Rockwell Automation Allen-Bradley 46DFA-L2LBT1-A2 Installation Instructions Manual Download Page 7

Rockwell Automation Publication 46DFA-IN001A-EN-P - January 2019

7

PHOTOSWITCH DIN  Rail Fiber Optic Amplifier

Light Source Intensity Adjustment Feature

The light source intensity can be automatically or manually adjusted.

Automatic Adjustment

The light source intensity is automatically adjusted when teaching is 

initiated. The light source level is settable to 15 steps for the 500 µs, 

ms, and 32 ms modes and 12 steps for the 50 µs mode. Larger numbers 

indicate higher light intensity.

Manual Adjustment

The sensitivity teach procedure does not change the light source 

intensity. Adjust the light source level manually when Teach errors occur 

(see Teach Errors i

Table 1 on page 5

).

Figure 21 - Cat. No. 46DFA-L2LBT1-X Dimensions [mm (in.)]

UL: Maximum ambient temperature: 50 °C (122 °F) for single use, 40 

°C (104 °F) for an installation with two or more units connected.

IMPORTANT

Light source intensity can be low depending on the level set 
in which the light spot cannot be seen.

0 (0.39)

5 (0.2)

11.5

(0.45)

3

(0.12)

3.5 (0.14)

19.5 (0.77)

16

(0.63)

2-

Ø

 3.2 x 5.2 (0.12 x 0.2) elongate hole

Mounting bracket 

(available separately)

2-

Ø

3.2 (0.12)

Optical transmission window

14.5

(0.57)

10.5

(0.41)

29 (1.14)

32.4

(1.27)

72 (2.83)

77 (3.03)

29 (1.14)

36.5 (1.44)

16

(0.63)

M12 pigtail

Table 

2 - S

pecifications

Attribute

46DFA-L2LBT1-A2, 46DFA-L2LBT1-F4, 46DFAL2LBT1-Y4

Operating voltage

12…24V DC, Class 2/Ripple 10% or less

Power consumption

Normal mode: 1000 mW or less (40 mA or less at 24V)

ECO mode: 750 mW or less (30 mA or less at 24V)

Output types

NPN open collector output/Load current 100 mA (30V DC, Class 2) or less/

Residual voltage: 2V or less

PNP open collector output/Load Current 100 mA(30V DC class 2) or less/ 

residual voltage: 2V or less

Output modes

Selectable Light Operate (L.O.) or Dark Operate (D.O.)

Output Timers

ON delay, Off delay, ON/OFF delay, Resettable One-shot, Timer off

Delay timer: 1...9999 ms (set in millisecond)

Output response time

Selectable: 50 µs, 500 µs, 4 ms, and 32 ms. The default setting is 500 µs.

Light source (wavelength)

Four-element (AlGaInp) LED (660 nm)

User interface

Operating indicator, setting/teaching indicator, 

L.O./D.O. Indicator: orange LED

Display

Received light level: 4 digits in red LED (50 µs mode [(0…3800), 5

00 μs

/

4 ms/32

 ms mode (0…9999)]

Threshold: 4 digits in green LED (50 µs mode [(0…3500, 

500 μs/4 ms/

32 ms 

mode (0…9700)]

Adjustment options

Teach and Set Button (SET)

Threshold and Configuration adjustment (UP/DOWN)

Sensitivity setting

Two-point teach/max sensitivity teach/full auto teach/position teach and 

window mode teach

Sensitivity adjustment function

Provided

Light source level adjustment

Provided (auto/manual)

Mutual interference prevention

Up to 8 units (500

 μ

s, 4 ms, and 32 ms modes only)

Protection circuit

Power reverse connection/output short-circuit protection

Material

Polycarbonate

Wiring options

2 m (6.56 ft) attached cable [outer dimension: 4.2 mm (0.16 in.) dia.] 

0.2 mm

2

 (0.007 in.) 4 cores

Weight

Approximately 75 g (2.64 oz)

Ambient light

Illumination on light receiving surface: 3500 lx or less (incandescent 

lamp)

Ambient temperature

1…5 adjacent units in operation: -25…+55 °C (-13…+131 °F)

6 or more adjacent units in operation: -25…+50 °C (-13…+122 °F)

Storage: -40…+70 °C (-40…+158 °F) (nonfreezing, noncondensing)

Ambient humidity

35…85% RH (noncondensing)

MTTF

53 years

Protective structure

IP40

Vibration

10…55 Hz/1.5 mm () double amplitude/2 hours each in X, Y, and Z 

directions

Shock

500 m/s

2

 /3 times each in X, Y, and Z directions

Dielectric withstanding

1000V AC for 1 minute

Insulation resistance

500V DC mega, 20 MΩ

Summary of Contents for Allen-Bradley 46DFA-L2LBT1-A2

Page 1: ...using pin 2 when connected using IO Link enables continuous sensor monitoring without impact on response time needs Fast response speeds of 50 s 500 s 4 ms and 32 ms allows operators easy adaptation o...

Page 2: ...cable unit L D Operating Indicator Orange Setting Teach Indicator Orange UP DOWN button To adjust threshold To select settings L Light Operate D Dark Operate indicator Orange Received Light Level Red...

Page 3: ...Use the bu on to specify between 1 and 9999 ms in increments of 1ms The ini al se ng is 1 ms source level adjustment The light source intensity can be adjusted both automa cally and manually NOTE The...

Page 4: ...al Opera on ECO mode Used to reduce power consump on Approx 15 seconds a er the se ng the 7 segment indica on turns OFF Pressng any bu on turns the display on and turns it o again a er 15 seconds Bu o...

Page 5: ...Service Func on Command or Index 60 Strandard I O Return to the Se ng mode go to Received light level indica on and select Standard indica on Then teaching can be conducted as described in 5 2 Teachi...