A EN P September 2000 11 4 Monitor Connections Notes ...
Page 160: ...Publication 1756 UM001A EN P September 2000 12 8 Communicate with a DeviceNet Device Notes ...
Page 204: ...Publication 1756 UM001A EN P September 2000 15 16 Communicate Over a Remote I O Network Notes ...
Page 266: ...Publication 1756 UM001A EN P September 2000 21 10 Maintain the Battery Notes ...
Page 286: ...Publication 1756 UM001A EN P September 2000 B 18 Estimate Execution Time Notes ...
Page 300: ...Publication 1756 UM001A EN P September 2000 C 14 Estimate Memory Use Notes ...
Page 305: ......
Page 307: ...ControlLogix System User Manual ...