24
Rockwell Automation Publication 440R-UM010A-EN-P - May 2015
Chapter 4
Configuration
Range Switch Setting
The Range switch sets the maximum time for the delay. The range is then
adjusted by the Time switch setting.
Table 3 - Range Switch Setting
Time Switch Setting
The Time switch sets the adjustment to the Range.
Table 4 - Time Switch Setting
Configuration Switches
Use a small slotted screwdriver to set the switches to the desired setting. The
configuration switches are multi-position switches with a limited rotation.
Figure 20 - Configuration Switch Adjustment
Range Switch Setting
Maximum Delay Time
Range Switch Setting
Maximum Delay Time
0
0.5 s without 10%
(1)
(1) To use the Range setting of zero, the Time setting must be set to something other than 1.
5
30 s
1
1 s
6
1 min
2
3 s
7
3 min
3
5 s
8
10 min
4
10 s
9
30 min
Time Switch Setting
Delay Adjustment (%)
Time Switch Setting
Delay Adjustment (%)
1
10
6
60
2
20
7
70
3
30
8
80
4
40
9
90
5
50
10
100
EXAMPLE
With the Range set to 4 and Time set to 4, the delay is:
10 seconds x 40% / 100 = 4 seconds
IMPORTANT
Adjust the switches gently and do not turn past the mechanical stops.
0
Mechanical Stops
Rotate along arrow