Mounting the Kinetix 5500 Drive System
Chapter 3
Drilling Hole Patterns
Hole patterns for drives mounted in zero-stack or shared-bus configuration are
provided for mounting your drives to the panel. Drives with the highest power
rating are always mounted to the left of any drive with a lower power rating in
shared-bus configurations:
•
Frame 1 drives can be followed by only another frame 1 drive.
•
Frame 2 drives can be followed by frame 1 drives or another frame 2 drive.
•
Frame 3 drives can be followed by frame 1, frame 2, or another frame 3
drive.
•
Mount Bulletin 2198 capacitor modules in the rightmost position.
–
Capacitor modules have the same hole pattern as frame 2 drives.
–
Only Shared DC, Shared AC/DC, and Shared AC/DC, hybrid
configurations are compatible with Bulletin 2198 capacitor modules.
Table 17 - Hole Pattern Overview
Table 18 - Capacitor Module Support
Drive Cat. No.
Frame Size
Frame Size Patterns
Page
2198-H003-ERS
x
2198-H008-ERS
x
Frame 1
As many as eight frame 1 drives
2198-H015-ERS
x
2198-H025-ERS
x
2198-H040-ERS
x
Frame 2
As many as 8 frame 2 drives
One frame 2 drive followed by as many as seven frame 1 drives
2198-H070-ERS
x
Frame 3
As many as 8 frame 3 drives
One frame 3 drive followed by as many as seven frame 1 drives
One frame 3 drive followed by as many as seven frame 2 drives
Drive Cat. No.
Fram
e S
ize
St
an
da
lo
ne
Single
Ph
ase
Op
er
at
io
n
Three-phase Operation
Standalone
Shared DC
Shared AC/DC
Shared AC/DC
Hybrid
Number of capacitor modules connected, max
2198-H003-ERS
x
(1)
(1) Catalog number 2198-H003-ERS and any drive in standalone single-phase operation is not compatible with the Kinetix 5500
capacitor module.
1
0
0
2198-H008-ERS
x
(1)
1
2
2198-H015-ERS
x
(1)
2
4
2198-H025-ERS
x
N/A
3
2198-H040-ERS
x
2198-H070-ERS
x
3
4